background image

Installation Manual

EDUS041111_a

74

Room Air Conditioners K-Series

Outdoor Unit Installation

5.

Purging air and checking gas leakage

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• If using additional refrigerant, perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant. 

• Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

*1. Pipe length vs. vacuum pump run time.  

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.  Check 

all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound pressure gauge reads –29.9inHg (–0.1MPa).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.  
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 49.2ft (15m)

Run time

Not less than 10 min.

Compound 
pressure gauge

Pressure 
meter

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

Содержание FTXN09KEVJU

Страница 1: ...EDUS041111_a K Series Cooling Only Heat Pump SEER 18 Models...

Страница 2: ...Unit 15 6 Piping Diagrams 16 6 1 Indoor Unit 16 6 2 Outdoor Unit 17 7 Capacity Tables 19 7 1 Cooling Only 19 7 2 Heat Pump 24 7 3 Capacity Correction Factor by the Length of Refrigerant Piping Referen...

Страница 3: ...ass 81 12 Operation Manual 93 12 1 Safety Considerations 09 12 Class 93 12 2 Safety Considerations 15 18 24 Class 122 13 Optional Accessories 149 13 1 Option List 149 13 2 BRC944B2 Wired Remote Contro...

Страница 4: ...Indoor Unit Outdoor Unit Power Supply Single Split Duct Free System FTXN09KEVJU RKN09KEVJU 1 208 230 V 60 Hz FTXN12KEVJU RKN12KEVJU FTXN15KVJU RKN15KEVJU FTXN18KVJU RKN18KEVJU FTXN24KVJU RKN24KEVJU F...

Страница 5: ...o Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check Function COMFORT AIRFLOW Operation Anti Corrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan...

Страница 6: ...Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display COMFORT AIRFLOW Operation Wiring Error Check Function Comfort Control Auto Fan Speed Anticorrosion Treatment of Outdoor Heat...

Страница 7: ...Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 20 0 18 0 20 0 18 Power Consumption Rated W 40 40 Power Factor 96 2 96 6 96 2 96 6 Temperature Con...

Страница 8: ...ble Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 17 0 15 Power Consumption Rated W 34 34 34 34 Power Factor 96 2 98 6 96 2 98 6 Temperature Control Microco...

Страница 9: ...Control Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 Power Consumption Rated W 34 34 Power Factor 96 2 98 6 Temperature Control Microcomp...

Страница 10: ...eps Quiet Auto Air Direction Control Right Left Horizontal Downward Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0...

Страница 11: ...orizontal Downward Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 18 0 16 0 17 0 15 0 18 0 16 Power Consu...

Страница 12: ...Direction Control Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 17 0 15 0 18 0 16 Power Consumption Rated W 34 34 36 36 Power Factor 96 2 98 6 96...

Страница 13: ...m FAN WALL HOLE FOR EMBEDDED PIPING RIGHT LEFT MANUAL 2 9 16 65mm HOLE WALL HOLE 5 2 9 16 65mm HOLE STANDARD LOCATIONS OF WALL HOLES WIRELESS REMOTE CONTROLLER 45 45 45 ARC452A19 3D065951C AIR FLOW IN...

Страница 14: ...E 3 8 9 5 CuT 5 7 8 150 5 7 8 150 3 15 16 100 1 15 16 50 3 15 16 100 1 15 16 50 1 15 16 50 1 15 16 50 UNIT INCH mm 11 13 16 300 3D071564A WALL HEIGHT ON AIR OUTLET SIDE MINIMUM SPACE FOR AIR PASSAGE L...

Страница 15: ...1 PCB3 R1T R2T NOTE S6 S602 S21 S1W 1 PCB3 SHOWS THE CASE OF X1M OPTION CONNECTION PCB 3 OPTION FRAME GROUND FUSE HARNESS PILOT LAMP FAN MOTOR SWING MOTOR PRINTED CIRCUIT BOARD THERMISTOR CONNECTOR OP...

Страница 16: ...LK 1 3 BLK GRY BLK BLK BLK BLK BLK BLK YEL RED BLU BRN RED ORG ORG WHT S80 BLU 3 1 RED YLW t t t S80 Q1L MS NOTE M V 3 IN CASE OF 1 REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS U R1T R3T R2T W RE...

