REMOTE CONTROL SETTING
10-2
Forced off and ON/OFF operation should be selected by
•
selecting the SECOND CODE NO. as shown in Table 4.
Table 4
External ON/OFF input
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Forced off
12 (22)
1
01*
ON/OFF operation
02
* factory set
Input A of forced off and ON/OFF operation work as shown
•
in Table 5.
Table 5
Forced off
ON/OFF operation
Input A “on” to force a stop
(remote controller reception
prohibited)
Unit operated by changing input
A from “off” to “on”
Input A “off” to allow remote
controller
Unit stopped by changing input A
from “on” to “off”
SETTING THE FILTER SIGN DISPLAY INTERVAL
10-3
Explain the following to the customer if the fi lter dirt settings
•
have been changed.
The fi lter sign display time is set to 2500 hours (equivalent
•
to 1 year’s use) when shipped.
The settings can be changed to not display.
•
When installing the unit in a dusty place, set the fi lter sign
•
display time to shorter intervals (1,250 hours).
Explain it to the customer that the fi lter needs to be cleaned
•
regularly to prevent clogging and also the time that is set.
Mode No.
FIRST CODE NO.
SECOND
CODE NO.
01
02
10 (20)
0
Filter dirt
low
high
1 (low/high)
Displayed time
(units: hours)
2500/
1250
10000/
5000
3
Filter sign display
ON
OFF
INSTALLATION OF THE OPTIONAL AIR FILTER
10-4
Purchase and install the air fi lter as in Table 6.
•
Table 6
Air fi lter
12 · 18 type
FIL 36-42
24 · 30 · 36 · 42 · 48 · 54 type
FIL 48-61
Take off the part on the bottom of the front panel.
(1)
Insert the air fi lter as far as it can go.
(2)
Air filter (optional accessories)
INSTALLATION OF THE ELECTRIC HEATER KIT
10-5
WARNING
All phases of the electrical installation must comply with
•
national, state, provincial, and local codes.
When connecting an electric heater, be sure to install an
•
earth leakage circuit breaker procured locally.
If an earth leakage circuit breaker is not installed, electric
•
shock or fi re may result.
Regarding the rated current of the earth leakage circuit
•
breaker to be installed, refer to the H.M.C.A. value indicated
on the manufacturer’s label or in a technical document.
The recommended rapid sensitive current and tripping time
•
are indicated below.
Recommended specifi cations of circuit breaker
Rapid sensitive current
30mA
Tripping time
0.1sec
Purchase and install the electric heater kit as in Table 7.
•
Also refer to the installation and operating instructions that
•
come with the electric heater kit.
The indoor unit fan operates at H speed during HEATER
•
operation.
Table 7
Model
Electric heater kit model name
HKR-
03
HKR-
05C
HKR-
06
HKR-
08C
HKR-
10C
HKR-
15C
HKR-
20C
12 type
18 type
1
24 type
1
30 · 36 type
1
1
42 type
1
1
1
1
2
48 · 54 type
1
1
1
1
2
2
1
: Auxiliary and Heat Pump Lockout: Electric heater opera-
tion with heat pump is allowed.
: Heat Pump Lockout: Only electric heater operation is
allowed. Heat pump and electric heater cannot operate at
the same time.
2
: Heat Pump Lockout: Only electric heater operation is al-
lowed. Heat pump and electric heater cannot operate at the
same time. In addition, acceptable 2 step heating control.