• Indoor Units • 2-Way Blow Ceiling Mounted Cassette • FXCQ-MVE9
1
1
• VRV
®
Systems • Indoor Units
4
1
Specifications
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXCQ20MVE9
FXCQ25MVE9
FXCQ32MVE9
FXCQ40MVE9
FXCQ50MVE9
FXCQ63MVE9
FXCQ80MVE9 FXCQ125MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
0.5
0.5
0.5
0.8
0.8
0.9
1.1
1.3
Maximum fuse amps (MFA)
A
15
15
15
15
15
15
15
15
Full load amps (FLA)
A
0.4
0.4
0.4
0.6
0.6
0.7
0.9
1.0
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXCQ20MVE9
FXCQ25MVE9
FXCQ32MVE9
FXCQ40MVE9
FXCQ50MVE9
FXCQ63MVE9
FXCQ80MVE9 FXCQ125MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
0.5
0.5
0.5
0.8
0.8
0.9
1.3
1.5
Maximum fuse amps (MFA)
A
15
15
15
15
15
15
15
15
Full load amps (FLA)
A
0.4
0.4
0.4
0.6
0.6
0.7
1.0
1.2
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 TECHNICAL SPECIFICATIONS
FXCQ20MVE9
FXCQ25MVE9
FXCQ32MVE9
FXCQ40MVE9
FXCQ50MVE9
FXCQ63MVE9
FXCQ80MVE9 FXCQ125MVE9