Страница 17: ...9 32CuT 3 16CuT 9 32CuT THERMISTOR ON HEAT EXCH 9 32CuT 9 32CuT CROSS FLOW FAN FIELD PIPING 1 4CuT M FAN MOTOR 3 8CuT FIELD PIPING 3 8CuT REFRIGERANT FLOW COOLING HEATING 4D066211A INDOOR UNIT 5 16CuT...

Страница 18: ...OUTDOOR AIR TEMPERATURE 5 16CuT THERMISTOR 5 16CuT 16 0 5 8CuT 5 16CuT 12 0 15 32CuT CAPILLARY TUBE 1 5 16CuT 5 16CuT 5 32CuT 8 0 4 0 5 16CuT CAPILLARY TUBE 2 6 0 6 0 REFRIGERANT FLOW 5 16CuT 5 32CuT...

Страница 19: ...R UNIT 8 0 HEAT EXCHANGER OUTDOOR AIR TEMPERATURE 5 16CuT THERMISTOR 5 16CuT 16 0 5 8CuT 5 16CuT 12 0 15 32CuT CAPILLARY TUBE 1 5 16CuT 5 32CuT 5 16CuT 4 0 8 0 5 16CuT CAPILLARY TUBE 2 6 0 6 0 REFRIGE...

Страница 20: ...68 8 21 5 62 0 71 7 96 5 42 0 74 7 54 5 09 0 75 60 8 71 6 9 64 6 43 0 58 9 22 6 07 0 63 8 80 5 73 0 69 8 63 5 59 0 71 8 38 5 40 0 75 7 96 5 08 0 75 64 4 77 0 10 05 6 48 0 58 9 63 6 14 0 64 9 21 5 81 0...

Страница 21: ...0 98 7 94 5 44 1 03 60 8 71 6 10 62 7 44 0 81 10 62 7 44 0 92 10 62 7 44 1 04 10 62 7 44 1 09 10 62 7 44 1 16 10 61 7 43 1 21 64 4 77 0 13 40 9 95 0 94 12 84 9 31 1 03 12 28 8 70 1 12 12 06 8 47 1 15...

Страница 22: ...1 19 13 84 10 50 1 24 13 14 10 20 1 25 64 4 77 0 16 63 12 06 0 97 15 93 11 76 1 06 15 23 11 46 1 15 14 95 11 34 1 19 14 53 11 17 1 25 13 83 10 88 1 26 67 0 80 0 17 11 12 12 0 97 16 41 11 84 1 07 15 71...

Страница 23: ...1 42 16 60 11 92 1 49 15 77 11 53 1 50 64 4 77 0 19 95 13 70 1 16 19 11 13 32 1 27 18 27 12 95 1 38 17 94 12 81 1 43 17 43 12 59 1 50 16 60 12 23 1 51 67 0 80 0 20 53 13 73 1 17 19 69 13 38 1 28 18 85...

Страница 24: ...2 43 20 28 13 67 2 54 17 81 12 48 2 38 64 4 77 0 24 37 15 75 1 98 23 35 15 26 2 17 22 32 14 78 2 36 21 91 14 59 2 44 21 30 14 31 2 55 18 74 13 16 2 38 67 0 80 0 25 08 15 74 1 99 24 06 15 28 2 18 23 03...

Страница 25: ...08 0 75 64 4 77 0 10 05 6 48 0 58 9 63 6 14 0 64 9 21 5 81 0 69 9 04 5 68 0 72 8 79 5 49 0 75 8 37 5 18 0 76 67 0 80 0 10 26 6 56 0 58 9 84 6 23 0 64 9 42 5 91 0 69 9 25 5 78 0 72 9 00 5 60 0 75 8 58...

Страница 26: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are base...

Страница 27: ...0 13 40 9 95 0 94 12 84 9 31 1 03 12 28 8 70 1 12 12 06 8 47 1 15 11 72 8 13 1 21 11 16 7 58 1 22 67 0 80 0 13 68 10 04 0 94 13 12 9 41 1 03 12 56 8 81 1 12 12 34 8 58 1 16 12 00 8 24 1 21 11 44 7 70...

Страница 28: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are base...

