8.6.
Connection
Use the appropriate cables, connect the power supply, multi tenant
power supply, and communication cable(s) to the appropriate
terminals as shown below.
1
Power supply
2
Multi tenant power supply
3
Transmission wiring
4
User interface wiring
5
Stress relief
Refer also to the wiring diagram for further details.
For the connections of optional PCB's please refer to the respective
installation manual.
Installation and connection of the remote controller
The unit is equipped with a remote controller offering user-friendly
way to set up, use and maintain the unit. Before operating the remote
controller, follow this installation procedure.
1
Remove the front part of the remote controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the remote controller, and
remove the front part of the remote
controller.
2
Fasten the remote controller on a flat
surface.
3
Wire the unit.
WARNING
The length of the conductors between the power supply
stress relief and the terminal block itself must be such that
the current-carrying wires are tautened before the earth
wire is, in case the power supply is pulled loose from the
stress relief.
2
5
5
4
3
5
1
INFORMATION
■
The wiring for connection is not included.
■
The remote controller, delivered in a kit, has to be
mounted indoors.
■
When the remote controller thermostat function is
used, select the installation location considering it
should be a place:
■
where the average temperature in the room can be
detected,
■
that is not exposed to direct sunlight,
■
that is not near a heat source,
■
that is not affected by outside air or air draught due
to e.g. door opening/closing,
■
where the display is kept clean,
■
where the temperature is between 0°C and 50°C,
■
where the relative humidity is maximum 80%.
NOTICE
Be careful not to distort the shape of the lower part of
the remote controller by over tightening the mounting
screws.
INFORMATION
If next to the standard remote controller the optional
remote controller is installed as well:
■
Connect the electrical wires of both remote
controllers in the same way like described below.
■
Select a master and a slave remote controller by
switching the SS1 selector switch.
Only the remote controller set as master can work as
room thermostat.
1
S
S
M
PCB
SS1
S
Slave
M
Master