background image

6

When opening valves with retainers, open each valve only until the 

top of the stem is 1/8” from the retainer.  To avoid loss of refrigerant, 

DO NOT apply pressure to the retainer. When opening valves without 

a retainer remove service valve cap and insert a hex wrench into 

the valve stem and back out the stem by turning the hex wrench 

counterclockwise. Open the valve until it contacts the rolled lip of 

the valve body.

NOTE:

 These are not back-seating valves. It is not necessary to 

force the stem tightly against the rolled lip. 
After the refrigerant charge has bled into the system, open the liquid 

service valve. The service valve cap is the secondary seal for the 

valve and must be properly tightened to prevent leaks. Make sure 

cap is clean and apply refrigerant oil to threads and sealing surface 

on inside of cap. Tighten cap finger-tight and then tighten additional 

1/6 of a turn (1 wrench flat), or to the following specification,  to 

properly seat the sealing surfaces.

 

1. 3/8” valve to 5 - 10 in-lbs

 

2. 5/8” valve to 5 - 20 in-lbs

 

3. 3/4” valve to 5 - 20 in-lbs

 

4. 7/8” valve to 5 - 20 in-lbs

Do not introduce liquid refrigerant from the cylinder into the crankcase 

of the compressor as this may damage the compressor.

1. 

Break vacuum by fully opening liquid and suction base valves.  

2.  Set thermostat to call for cooling.  Check indoor and outdoor 

fan operation and allow system to stabilize for 20 minutes for 

expansion valves.

CHARGE VERIFICATION

REFRIGERANT UNDER PRESSURE!

 

• Do not overcharge system with refrigerant.

• Do not operate unit in a vacuum or at negative pressure.

Failure to follow proper procedures may cause 

property damage, personal injury or death.

Use refrigerant certified 

 standards. Used refrigerant

may cause compressor damage.  Most portable machines

cannot clean used refrigerant to meet 

tandards.

to AHRI

AHRI s

NOTICE

Operating the compressor with the suction valve closed is not

covered by the warranty and will cause serious

compressor damage.

FINAL CHARGE ADJUSTMENT

Airflow and Total Static Pressure for the indoor unit should be 

verified before attempting to charge system.

1. 

Total static pressure is .5” WC or less.

2. 

Airflow is correct for installed unit.

3. 

Airflow tables are in the installation manual and Spec Sheet 

for Indoor Unit.

4.  Complete charging information are in Service Manual 

RS6200006

NOTE: Superheat adjustments should not be made until 

indoor ambient conditions have stabilized. This could 

take up to 24 hours depending on indoor temperature 

and humidity. Before checking superheat run the unit 

in cooling for 10-15 minutes or until refrigerant 

pressures stabilize. Use the following guidelines and 

methods to check unit operation and ensure that the 

refrigerant charge is within limits. 

The outdoor temperature must be 60°F or higher. Set the room 

thermostat to COOL, fan switch to AUTO, and set the temperature 

control well below room temperature.

Units matched with indoor coils equipped with a non-adjustable 

TXV should be charged by Subcooling only. Superheat on 

indoor coils with adjustable TXV valves are factory set and no 

adjustment is normally required during startup. Only in unique 

applications due to refrigerant line length, differences in height 

between the indoor and outdoor unit and refrigerant tubing sizes 

or poor performance should Superheat setting require adjustment. 

These adjustments should only be performed by qualified service 

personnel. For detailed charge and TXV adjustments refer to the 

appropriate Service Manual.

55

57

59

61

63

65

67

69

71

10

13

17

20

23

26

29

30

31

8

11

14

16

19

22

26

27

29

5

8

10

13

15

19

23

24

25

---

---

6

9

11

15

20

21

23

---

---

---

---

7

12

17

18

20

---

---

---

---

---

8

13

15

16

---

---

---

---

---

7

10

11

13

---

---

---

---

---

---

7

8

10

---

---

---

---

---

---

---

7

8

---

---

---

---

---

---

---

---

7

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

SYSTEM SUPERHEAT (+/- 1°F)

Indoor Wet Bulb Temperature, °F

Outdoor Dry Bulb 

Temperature, °F

60
65
70

105
110
115

75
80
85
90
95

100

Содержание Goodman GSZ140481A

Страница 1: ...s for transportation damage or installation of incorrectly shipped units CODES REGULATIONS This product is designed and manufactured to comply with national codes Installation in accordance with such...