Страница 29: ...12 06 0 97 15 93 11 76 1 06 15 23 11 46 1 15 14 95 11 34 1 19 14 53 11 17 1 25 13 83 10 88 1 26 67 0 80 0 17 11 12 12 0 97 16 41 11 84 1 07 15 71 11 56 1 16 15 43 11 45 1 19 15 00 11 28 1 25 14 31 11...

Страница 30: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Страница 31: ...70 1 16 19 11 13 32 1 27 18 27 12 95 1 38 17 94 12 81 1 43 17 43 12 59 1 50 16 60 12 23 1 51 67 0 80 0 20 53 13 73 1 17 19 69 13 38 1 28 18 85 13 03 1 39 18 52 12 89 1 43 18 00 12 68 1 50 17 18 12 34...

Страница 32: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Страница 33: ...1 98 23 35 15 26 2 17 22 32 14 78 2 36 21 91 14 59 2 44 21 30 14 31 2 55 18 74 13 16 2 38 67 0 80 0 25 08 15 74 1 99 24 06 15 28 2 18 23 03 14 82 2 37 22 62 14 64 2 45 22 00 14 37 2 56 19 40 13 25 2...

Страница 34: ...not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level differe...

Страница 35: ...ordance with the length of refrigerant piping the distance between the indoor unit and the outdoor unit line cooling capacity line heating capacity 7 3 1 09 12 Class 7 3 2 15 18 Class Capacity correct...

Страница 36: ...Conditioners K Series 35 7 3 3 24 Class Note The graphs show the factor when additional refrigerant of the proper quantity is charged 1 16 4 32 8 49 2 65 6 82 0 R 410A 24 class Piping length ft Range...

Страница 37: ...nt piping length 25ft Level difference 0m Air flow rate High 4D071134 Note Operation can be extended to 0 F in cooling with use of the optional wind baffle Cooling 122 114 8 104 86 68 50 Outdoor temp...

Страница 38: ...length 25ft Level difference 0m Air flow rate High Note Operation can be extended to 0 F in cooling with use of the optional wind baffle 3D072084a Heating 68 64 4 59 50 41 32 Outdoor temp FWB 23 Conti...

Страница 39: ...und is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit Single Split Duct Free System Outdoor Unit 3 3 ft 2 6 ft R5162 3 3 ft R4796 Cooling H...

Страница 40: ...H 60Hz 208 230V L 208 230V 41 60Hz H 208 230V 60Hz 208 230V 29 60Hz L POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED STANDARD EXTERNAL STATIC PRESSURE S...

Страница 41: ...40 NC 30 NC 20 Cooling 60Hz 208 230V 208 230V 60Hz POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED 60Hz 53 208 230V H OCTAVE BAND SOUND PRESSURE LEVEL dB...

Страница 42: ...g POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED 60Hz 53 208 230V H 208 230V 60Hz 60Hz 208 230V 3D071283 NC 60 NC 60 NC 50 NC 50 NC 40 NC 40 NC 30 NC 30...

Страница 43: ...U RXN09KEVJU 60 208 MAX 60 Hz 253 V MIN 60 Hz 187 V 4 8 15 4 1 33 0 19 16 0 20 60 230 3 7 0 17 0 18 FTXN12KEVJU RXN12KEVJU 60 208 MAX 60 Hz 253 V MIN 60 Hz 187 V 7 0 15 6 1 33 0 19 16 0 20 60 230 5 5...

Страница 44: ...materials used for transportation may cause injuries or death by suffocation Only qualified personnel must carry out the installation work Installation must be done in accordance with this installatio...

Страница 45: ...rmal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or ra...

Страница 46: ...sound 9 no laundry equipment is located Mounting plate 1 Remote controller holder 1 Operation manual 1 Mounting plate fixing screw 3 16 1 M4 25mm 6 Fixing screw for remote controller holder 1 8 13 16...

Страница 47: ...n there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you In...

Страница 48: ...the mounting plate If the claws are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is...

Страница 49: ...ting plate retention spots and dimensions The removed pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate Use tape measure as shown Position the end of a...

Страница 50: ...e 2 Wrap the refrigerant pipes and drain hose together with insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by us...

Страница 51: ...on fixing screws on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing scr...

Страница 52: ...nduit Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire 5 When connecting to a wired remote controller If work space is available on the right side of the indo...

Страница 53: ...accessory separate product into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position...

Страница 54: ...mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use part...

Страница 55: ...pipe s surface temperature reaches 230 F 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation...

Страница 56: ...he air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power con...

Страница 57: ...must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the...

Страница 58: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Страница 59: ...Installation Manual EDUS041111_a 58 Room Air Conditioners K Series Accessories...

Страница 60: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 59...

Страница 61: ...Installation Manual EDUS041111_a 60 Room Air Conditioners K Series...

Страница 62: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 61...

Страница 63: ...Installation Manual EDUS041111_a 62 Room Air Conditioners K Series...

Страница 64: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 63...

Страница 65: ...Installation Manual EDUS041111_a 64 Room Air Conditioners K Series...

Страница 66: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 65...

Страница 67: ...Installation Manual EDUS041111_a 66 Room Air Conditioners K Series...

Страница 68: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 67 3P276866 2...

Страница 69: ...must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the...

Страница 70: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Страница 71: ...Manual EDUS041111_a 70 Room Air Conditioners K Series Accessories Accessories Accessories supplied with the outdoor unit A Installation manual 1 B Drain plug Heat pump models There is on the bottom pa...

Страница 72: ...e may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the air discharge side of the outdoor unit In heavy snowfall areas select an installation s...

Страница 73: ...ace Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is...

Страница 74: ...e torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them...

Страница 75: ...h 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressu...

Страница 76: ...oam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 230 F 110 C max Choose heat insulation materials that will...

Страница 77: ...terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close the gas stop valve within 3 minutes then stop the forced operation Facility Setting...

Страница 78: ...e screws The screws are packed with the terminal board Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection pl...

Страница 79: ...C to 28 C 3 For protection the system disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functi...

Страница 80: ...l must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing th...

Страница 81: ...t transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possibl...

Страница 82: ...E Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent expo...

Страница 83: ...Installation Manual EDUS041111_a 82 Room Air Conditioners K Series...

Страница 84: ...tion drawing fi foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their length are 3 4 inch 20mm from the foundation surface 3...

Страница 85: ...e Liquid side 1 4 inch 6 4mm 15 9 20 2ft Ibf 21 6 27 4N m Gas side 1 2 inch 12 7mm 35 5 44 0ft Ibf 48 1 59 7N m Service port cap tightening torque 7 9 10 8ft lbf m N 7 4 1 8 0 1 Do not apply refrigera...

Страница 86: ...g 0 1MPa 1 3 Close gauge manifold s low pressure valve Lo and stop vacuum pump 4 Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 Remove ca...

Страница 87: ...s 7 2 When using commercial copper pipes and fi Insulation material Polyethylene foam 1 Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Refrigerant gas pipe s sur...

Страница 88: ...EDUS041111_a Installation Manual Room Air Conditioners K Series 87...

Страница 89: ...rminal screws securely We recommend a fl screwdriver be used to tighten the screws Work before wiring A protection plate is fi Before staring wiring work dismount the protection plate by removing the...

Страница 90: ...art back up once the temperature rises again Remove the 3 screws on the side and remove the top plate of the outdoor unit 1 Remove the drip proof cover 2 Cut the jumper J6 of the PCB inside 3 J5 J7 J8...

Страница 91: ...accordance with the operation manual to ensure that all functions and parts 1 3 such as fi The air conditioner requires a small amount of power in its standby mode If the system is not to be used for...

Страница 92: ...serious injury or death Be sure to ventilate the room sufficiently to avoid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may caus...

Страница 93: ...as they can cut and cause injury Do not place objects in direct proximity of the outside unit Do not let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which...

Страница 94: ...t there are no obstacles close to the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dea...

Страница 95: ...Operation Manual EDUS041111_a 94 Room Air Conditioners K Series...

Страница 96: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 95...

Страница 97: ...Operation Manual EDUS041111_a 96 Room Air Conditioners K Series...

Страница 98: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 97...

Страница 99: ...Operation Manual EDUS041111_a 98 Room Air Conditioners K Series...

Страница 100: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 99...

Страница 101: ...Operation Manual EDUS041111_a 100 Room Air Conditioners K Series...

