background image

INSTALLATION 
MANUAL

R410A Split Series

Models

FTXL25J2V1B
FTXL35J2V1B
ATXL25J2V1B
ATXL35J2V1B

УСТАНОВКА КОНДИЦИОНЕРОВ DAIKIN

Содержание FTXL25J2V1B

Страница 1: ...INSTALLATION MANUAL R410A Split Series Models FTXL25J2V1B FTXL35J2V1B ATXL25J2V1B ATXL35J2V1B DAIKIN...

Страница 2: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Страница 3: ...may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections o...

Страница 4: ...ite where remote controller signals are properly received by the indoor unit within 7 metres CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In...

Страница 5: ...d push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the centr...

Страница 6: ...panel 50mm or more from walls on both sides Air filters Titanium apatite deodorizing filter 2 Air filter Titanium apatite deodorizing filter Filter frame Tab Service lid Opening service lid The servi...

Страница 7: ...the wall with screws Recommended mounting plate retention spots and Dimensions Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liqu...

Страница 8: ...pes keep the following precautions in mind Abnormal sound may be generated if improper work is conducted 1 Do not strongly press the refrigerant pipes onto the bottom frame 2 Do not strongly press the...

Страница 9: ...the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the interconnecting wire ends are to be stripped first bundle wire ends wi...

Страница 10: ...to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it to the...

Страница 11: ...IRCUIT BREAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER...

Страница 12: ...e 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps inv...

Страница 13: ...ct into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Ins...

Страница 14: ...rly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous...

Страница 15: ...Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide i...

Страница 16: ...cessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...3P377527 2D 2017 02 Copyright 2014 Daikin...

Отзывы: