Space Temperature Sensor
The Space Temperature Sensor is installed on the wall in the space served by the rooftop unit
to provide feedback of space temperature conditions to the controller. The unit will not operate
without a properly installed Space Temperature Sensor. The sensor should be installed
approximately 4 feet above the finished floor or per site requirements and should be located to
avoid exposure to direct sunlight, other heat sources, and drafts from HVAC supply vents.
Wiring Example:
No wiring for the push button override feature is required if the jumper in the
sensor is left in the factory default “Short Sensor” position. If the jumper is moved to the
“Separate Input” position, the O/R terminals must be wired to the Remote Start Stop digital input
for the push button override feature to be functional. In some cases, controller terminal J6 may
be factory wired to a more easily accessible set of terminals in the unit control box. Refer to the
wiring diagram supplied with the unit for additional details.