Страница 102: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 101 14 115 14 115...

Страница 103: ...Operation Manual EDUS041111_a 102 Room Air Conditioners K Series...

Страница 104: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 103...

Страница 105: ...Operation Manual EDUS041111_a 104 Room Air Conditioners K Series...

Страница 106: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 105...

Страница 107: ...Operation Manual EDUS041111_a 106 Room Air Conditioners K Series...

Страница 108: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 107...

Страница 109: ...Operation Manual EDUS041111_a 108 Room Air Conditioners K Series...

Страница 110: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 109...

Страница 111: ...Operation Manual EDUS041111_a 110 Room Air Conditioners K Series...

Страница 112: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 111...

Страница 113: ...Operation Manual EDUS041111_a 112 Room Air Conditioners K Series...

Страница 114: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 113...

Страница 115: ...Operation Manual EDUS041111_a 114 Room Air Conditioners K Series...

Страница 116: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 115...

Страница 117: ...Operation Manual EDUS041111_a 116 Room Air Conditioners K Series...

Страница 118: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 117...

Страница 119: ...Operation Manual EDUS041111_a 118 Room Air Conditioners K Series...

Страница 120: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 119 3P272441 1...

Страница 121: ...oid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging ba...

Страница 122: ...ot let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which can enter the unit Once inside the unit animals can cause the unit to malfunction and cause smoke...

Страница 123: ...the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dealer if the air conditioner or heat...

Страница 124: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 123...

Страница 125: ...Operation Manual EDUS041111_a 124 Room Air Conditioners K Series...

Страница 126: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 125...

Страница 127: ...Operation Manual EDUS041111_a 126 Room Air Conditioners K Series...

Страница 128: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 127...

Страница 129: ...Operation Manual EDUS041111_a 128 Room Air Conditioners K Series...

Страница 130: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 129...

Страница 131: ...Operation Manual EDUS041111_a 130 Room Air Conditioners K Series 14 115 F 14 115 F...

Страница 132: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 131...

Страница 133: ...Operation Manual EDUS041111_a 132 Room Air Conditioners K Series...

Страница 134: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 133...

Страница 135: ...Operation Manual EDUS041111_a 134 Room Air Conditioners K Series...

Страница 136: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 135...

Страница 137: ...Operation Manual EDUS041111_a 136 Room Air Conditioners K Series When it is dirty wipe it gently with a water soaked cloth...

Страница 138: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 137...

Страница 139: ...Operation Manual EDUS041111_a 138 Room Air Conditioners K Series...

Страница 140: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 139...

Страница 141: ...Operation Manual EDUS041111_a 140 Room Air Conditioners K Series...

Страница 142: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 141...

Страница 143: ...Operation Manual EDUS041111_a 142 Room Air Conditioners K Series...

Страница 144: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 143...

Страница 145: ...Operation Manual EDUS041111_a 144 Room Air Conditioners K Series...

Страница 146: ...EDUS041111_a Operation Manual Room Air Conditioners K Series 145...

Страница 147: ...Operation Manual EDUS041111_a 146 Room Air Conditioners K Series 3P276856 2...

Страница 148: ...ontroller Kit 26 ft 1 BRC944B2 A08 2 Interface Adaptor for Wired Remote Controller KRP980B1 3 Centralized Control Board Up to 5 Rooms 2 KRC72 4 Wiring Adapter for Timer Clock Remote Controller 3 Norma...

Страница 149: ...oard or the adapter board 5 Keep the wiring away from any other power source lines to avoid electric noise external noise 6 Select a flat surface wherever possible to mount the remote controller To pr...

Страница 150: ...tape Double face adhesive tape Attached five wire cord Remote controller cord Note 1 Connector Connector Connector Tie band to secure the cord Tie band to secure the cord Tie band to secure the cord U...

Страница 151: ...Adjusts the temperature setting Airflow rate button Adjusts the airflow rate Time setting button for the timer Display Timer select button Displays the operating conditions Clock setting button page...

Страница 152: ...energy Clean the air filter monthly every two weeks as required or so Please take note of the following points Electric power is consumed even when the air conditioner is not in operation When the un...

