Main Functions
SiUS042113E
30
Part 4 Functions and Control
1.6 Hybrid Cooling
Operation
Hybrid cooling becomes effective when COOL or DRY is selected from
MODE
button of the remote
controller. In cooling operation, hybrid cooling is automatically activated when the room
temperature approaches to the target temperature set from the remote controller. When more
cooling capacity is required, the operation automatically returns to the normal cooling operation.
During dry operation, in addition to the above, the indoor unit fan is automatically controlled to help
dehumidification.
R4003786
Outline
In hybrid cooling, only a part of the heat exchanger is cooled. The cool, dehumidified air is mixed
with the room air, and then blown out at around the same temperature with the room air. This is to
keep dehumidification effect after the target temperature is reached. The area of the heat
exchanger to be cooled is determined automatically based on the amount of humidity to remove.
Particularly, when the amount of humidity is large, the area of the heat exchanger to be cooled also
becomes large. When the amount of humidity is small, the area of heat exchanger becomes small,
too.
MODE selector button
• Selects the operation mode.
AUTO
DRY
COOL
HEAT
FAN
(R25241)
Temperat
u
re is controlled by
mixing the room air
Normal cooling
Hybrid cooling:
After the target temperat
u
re
is reached
Deh
u
midification effect
contin
u
es by partially cooling
the heat exchanger
Содержание FTXM-V Series
Страница 13: ...SiUS042113E Part 1 General Information 9 1 Applicable Models 10 2 Functions 11 Part 1 General Information...
Страница 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Страница 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Страница 147: ...SiUS042113E Check Part 6 Service Diagnosis 143 09 12 class 18 24 class 1 2 3 4 Multimeter R24538 1 2 3 4 Multimeter...
Страница 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Страница 165: ...SiUS042113E Piping Diagrams Part 8 Appendix 161 1 2 Outdoor Unit RXM09 12VVJU RXM18VVJU 3D131979 3D132216...
Страница 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Страница 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...