Installation
EDUS39-600-F5
18
FXHQ-M
Install the indoor unit as far a
w
ay from fluorescent lamps as
possible.
• Arrange the drain hose to ensure smooth drainage.
Incomplete drainage may cause leaks in the building
and on furniture.
• Radio interference may result if installed too close to
other electrical devices.
• Dismantling of the unit, and treatment of the refriger-
ant, oil, and other parts, should be done in accordance
with the relevant local and national regulations.
2.
BEFORE INSTALLATION
• When moving the unit while removing it from the pack-
ing case, be sure to lift it by the four hanger brackets.
Avoid putting any pressure on other parts especially
the refrigerant piping.
• Be sure to check the type of R-410A refrigerant to be used
before installing the unit as using an incorrect refrigerant
w
ill prevent normal operation of the unit.
• The accessories needed for installation must be retained in
your custody until the installation
w
ork is completed. Do not
discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging until reaching the instal-
lation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together
w
ith a rope
w
hen
lifting, to avoid damage or scratches to the unit.
• When moving the unit after opening, hold the unit by the
hanger brackets (× 4). Do not apply force to the refrigerant
piping, drain piping or plastic parts.
• For the installation of an outdoor unit, refer to the installa-
tion manual attached to the outdoor unit.
• Do not install or operate the unit in the follo
w
ing areas:
• Kitchens or rooms that might be laden with mineral
oil, or filled with oil vapor or spray. Plastic parts
may deteriorate and eventually cause the unit to fall
out of place or leaks.
• Where sulfurous or other corrosive gas exists. Cop-
per tubing and brazed spots may corrode and lead
to refrigerant leaks.
• Where machines generate electromagnetic waves
and cause the control system to malfunction.
• Where the air contains high levels of salt as near the
ocean, and where voltage fluctuates greatly as in
factories.
Also in vehicles or vessels.
• This unit, both indoor and outdoor, is suitable for installation in
a commercial and light industrial environment.
If installed as a household appliance, it could cause elec-
tromagnetic interference.
WARNING
• Entrust installation to the place of purchase or a
q
ualified
serviceman. Improper installation can result in leaks or
even electric shock or fire.
• Use of unspecified parts could result in the unit falling,
leaks, or even electric shock or fire.
NOTE
• Be sure to read this manual before installing the indoor unit.
• Be sure to procure an air filter in the field and mount it in the
suction air passage to prevent
w
ater leaks or other prob-
lems.
Содержание FXHQ-M
Страница 1: ...AMERICAS EDUS 39 600 F5 FXHQ M Ceiling Suspended Type...
Страница 5: ...Dimensions EDUS39 600 F5 4 FXHQ M 3 Dimensions FXHQ12MVJU 3D049330...
Страница 6: ...EDUS39 600 F5 Dimensions FXHQ M 5 FXHQ24MVJU 3D049331...
Страница 7: ...Dimensions EDUS39 600 F5 6 FXHQ M FXHQ36MVJU 3D049332...
Страница 9: ...Wiring Diagrams EDUS39 600 F5 8 FXHQ M 5 Wiring Diagrams FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU 3D048116...
Страница 10: ...EDUS39 600 F5 Electric Characteristics FXHQ M 9 6 Electric Characteristics C 4D049333...