Страница 153: ...dication is changed to Celsius one the temperature value 0 5 C will be rounded up Thus the preset temperature may be changed Example A preset temperature of 65 F equivalent to 18 5 C will be changed t...

Страница 154: ...een Automatic DRY Heating Cooling DRY Cooling Cooling only model Heat pump model To stop the operation Press again The run indicator lamp goes out In Automatic the temperature setting and operation mo...

Страница 155: ...uring heating operation the heating capacity is decreased In this case the unit starts defrosting operation No hot air comes out of the indoor unit during defrosting operation To adjust the temperatur...

Страница 156: ...ntroller Do not forcibly adjust louvers by hand or a malfunction may occur Adjusting Airflow Direction 1 Press during operation Each time the button is pressed the airflow direction louvers change the...

Страница 157: ...ight and left The vertical airflow direction louvers stop just when the button is pressed Swing horizontally Swing vertically Airflow direction louvers stop The vertical and horizontal louvers cannot...

Страница 158: ...inute has passed before making any timer setting the previous timer settings are reintroduced and the timer is on standby In this case use the time setting button and make your desired timer settings...

Страница 159: ...or decrement Hold the button down to advance quickly When the ON timer is not used save the setting as 4 Press 5 Press to make the OFF timer setting 6 Press The ONE TIME timer is now programmed Both...

Страница 160: ...ammed ONE TIME timer DAILY timer TIMER OFF The timer lamp lights up 1 2 1 2 ON time 24 hour timer display OFF time Timers The settings of timers and can be seen at a glance Two pairs of ON and OFF tim...

Страница 161: ...pears lights up 3 Press The DAILY timer is now programmed Note If the following appears on the display the timer must be reprogrammed The 24 hour timer display is blinking The 24 hour timer display is...

Страница 162: ...When the unit is not used for a long time On a sunny day keep the system running for half a day in the FAN mode to dry it up inside 3 1 2 FAN mode 1 Press to select the cooling mode 2 Press to adjust...

Страница 163: ...lure Group control i e the control a number of indoor units through a single remote controller Monitoring of the following items Indoor temperature and operating conditions of thermo compressor indoor...

Страница 164: ...tabs Place both hands under the center of the front grille and while pushing up pull it toward you Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of...

Страница 165: ...grille 3 Remove the service lid of the indoor unit 4 Remove the cover of the electrical component cover 1 Remove the flap in control of wind directions upward and downward 2 Disconnect the communicati...

Страница 166: ...rough the cut out of the set and mount the electrical component cover to the original position 4 Insert the connector of the set into the S403 in the indoor unit electrical component connector Then ro...

Страница 167: ...Optional Accessories EDUS041111_a 166 Room Air Conditioners K Series 13 4 KRP413AB1S Wiring Adaptor for Timer Clock Remote Controller...

Страница 168: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 167...

Страница 169: ...Optional Accessories EDUS041111_a 168 Room Air Conditioners K Series...

Страница 170: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 169 3P248024 2...

Страница 171: ...Optional Accessories EDUS041111_a 170 Room Air Conditioners K Series 13 5 KRP928BB2S Interface Adaptor for DIII NET Residential Air Conditioner...

Страница 172: ...EDUS041111_a Optional Accessories Room Air Conditioners K Series 171 3P248024 1A...

Страница 173: ...Optional Accessories EDUS041111_a 172 Room Air Conditioners K Series Connection to Remote Control PC board 3P248024 3B...

Страница 174: ...ing conditions When installing near the border to a neighbor s house If exhaust blows directly on passers by because outdoor unit is installed facing a road Changing the fan direction of the outdoor u...

Страница 175: ...airflow direction to prevent exhaust blowing directly onto passersby or garden plants M4 x 30 Screw 4 pcs 4 pcs Installation manual One sheet this sheet Seal 1 pc Spacer 1 Install the air direction a...

Страница 176: ...le aligning the center of each part s hole At 4 positions Be careful that the spacer does not come off before it is fixed to the front panel with screws 1 Remove the 4 outlet grille fixing screws 2 Af...

Страница 177: ...Optional Accessories EDUS041111_a 176 Room Air Conditioners K Series...

Страница 178: ...is product conforms tot he applicable standards and is suitable for use in the region where the product will be used This statement does not purport to exclude restrict or modify the application of an...

Отзывы: