3
|
Components
Service manual
100
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
a
Fuse
2
To install a fuse on the main PCB, see
To install a fuse on the main PCB
ARXP-L + ARXP-M + RXP-L + RXP-M + RXP50~71N units
WARNING
For continued protection against risk of fire, replace only with same type and rating
of fuse.
1
Install the fuse on the correct location on the PCB.
CAUTION
Make sure the fuse is plugged‑in correctly (contact with the fuse holder).
a
a
Fuse
Is the problem solved?
Action
Yes
No further actions required.
No
84] of the PCB and
continue with the next procedure.
3.8 Outdoor unit fan motor
3.8.1 Class 20~35 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.