Installation manual
22
HXHD125A7V1B
VRVIII system indoor unit
4PW62584-1A – 11.2010
1
Unit
2
Rear part of the remote controller
3
Front part of the remote controller
4
Wired from the rear
5
Wired from the top
6
Notch the part for the wiring to pass through with nippers,
etc.
Connect the terminals on top of the front part of the remote
controller and the terminals inside the unit (P1 to X3M: P1, P2 to
X3M: P2).
4
Reattach the upper part of the remote controller.
First begin fitting from the clips at the
bottom.
Connection to a benefit kWh rate power supply
Electricity companies throughout the world work hard to provide
reliable electric service at competitive prices and are often authorized
to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates,
Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such benefit rate power
supply delivery systems.
Consult with the electricity company acting as provider at the site
where this equipment is to be installed to know whether it is
appropriate to connect the equipment in one of the benefit kWh rate
power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power
supply, the electricity company is allowed to:
■
interrupt power supply to the equipment for certain periods of
time;
■
demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the
unit switches into forced off mode. At that moment, the unit
compressors will not operate.
NOTICE
Peel the shield for the part that has to
pass through the inside of the remote
controller case (
l
).
NOTICE
Be careful not to pinch the wiring when attaching.
P1
P2
6
2
1
3
4
5
P1
P2
P2
P1
P2
P1
X3M
X3M
1
NOTICE
A benefit kWh rate power supply is only possible for the
indoor unit. For compressor reliability reasons it is not
allowed to connect the outdoor unit to such a power
supply.
INFORMATION
For a benefit kWh rate power supply like illustrated
below as type 1
During the period that the benefit kWh rate is active and
power supply is continuous, then stand-by power
consumption of the inverter PCB is possible.