If the drain riser is installed inclined, the float switch
may malfunction and cause water leakage.
r
Make sure to use the drain hose (1), the elbow (10) and
the sealing material (Large) (8) attached to the indoor
unit as accessories.
To prevent the elbow from getting damaged by the
metal clamp (2) for upward and backward piping,
wrap the vinyl tape around the elbow 2 to 3 times so
that the tape covers more than the width of metal
clamp (2) leaving 3/8 - 5/8 in. (10 - 15 mm) from the
tip of the elbow (10) without wrapping as shown in
(KI
.
Fig. 30
For upward piping : shorter side
For backward piping : longer side
3/8-5/8 in.
(10-15 mm)
Elbow (10) (accessory)
Vinyl tape
Wrap with the width (approx. 13/16 in.
(20mm)) larger than metal clamp (2).
Insert the drain hose (1) and the elbow (10) to the
root of the drain socket. Tighten the metal clamp (2)
within the taped range of hose inserted tip with the
torque 1.00±0.11 lbf·ft. (1.35±0.15 N·m).
4GHGTVQ(KICPF
Fig. 31
Taped part
Drain hose (1) (accessory)
Insert without leaving any clearance
Metal clamp (2) (accessory)
Fix the metal clamp (2) so that the screw
head faces downward.
Indoor unit (Drain socket)
r
Do not tighten the metal clamp (2) with the torque more
VJCPVJGURGEKƂGFXCNWG
The socket, the drain hose (1), the elbow (10) or the
metal clamp (2) may be damaged.
(KZVJGOGVCNENCORUQVJCVVJGVKIJVGPGFRCTVOC[DG
in the range shown by
(KI
.
3.
Wrap the vinyl tape around the end of the metal
clamp (2) so that the sealing material (large) (8) to
DGWUGFCVVJGPGZVRTQEGUUOC[PQVDGFCOCIGF
with the clamp end or bend the tip of the metal
clamp (2) inward as shown.
4GHGTVQ(KI
Fig. 32-1
(Section A - A of Fig. 31)
Tightened part
< In case of bending the tip >
appro
x.
90°
Bend the tip without tearing
the sealing material (Large) (8).
Fig. 32-2
(Section A - A of Fig. 31)
Tightened part
< In case of sticking vinyl tape >
Vinyl
tape
appro
x.
90°
Stick vinyl tape without
tearing the sealing material
(Large) (8).
Insulate the metal clamp (2), the drain hose (1), the
elbow (10) with the attached sealing material (Large)
(8).
4GHGTVQ(KICPF
The metal clamp (2) causes condensation.
Fig. 33
Drain hose (1)
(accessory)
Metal clamp (2)
(accessory)
Sealing material (8)
(accessory)
Wrap the sealing
material so that the
clamp end side may be
doubled.
Start wrapping from
where the clamp is
tightened.
Содержание FXUQ PVJU Series
Страница 1: ...EDUS391437 F15 FXUQ PVJU 4 Way Blow Ceiling Suspended Type ...
Страница 2: ......
Страница 14: ...Sound Levels Reference Data EDUS391437 F15 12 FXUQ PVJU FXUQ30PVJU FXUQ36PVJU 4D090215A ...
Страница 36: ...Installation Manual EDUS391437 F15 34 FXUQ PVJU C 3P161684 8T ...
Страница 40: ...Detail of Optional Accessories EDUS391437 F15 38 FXUQ PVJU 1P383776 1 ...
Страница 41: ...EDUS391437 F15 Detail of Optional Accessories FXUQ PVJU 39 1P383776 1 ...
Страница 42: ......
Страница 43: ......