![Daikin iLINQ Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/daikin/ilinq/ilinq_quick-start-manual_501833022.webp)
DAIKIN
ILINQ
QUICK START GUIDE
22
In Force Vent Mode, the blower speed and the economizer damper position can be set to user-
defined values. This can be used to help during unit startup when airflow may need to confirmed
or adjusted and the economizer damper position settings need to be determined to meet fresh
air requirements.
Force Mode is intended to be used for short time intervals for a startup or test/balance
procedures. If the unit has been in a Force Mode for longer than 30 minutes without any
changes being made to any of the Force Mode settings, the unit returns to normal operation.
If it is determined that economizer minimum positions or blower speed settings need to be
adjusted to meet airflow requirements for the site or to match the airflow tables in the unit IO
manual, navigate to the Parameters
→
Econ/Blower Settings screen in the Navigation Menu.
Содержание iLINQ
Страница 1: ...Daikin iLINQ Quick Start Guide QSG ILINQA ...
Страница 24: ...DAIKIN ILINQ QUICK START GUIDE 24 ...