9-2  ELECTRICAL CHARACTERISTICS

Table 4

Units

Power  

supply

Fan motor

Model

Hz Volts

Voltage 

range

MCA MOP

kW

FLA

FXSQ05TAVJU

60

208V- 
230V

Max. 253V

Min.  187V

0.8

15

0.078 0.6

FXSQ07TAVJU

0.8

15

0.078 0.6

FXSQ09TAVJU

0.8

15

0.078 0.6

FXSQ12TAVJU

0.8

15

0.078 0.7

FXSQ15TAVJU

1.4

15

0.130 1.2

FXSQ18TAVJU

1.6

15

0.230 1.3

FXSQ24TAVJU

1.8

15

0.230 1.4

FXSQ30TAVJU

1.8

15

0.230 1.5

FXSQ36TAVJU

2.5

15

0.300 2.0

FXSQ48TAVJU

2.8

15

0.300 2.0

FXSQ54TAVJU

3.3

15

0.350 2.6

MCA: Min. Circuit Amps (A) ;  MOP: Max. Overcurrent Protective Device (A)

kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)

9-3  SPECIFICATION FOR FIELD SUPPLY FUSES 

AND WIRING

Table 5

Model

Power supply wiring

Remote controller wiring

Transmission wiring

MOP 

Size

Wiring

Size

FXSQ05TAVJU

15A

Wiring size 

and length 

must comply 

with local 

codes.

2-conductor, 

stranded 

nonshielded  

copper cable 

PVC/vinyl 

jacket  

(NOTE 2)

AWG18-16 

(0.75- 

1.25 mm

2

)

FXSQ07TAVJU

FXSQ09TAVJU

FXSQ12TAVJU

FXSQ15TAVJU

FXSQ18TAVJU

FXSQ24TAVJU

FXSQ30TAVJU

FXSQ36TAVJU

FXSQ48TAVJU

FXSQ54TAVJU

The lengths of remote controller wiring and transmission 
wiring are as follows:
(1)   Remote controller wiring (indoor unit - remote controller) 

 ..............................................................

Max. 1,640 ft. (500 m)

(2)  

Transmission wirings ... Total wiring length 6,560 ft. (2,000 m)

• 

Outdoor unit - Indoor unit ........

Max. 3,280 ft. (1,000 m)

• 

Outdoor unit - Branch Selector unit ...

Max. 3,280 ft. (1,000 m)

• 

Branch Selector unit - Indoor unit .....

Max. 3,280 ft. (1,000 m)

• 

Indoor unit - Indoor unit ..........

Max. 3,280 ft. (1,000 m)

NOTE 

1. 

Vinyl cord with sheath or cable (Insulated thickness :  
1/16 in. (1 mm) or more)

9-4  WIRING CONNECTION METHOD

 CAUTION FOR WIRING

• 

For connection to the terminal block, use ring type crimp 
style terminals with insulation sleeve or insulate the wirings 
properly.

Insulation sleeve

Ring type crimp 
style terminals

Wiring

Fig. 21

• 

Connect the terminal as shown in Fig. 22.

• 

Do not carry out soldering finish when stranded wires are 

used. (Otherwise, the loosening of wires may result in 
abnormal heat radiation.)

Use wires the same in size 

(if the air conditioner is 

in simultaneous multi operation)

Fig. 22

(Abnormal heating may occur if the wirings are not tight-
ened securely.)

• 

Use the required wirings, connect them securely and fix 
these wirings securely so that external force may not apply 

to the terminals.

• 

Use a proper screw driver for tightening the terminal 
screws. 
If an improper screw driver is used, it may damage the 
screw head and a proper tightening cannot be car ried out.

• 

If a terminal is over tightened, it may be damaged. 
Refer to the table shown below for tightening torque of 
terminals.
Table 6

Tightening torque 

[lbf·ft. (N·m)]

Terminal for remote controller and 
transmission wirings

0.65 ± 0.07  

(0.88 ± 0.08)

Terminal for power supply

0.965 ± 0.095 

(1.31 ± 0.13)

Ground terminal

• 

Do not carry out soldering finish when stranded wirings 

are used.

01_EN_3P184443-13Z.indd   14

2/15/2018   9:15:29

Содержание FXSQ05TAVJU

Страница 1: ...TAVJU FXSQ36TAVJU FXSQ07TAVJU FXSQ18TAVJU FXSQ48TAVJU FXSQ09TAVJU FXSQ24TAVJU FXSQ54TAVJU FXSQ12TAVJU FXSQ30TAVJU INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MA...

Страница 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Страница 3: ...contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Th...

Страница 4: ...Joint insulating material 6 Sealing material 7 Sealing material 8 Clamp Quantity 1 each 1 sheet 2 sheets 8 pcs Shape Thin 4 For liquid piping Thick 5 For gas piping Large Dark gray Medium Dark gray Na...

Страница 5: ...ote controller connected to the master unit if the system is in simultaneous multi operation Have you explained failure examples of 3 SELECTION OF INSTALLATION LOCATION Points of the operation explana...

Страница 6: ...oom where an elec tronic lighting type inverter or rapid start type fluorescent lamp is installed 2 Use hanging bolts for installation Investigate if the installation place can withstand the weight of...

Страница 7: ...e instal lation location and work on the refrigerant piping drain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the pi...

Страница 8: ...heet to pre vent weld spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust...

Страница 9: ...When making a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Sp...

Страница 10: ...ing beginning at the base Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE...

Страница 11: ...not deflect Refer to Fig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put...

Страница 12: ...rain pump stops and generate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection...

Страница 13: ...he connectors may not come off 3 Gradually pour 1 4 gal 1 of water from the air out let on the left side of the drain socket into the drain pan giving caution to avoid splashing water on the electric...

Страница 14: ...ed with the unit Insulation material eld supply Air inlet Air outlet Screws for duct anges 3 accessory Screws for duct anges 3 accessory Flange on air outlet side provided with the unit Fig 20 CAUTION...

Страница 15: ...m Outdoor unit Branch Selector unit Max 3 280 ft 1 000 m Branch Selector unit Indoor unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insu...

Страница 16: ...fixture if you have difficulty in performing this step Screws 2 points Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control b...

Страница 17: ...T P Remote controller Remote controller Remote controller L1 L2 option option option L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller control Outdoor unit Note There is n...

Страница 18: ...t A Wiring specification Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC...

Страница 19: ...be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume ad...

Страница 20: ...e 11 Remote controller indication Details Though the central ized control is not carried out the indication turns on The terminals T1 T2 for FORCED OFF on the indoor unit trans mission terminal block...

Страница 21: ...1804 HT 3P184443 13Z EM17A015A 5151 San Felipe Suite 500 Houston TX 77056...

Отзывы: