8-2 Electrical characteristics
MCA: Min. Circuit Amps (A)
MOP: Maximum Overcurrent Protective Device (A)
kW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
8-3 Specifications for field supplied fuses and wire
Allowable length of transmission wirings and remote controller wiring are as follows.
(1) Outdoor unit - Indoor unit:
Max. 3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit - Remote controller
Max. 1640ft.
NOTE
1.
Vinyl cord with sheath or cable (Insulated thickness : 0.04in. or more)
9. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER
9-1 How to connect wirings
Connection of wiring between units, ground wire and for the remote controller cord (Refer to Fig. 25)
•
Wiring the units and ground wire
Remove the control box lid and connect wires of matching number to the terminal block for wiring the units
(3 P) inside. And connect the ground wire to the ground terminal. In doing this, pull the wires inside through
the hole and fix the wires securely with the included clamp (4) (2 points).
•
Remote controller cords (not neccessary for slave unit of simultaneous operation system)
Remove the control box lid and pull the wires inside through the hole and connect to the terminal block for
remote controller (6 P). (no polarity) Securely fix the remote controller cord with the included clamp (4) (2
points).
•
After connection, attach sealing pad (13).
•
Be sure to attach it to prevent the infiltration of water from the outside.
Units
Power supply
Fan motor
Model
Hz
Volts
Voltage range
MCA
MOP
kW
FLA
FXFQ09PVJU
60
208/230
Max. 253
Min. 187
0.3
15
0.056
0.2
FXFQ12PVJU
0.3
15
0.056
0.2
FXFQ18PVJU
0.4
15
0.056
0.3
FXFQ24PVJU
0.5
15
0.056
0.4
FXFQ30PVJU
0.6
15
0.056
0.5
FXFQ36PVJU
1.4
15
0.120
1.1
FXFQ48PVJU
1.5
15
0.120
1.2
Power supply wiring
Remote controller wiring
Transmission wiring
Field fuses
Size
Wire
Size
15A
Wire size must comply with
local codes.
Sheathed wire
(2 wire)
AWG18 - 16