Systems • Introduction
3
• Introduction
2
Possible outdoor units using R-410A
2-1
Indoor unit capacity index
NOTE
1
e.g. Selected indoor units: F F FXSQ40
Connection ratio: 25 + 100 + 200 + 40 = 365
→
Possible outdoor unit: RXYQ12M
VRV II heat pump
Fixed combinations
Nr. of outdoors
Nr. of compressors
Nr. of connectable indoor units
Minimum capacity index
Maximum capacity index
RXYQ5M
RXYQ5M
1
1
8
63
163
RXYQ8M
RXYQ8M
1
2
13
100
260
RXYQ10M
RXYQ10M
1
2
16
125
325
RXYQ12M
RXYQ12M
1
2
20
150
390
RXYQ14M
RXYQ14M
1
3
20
175
455
RXYQ16M
RXYQ16M
1
3
20
200
520
RXYQ18M
RXYQ10M
2
4
20
225
585
RXYQ20M
RXYQ10M x 2
2
4
20
250
650
RXYQ22M
R RXYQ12M
2
4
22
275
715
RXYQ24M
R RXYQ14M
2
5
32
300
780
RXYQ26M
R RXYQ16M
2
5
32
325
845
RXYQ28M
R RXYQ16M
2
5
32
350
910
RXYQ30M
R RXYQ16M
2
6
32
375
975
RXYQ32M
RXYQ16M x 2
2
6
32
400
1,040
RXYQ34M
RXYQ10M x 2 + RXYQ14M
3
7
34
425
1,105
RXYQ36M
RXYQ10M x 2 + RXYQ16M
3
7
36
450
1,170
RXYQ38M
R R RXYQ16M
3
7
38
475
1,235
RXYQ40M
R R RXYQ16M
3
8
40
500
1,300
RXYQ42M
R RXYQ16M x 2
3
8
40
525
1,365
RXYQ44M
R RXYQ16M x 2
3
8
40
550
1,430
RXYQ46M
R RXYQ16M x 2
3
9
40
575
1,495
RXYQ48M
RXYQ16M x 3
3
9
40
600
1,560
Model
20
25
32
40
50
63
80
100
125
200
250
Capacity index
20
25
31.25
40
50
62.5
80
100
125
200
250