Страница 2: ...struc ture maintains minimum service clearance Corner installations are strongly discouraged OK OK AA AA A A C C C C OK OK OK OK NOT RECOMMENDED AA AA AA AA AA B B B B Model Type A B C AA Residential...

Страница 3: ...rigerant lines through a foundation or wall openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation Any gap between foun dation or wall...

Страница 4: ...pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 450 psig Leak test the system using dry nitrogen and soapy water to identify leaks If you p...

Страница 5: ...y units require 25VA minimum and heat pump units require 40VA minimum Low voltage wiring for two stage units depends on the thermostat used and the number of control wires between the indoor unit and...

Страница 6: ...to meet tandards to AHRI AHRI s NOTICE Operating the compressor with the suction valve closed is not covered by the warranty and will cause serious compressor damage FINAL CHARGE ADJUSTMENT Airflow a...

Страница 7: ...n a 123 445 n a 125 475 n a 130 500 n a 134 525 n a 138 550 n a 142 575 n a 145 600 n a 149 625 n a 152 SATURATED LIQUID PRESSURE TEMPERATURE CHART SATURATED LIQUID TEMPERATURE F SUCTION PRESSURE PSIG...

Страница 8: ...only be performed by qualified service personnel Advanced Adjustment Recommendations SUPERHEAT FORMULA SUCTION LINE TEMPERA TURE SATURATED SUCTION TEMPERATURE 1 Clamp a pipe clamp thermometer 4 6 fro...

Страница 9: ...mproper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Lim...

Страница 10: ...line insulation is required to reduce loss of capacity if the line set passes through a high ambient temperature zone The liquid line must be insulated if more than 50 feet of liquid line will pass t...

Страница 11: ...t lines must not touch wall Strap Sleeve Strap Sleeve Wire Tie Wire Tie PVC Pipe Caulk Outside Wall Armaflex Wrapped Suction Line Liquid Line Wood Block Between Studs IMPORTANT Refrigerant lines must...

Страница 12: ...ng Horizontal 8 Final Charge Adjustment All units must have refrigerant charge verified by proper adjustment of subcooling at the indoor unit after initial charge adjustment per Section 3 Proper adjus...

Страница 13: ...ructed of standard refrigerant fitting See Figure 2 1 Liquid line solenoid not required if non bleed TXV is used on the outdoor unit 1 Suction line must be sloped continuously towards the indoor unit...

Страница 14: ...rt and secure the inverted loop to the nearest point on the indoor unit or adjacent structure 4 An accumulator is required to be added external to the outdoor unit within 2 linear feet of the outdoor...

Страница 15: ...Properly size the suction line to minimize capac ity loss 3 4 7 8 1 1 8 90 short radius 1 7 2 2 3 90 long radius 1 5 1 7 1 6 45 0 7 0 8 1 Type of Elbow Fitting Inside Diameter inches Table 3 1 Losses...

Страница 16: ...r 2 ton two stage heat pump applications 3 7 8 vapor line is not approved for 3 ton two stage heat pump applications over 80 feet 4 1 1 8 vapor line is not approved for 4 ton and 5 ton two stage heat...

Страница 17: ...8 liquid line only 15 30 45 60 75 90 105 3 8 liquid line 5 8 suction line 16 32 47 63 79 95 110 3 8 liquid line 3 4 suction line 17 34 50 67 84 101 117 3 8 liquid line 7 8 suction line 18 35 53 70 88...

Страница 18: ...l hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the ou...

Страница 19: ...Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING SH SC Line...

Страница 20: ...ight for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not requ...

Отзывы: