12

English

No. 3 system: When including BS unit

[ PRECAUTIONS ] 

1. If no earth leakage breaker is required, install a breaker or 

load switch with a fuse for the wiring. If an earth leakage 
breaker is required, make sure that the earth leakage 
breaker is designed to protect the air conditioner from 
ground faults, overloads, and short-circuiting.

2. The remote controller wiring (P1 and P2) and transmission 

wiring (F1 and F2) have no polarity.

10-3 CONTROL BY 2 REMOTE CONTROLLERS (Con-

trolling 1 indoor unit by 2 remote controllers)

• Set one of the remote controllers to main and the other to sub 

in the case of remote control with two remote controllers.

Switching Main/Sub

(1) Insert a 

 screwdriver into the clearance between the 

grooves of the lower casing and the upper casing to remove 
the upper casing. (2 grooves) (The remote controller PCB is 
attached to the upper casing.)

(2) Set the main/sub switch on one of the remote controller 

PCBs to sub. (Keep the switch of the other remote controller 
PCB set to main.)

10-4 COMPUTERISED CONTROL (FORCED OFF 

AND ON/OFF OPERATION) 

(1) Wire specifications and how to perform wiring 

• Connect the input from outside to terminals T1 and T2 of 

the terminal block for remote controller.

(2) Actuation 

• The following table explains FORCED OFF and ON/OFF 

OPERATIONS in response to Input A. 

(3) How to select FORCED OFF and ON/OFF OPERATION 

• Turn the power on and then use the remote controller to 

select operation. 

10-5 CENTRALIZED CONTROL 

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional control-
lers for centralized control.

11. FIELD SETTING

NOTE

• Before the test operation of the outdoor unit as explained in 

12. TEST OPERATION

, be sure to make the following field 

settings as explained in 

11. FIELD SETTING

.

Make sure the control box lids are closed on the indoor and 
outdoor units.
Field setting must be made from the remote controller in 
accordance with the installation condition.

• Setting can be made by changing the “MODE NO.”, “FIRST 

CODE NO.”, and “SECOND CODE NO.”.

Outdoor unit

BS unit

L

N

Indoor unit A

Remote controller

(option)

F

F

1

2

F

F

1

2

F

F

1

2

F

F

1

2

IN/D

IN/D

OUT/D

OUT/D

1

P

P

2

1

F

2

N

F

L

1

2

T T

1

P

2

P

Power supply

single phase

50Hz 220-240V

or

single phase

60Hz 220V

Lower part of 
remote controller

Upper part of 
remote controller

Insert the screwdriver here and gently work 
off the upper part of remote controller.

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum appli-
cable load of 15 V DC, 10 mA.

FORCED OFF

ON/OFF OPERATION

Input “ON” stops operation (impossible by 
remote controllers.)

Input OFF 

→ 

ON turns 

ON unit.

Input OFF enables control by remote con-
troller.

Input ON 

→ 

OFF turns 

OFF unit.

Only one remote 
controller needs to be 
changed if factory 
settings have 
remained untouched.

S

M

S

S

M

(Factory setting)

Remote controller 
PC board

F2

T1

T2

FORCED
OFF

Input A

01_EN_3PN06583-7N.fm  Page 12  Saturday, February 28, 2009  3:02 PM

Содержание FXMQ100PVE

Страница 1: ...ERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE ...

Страница 2: ...partment 9th of January 2009 DAIKIN INDUSTRIES LTD EN60335 2 40 DAIKIN TCF 024D9 12 2008 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC ...

Страница 3: ...icient strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualifie...

Страница 4: ...al oil or filled with oil vapor or spray like in kitchens Plastic parts may deteriorate which could eventually cause the unit to fall out of place or could lead to leaks Where corrosive gas like sulfurous gas exists Cop per tubing and brazed spots may corrode which could eventually lead to refrigerant leaks Where exposed to combustible gases and where vol atile flammable gas like thinner or gasoli...

Страница 5: ...way from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Name Washer 11 Wire fixing bracket 12 Wire fixing screw 13 Other Operation manual Installation manual Quantity 8 pcs 2 pcs 2 pcs Shape Remote controller Wired type Wireless type Heat pump type Cooling only type Items t...

Страница 6: ...r refer to the installation manual provided with the wireless remote controller Refer to 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the vibration of the ceiling after the installation holes are opened For details consult your construction or...

Страница 7: ...it refer to the installation manual provided to the outdoor unit Perform heat insulation work on both gas piping and liquid piping or otherwise water leakage may result Use the insulation material that withstands a temperature of 120 C Reinforce the insulation material for the refrigerant piping if the ambient temperature is high or otherwise dew conden sation may result on the surface of the insu...

Страница 8: ...erial 7 around the insula tion for fitting 4 and 5 for the joint flare nut part CAUTION Be sure to perform the heat insulation of the local piping up to the piping joint If the piping is exposed dew condensation may result Fur thermore a burn may be caused if a human body comes in contact with the piping Pipe size Tightening torque Flare dimensions A mm Flare shape φ 6 4 14 2 17 2N m 8 7 9 1 φ 9 5...

Страница 9: ...acket at 1 to 1 5 m intervals for the prevention of piping deflection Be sure to use the drain hose 2 and metal clamp 1 Insert the drain hose 2 deep into the base of the drain socket and securely fasten the metal clamp 1 within the taped part on the insertion front end of the hose Be sure to fasten the screw of the metal clamp 1 until the margin of the screw thread decreases to 4 mm or less NOTE B...

Страница 10: ...of the drain pump and others 3 Be sure to conduct heat insulation work on the follow ing portions or otherwise water leakage may occur as a result of dew condensation Drain piping indoors Drain socket On completion of the drainage check refer to the follow ing illustration and use the provided large sealing pad 6 and heat insulate the metal clamp 1 and drain hose 2 8 DUCT WORK Pay the utmost atten...

Страница 11: ... leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Allowable length of transmissi...

Страница 12: ... wiring neatly and attach the control box lid securely An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid 4 Put the control box lid and wrap the wire sealing material Small 10 around the wires so as to block the wire through holes CAUTION After all the wiring connections are done fill in any gaps in the through holes with putty or insulation...

Страница 13: ...orque N m Terminal block for remote controller and transmission wires 0 80 0 96 Terminal block for power supply 1 18 1 44 Power supply wiring Earth wiring Transmission wiring Remote controller wiring Fixing use Wire fixing screw 13 accessory Wire fixing bracket 12 accessory Clamp 8 accessory Electric wire Round crimp style terminal Attach insulation sleeve Connect the wires evenly Do not connect a...

Страница 14: ...n use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control 11 FIELD SETTING NOTE Before the test operation of the outdoor unit as explained in 12 TEST OPERATION be sure to make the following field settings as explained in 11 FIELD SET...

Страница 15: ...N OFF OPERATION button Then the operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic adjustment Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the air conditioner After the air conditioner runs approximately one to eight min utes the air conditioner will finish airflow adjustment automatically the operation lam...

Страница 16: ...not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that will be generated from interior finish work materials such as paint and adhesive agents may con taminate the air conditioner External Static Pressure MODE NO FIRST CODE NO SECOND CODE NO 30Pa 1 4 13 23 06 01 50Pa 02 60Pa 03 70Pa 04 80Pa 05 90Pa 06 100P...

Страница 17: ... 0904 HT 3PN06583 7N EM07A049D ...

Отзывы: