Installation

EDUS39-600-F7

21

FXLQ-M / FXNQ-M

• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or  
four times first, then screw in.

• Refer to the Table 2 for tightening torque.
• After inspecting pipe joints for gas leakage, be sure to insu-

late with the accessory joint insulation for fitting (3) (4) while 
referring to the figure below. Fasten both ends with clamps 
(6).
Wrap only the gas line side with the sealing pad (5). Bend 
the pad over the insulation for fitting (union) from above.

Use Table 3 as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque  suddenly 
increases. From that position, tighten the nut to the angle 
shown on Table 3 .

• Make absolutely sure to execute heat insulation works on 

the pipe-connecting section after checking gas leakage by 
thoroughly studying the following figure and using the 
attached heat insulating materials for fitting (3) and (4). 
(Fasten both ends with the clamps (6) (accessory).) 

(Refer 

to Fig. 1)

CAUTION

• Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 
condensate or burns if touched.

• CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-

ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
Flux has an extremely negative effect on refrigerant piping 
systems. For instance, if chlorine based flux is used, it will 
cause pipe corrosion. If the flux contains fluorine, it will 
damage the refrigerant oil.

DANGER

• Use of oxygen may cause an explosion resulting in serious 

injury or death. Only use nitrogen gas.

• Refrigerant gas may produce toxic gas if it comes in contact 

with fire such as from a fan heater, stove or cooking device. 
Exposure to this gas could cause severe injury or death.

• Before brazing local refrigerant piping, nitrogen gas shall 

be blown through the piping to expel air from the piping.
If brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing 

after having carried out nitrogen substitution or while 
inserting nitrogen into the refrigerant piping. Once this is 
done, connect the indoor unit with a flared or a flanged con-
nection.

• Nitrogen should be set to 2.9 psi with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping. 

NOTE

Use the flare nuts attached with the unit. Not recom-
mended but if no torque wrench is available,  refer 
to table 2 for tightening torque:  

Table 2

Ester oil or ether oil.

Torque wrench

Spanner

Piping union

Flare nut

Insulation for fitting 
(accessory) (4)

(For liquid pipe)

Clamp (6)
(accessory)

Insulation for fitting 
(accessory) (3)

(For gas pipe)

Sealing pad (accessory) (5)

(Wrapped over union)

Gas pipe

Liquid pipe

Fig. 1

Pipe 

size

Tightening 

torque

(ft-lbf)

Flare 

dimensions

A (in.)

Flare shape (in.)

 φ

 1/4”

10.5 – 12.7

0.343 – 0.358

 φ

 3/8”

24.1 – 29.4

0.504  – 0.520

 φ

 1/2”

36.5 – 44.5

0.638 – 0.654

 φ

 5/8”

45.6 – 55.6

0.760  – 0.776

Refrigerant 
piping

Part to be 
brazed

Taping

Pressure-
reducing 
valve

hands valve

Nitrogen

Nitrogen

45˚± 2˚

90˚± 2˚

R 0.016 ~ 0.031

A

Содержание FXLQ-M

Страница 1: ..._a AMERICAS FXLQ M FXNQ M Floor Standing Type Concealed Floor Standing Type 1645 Wallace Drive Suite 110 Carrollton TX75006 info daikinac com www daikinac com EDUS39 600 F7 Printed in U S A 09 2006 K...

Страница 2: ...Type 1 Features 2 2 Specifications 3 2 1 FXLQ 3 2 2 FXNQ 4 3 Dimensions 5 3 1 FXLQ 5 3 2 FXNQ 7 4 Piping Diagrams 9 5 Wiring Diagrams 10 6 Electric Characteristics 11 7 Capacity Tables 12 7 1 Cooling...

Страница 3: ...easy to access 3 Easy maintenance Wall units allow more space plus access to floor for cleaning Exposed type Easier maintenance of discharge grille The interval of filter cleaning is prolonged Efficie...

Страница 4: ...035 Air Flow Rate H L cfm 280 210 490 380 560 420 Drive Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooli...

Страница 5: ...cfm 280 210 490 380 560 420 Drive Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microp...

Страница 6: ...EDUS39 600 F7_a Dimensions FXLQ M FXNQ M 5 3 Dimensions 3 1 FXLQ FXLQ12MVJU 3D045642...

Страница 7: ...Dimensions EDUS39 600 F7_a 6 FXLQ M FXNQ M FXLQ18MVJU FXLQ24MVJU 3D045643...

Страница 8: ...EDUS39 600 F7_a Dimensions FXLQ M FXNQ M 7 3 2 FXNQ FXNQ12MVJU 3D045650...

Страница 9: ...Dimensions EDUS39 600 F7_a 8 FXLQ M FXNQ M FXNQ18MVJU FXNQ24MVJU 3D045651...

Страница 10: ...on air temperature R2T Thermistor for liquid line temperature R3T Thermistor for gas line temperature Capacity GAS Liquid 12 18M 1 2 1 4 24M 5 8 3 8 C 4D034245C Heat exchanger Gas piping connection po...

Страница 11: ...Wiring Diagrams EDUS39 600 F7_a 10 FXLQ M FXNQ M 5 Wiring Diagrams FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...

Страница 12: ...EDUS39 600 F7_a Electric Characteristics FXLQ M FXNQ M 11 6 Electric Characteristics 4D047090...

Страница 13: ...7 9 12 0 8 3 12 3 8 3 12 4 7 8 12 7 7 6 18 75 14 2 10 7 16 1 11 5 18 0 12 2 19 9 12 7 21 0 12 8 21 4 12 2 79 14 2 10 7 16 1 11 5 18 0 12 2 19 9 12 7 20 7 12 7 21 1 12 0 83 14 2 10 7 16 1 11 5 18 0 12...

Страница 14: ...12 3 60 0 56 0 15 5 14 7 14 0 13 5 13 0 12 3 18 22 0 20 0 17 5 17 5 17 4 17 4 17 4 17 4 26 0 24 0 18 3 18 3 18 3 18 3 18 2 18 2 30 0 28 0 19 2 19 1 19 1 19 1 19 1 18 4 35 0 32 0 20 0 20 0 19 9 19 9 19...

Страница 15: ...pe dBA Model 208 230V 60Hz Model 208 230V 60Hz H L H L FXLQ12MVJU 36 33 FXNQ12MVJU 36 33 FXLQ18MVJU 40 35 FXNQ18MVJU 40 35 FXLQ24MVJU 41 36 FXNQ24MVJU 41 36 Note Operation noise differs with operation...

Страница 16: ...600 F7_a Installation FXLQ M FXNQ M 15 9 Installation Installation Example Center of Gravity FXLQ FXNQ FXLQ12MVJU MODEL 4D045645 FXLQ18 24MVJU 22 1 2 28 FXNQ12MVJU 4D045652 FXNQ18 24MVJU 18 1 4 19 7 8...

Страница 17: ...ildren will not play with them Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries WARNING Ask your dealer or an a...

Страница 18: ...smantling of the unit and treatment of the refrigerant oil and other parts should be done in accordance with the relevant local and national regulations 2 BEFORE INSTALLATION Be sure to read this manu...

Страница 19: ...he risk of explosion resulting in serious injury or death NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5 ft away from televisions or radios in order to...

Страница 20: ...e front panel towards the front of the unit To close perform the procedure in opposite order by pulling toward the front of the unit until the knob snaps in place Base FXLQ Window 4 or more FXLQ 6 or...

Страница 21: ...ght cause leaks 6 REFRIGERANT PIPING WORK For refrigerant piping of outdoor units see the installa tion manual attached to the outdoor unit Execute heat insulation work completely on both sides of the...

Страница 22: ...lorine based flux is used it will cause pipe corrosion If the flux contains fluorine it will damage the refrigerant oil DANGER Use of oxygen may cause an explosion resulting in serious injury or death...

Страница 23: ...he outdoor unit indoor units and the remote controllers For details on hooking up the remote controller refer to the INSTALLATION MANUAL OF REMOTE CONTROLELR All wiring must be performed by an authori...

Страница 24: ...ment Make sure that the electric box lid fits tightly Incomplete connections could result in overheating and in worse case result in electric shock or fire NOTE To avoid a short circuit in the electri...

Страница 25: ...on if subjected to electric external noise 5 For remote controller wiring refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER 9 2 WIRING EXAMPLE Fit the power supply wiring of each unit with a switc...

Страница 26: ...t input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A The T1 T2 termi...

Страница 27: ...curs Check the malfunction code on the liquid crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in the installation manual...

Страница 28: ...ories Optional Accessories For Unit 4D045647 For Controller Optional Accessories Refer to Controller Manual No Type FXLQ12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ24MVJU FXNQ24MVJU Item 1 Long life r...

Страница 29: ...Accessories EDUS39 600 F7_a 28 FXLQ M FXNQ M...

Страница 30: ...US 39 600 F2 AMERICAS FXDQ M Slim Ceiling Mounted Duct Type 1645 Wallace Drive Suite 110 Carrollton TX75006 info daikinac com www daikinac com EDUS39 600 F7_a Printed in U S A 05 2007 AMERICAS May 200...

Отзывы: