Specifications
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXLQ20MAVE
FXLQ25MAVE
FXLQ32MAVE
FXLQ40MAVE
FXLQ50MAVE
FXLQ63MAVE
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
0.3
0.3
0.6
0.6
0.6
0.6
Maximum fuse amps (MFA)
A
15
Full load amps (FLA)
A
0.2
0.2
0.5
0.5
0.5
0.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXLQ20MAVE
FXLQ25MAVE
FXLQ32MAVE
FXLQ40MAVE
FXLQ50MAVE
FXLQ63MAVE
Power Supply
Name
VE
Phase
1~
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
0.3
0.3
0.5
0.5
0.6
0.6
Maximum fuse amps (MFA)
A
15
Full load amps (FLA)
A
0.2
0.2
0.4
0.4
0.5
0.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
Содержание FXLQ25MAVE
Страница 1: ...technical data Floor Standing Unit FXLQ MAVE air conditioning systems...
Страница 2: ...air conditioning systems technical data Floor Standing Unit FXLQ MAVE...
Страница 3: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE VRV Systems Indoor Units 2...
Страница 5: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE VRV Systems Indoor Units 2...
Страница 23: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE 1 10 VRV Systems Indoor Units 20 10 Installation 10 2 Service space...