CONDENSING UNIT

HEAT PUMP

INSTALLATION & SERVICE REFERENCE

IMPORTANT SAFETY INSTRUCTIONS

The following symbols and labels are used throughout this manual 

to indicate immediate or potential safety hazards.  It is the owner’s 

and installer’s responsibility to read and comply with all safety in-

formation and instructions accompanying these symbols.  Failure to 

heed safety information increases the risk of personal injury, property 

damage, and/or product damage.

Imortant Safety Instructions

 ......................................1

Shipping Inspections

 ......................................................1

Codes & Regulations

 ......................................................1

Installation Clearances

 ...............................................2

Rooftop Installations

 ...................................................2

Safe Refrigerant Handling

 ..........................................2

Refrigerant Lines

 ..........................................................3

Existing Line Sets

 ...........................................................3

Refrigerant Line Connections

 ....................................4

Leak Testing (Nitrogen or Nirtogen-Traced)

 ..........4

System Evacuation

 .........................................................4

Electrical Connections

 ................................................5

Overcurrent Protection

 ..............................................5

High Voltage Connections

 ...........................................5

Low Voltage Connections

 ............................................5

System Start Up

..............................................................5 

Charge Verification

 .......................................................6

Final Charge Adjustment

 .............................................6

Fixed Orifice

 ....................................................................6

Expansion Valve System

 ................................................8

Heat Pump - Heating Cycle

 ............................................8

Troubleshooting Information

 .....................................9

Long Line Set Application R-410A

 .............................10

Start Up Checklist

 .......................................................19

SHIPPING INSPECTION

Always keep the unit upright; laying the unit on its side or top may 

cause equipment damage. Shipping damage, and subsequent 

investigation is the responsibility of the carrier.  Verify the model 

number, specifications, electrical characteristics, and accessories are 

correct prior to installation. The distributor or manufacturer will not 

accept claims from dealers for transportation damage or installation 

of incorrectly shipped units.

CODES & REGULATIONS

This product is designed and manufactured to comply with national 

codes. Installation in accordance with such codes and/or prevailing 

local codes/regulations is the responsibility of the installer.  The 

manufacturer assumes no responsibility for equipment installed 

in violation of any codes or regulations.  Rated performance is 

achieved after 20 hours of operation. Rated performance is deliv-

ered at the specified airflow. See outdoor unit specification sheet 

for  split  system  models  or  product  specification  sheet  for  pack

-

aged  and  light  commercial  models.  Specification  sheets  can  be 

found at www.goodmanmfg.com for Goodman® brand products or  

ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, 

ADJUST, SERVICE, MAINTENANCE OR REPAIR (HEREIN

-

AFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS 

MANUAL SHOULD SERVICE THE EQUIPMENT.  THE MANU

-

FACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY 

OR PROPERTY DAMAGE ARISING FROM IMPROPER SER

-

VICE OR SERVICE PROCEDURES.  IF YOU SERVICE THIS 

UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR 

PROPERTY DAMAGE WHICH MAY RESULT.  IN ADDITION, IN 

JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES 

TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANU

-

AL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE 

EQUIPMENT.  

 

IMPROPER INSTALLATION, ADJUSTMENT, SERVICING, 

MAINTENANCE OR REPAIR OF THE EQUIPMENT SPECIFIED 

IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, 

SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS 

MANUAL WITHOUT PROPER TRAINING MAY RESULT IN 

PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJU

-

RY OR DEATH.

WARNING

WARNING

DO NOT BYPASS SAFETY DEVICES

Scroll equipped units should never be used to evacuate the air

conditioning system. Vacuums this low can cause internal

electrical arcing resulting in a damaged or failed compressor.

Содержание Goodman GSZ140481A

Страница 1: ...s for transportation damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with national codes Installation in accordance with such...

Страница 2: ...struc ture maintains minimum service clearance Corner installations are strongly discouraged OK OK AA AA A A C C C C OK OK OK OK NOT RECOMMENDED AA AA AA AA AA B B B B Model Type A B C AA Residential...

Страница 3: ...rigerant lines through a foundation or wall openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation Any gap between foun dation or wall...

Страница 4: ...pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 450 psig Leak test the system using dry nitrogen and soapy water to identify leaks If you p...

Страница 5: ...y units require 25VA minimum and heat pump units require 40VA minimum Low voltage wiring for two stage units depends on the thermostat used and the number of control wires between the indoor unit and...

Страница 6: ...to meet tandards to AHRI AHRI s NOTICE Operating the compressor with the suction valve closed is not covered by the warranty and will cause serious compressor damage FINAL CHARGE ADJUSTMENT Airflow a...

Страница 7: ...n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE F SUCTION PRESSURE PSIG...

Страница 8: ...only be performed by qualified service personnel Advanced Adjustment Recommendations SUPERHEAT FORMULA SUCTION LINE TEMPERA TURE SATURATED SUCTION TEMPERATURE 1 Clamp a pipe clamp thermometer 4 6 fro...

Страница 9: ...mproper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Lim...

Страница 10: ...line insulation is required to reduce loss of capacity if the line set passes through a high ambient temperature zone The liquid line must be insulated if more than 50 feet of liquid line will pass t...

Страница 11: ...t lines must not touch wall Strap Sleeve Strap Sleeve Wire Tie Wire Tie PVC Pipe Caulk Outside Wall Armaflex Wrapped Suction Line Liquid Line Wood Block Between Studs IMPORTANT Refrigerant lines must...

Страница 12: ...ng Horizontal 8 Final Charge Adjustment All units must have refrigerant charge verified by proper adjustment of subcooling at the indoor unit after initial charge adjustment per Section 3 Proper adjus...

Страница 13: ...ructed of standard refrigerant fitting See Figure 2 1 Liquid line solenoid not required if non bleed TXV is used on the outdoor unit 1 Suction line must be sloped continuously towards the indoor unit...

Страница 14: ...rt and secure the inverted loop to the nearest point on the indoor unit or adjacent structure 4 An accumulator is required to be added external to the outdoor unit within 2 linear feet of the outdoor...

Страница 15: ...Properly size the suction line to minimize capac ity loss 3 4 7 8 1 1 8 90 short radius 1 7 2 2 3 90 long radius 1 5 1 7 1 6 45 0 7 0 8 1 Type of Elbow Fitting Inside Diameter inches Table 3 1 Losses...

Страница 16: ...r 2 ton two stage heat pump applications 3 7 8 vapor line is not approved for 3 ton two stage heat pump applications over 80 feet 4 1 1 8 vapor line is not approved for 4 ton and 5 ton two stage heat...

Страница 17: ...8 liquid line only 15 30 45 60 75 90 105 3 8 liquid line 5 8 suction line 16 32 47 63 79 95 110 3 8 liquid line 3 4 suction line 17 34 50 67 84 101 117 3 8 liquid line 7 8 suction line 18 35 53 70 88...

Страница 18: ...l hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the ou...

Страница 19: ...Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING SH SC Line...

Страница 20: ...ight for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not requ...