5 Unit installation

Installation Manual

6

FTXF20~42C5V1B 

Daikin room air conditioners

3P519299-9X – 2020.12

(a)

A safety device might stop the operation of the system if the unit
runs outside its operation range.

(b)

Condensation and water dripping might occur if the unit runs
outside its operation range.

5

Unit installation

5.1

Preparing the installation site

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating gas appliance or an operating electric heater).

5.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

Air flow.

 Make sure nothing blocks the air flow.

Drainage.

  Make  sure  condensation  water  can  be  evacuated

properly.

Wall insulation

. When conditions in the wall exceed 30°C and a

relative  humidity  of  80%,  or  when  fresh  air  is  inducted  into  the
wall,  then  additional  insulation  is  required  (minimum  10  mm
thickness, polyethylene foam).

Wall  strength. 

Check  whether  the  wall  or  the  floor  is  strong

enough to support the weight of the unit. If there is a risk, reinforce
the wall or the floor before installing the unit.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

5.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

5.2

Opening the indoor unit

5.2.1

To remove the front panel

1

Hold the front panel by the panel tabs on both sides and open
it.

a

a

Panel tabs

2

Remove  the  front  panel  by  sliding  it  to  the  left  or  the  right  and
pulling it toward you.

Result: 

The front panel shaft on 1 side will be disconnected.

3

Disconnect  the  front  panel  shaft  on  the  other  side  in  the  same
manner.

a

a

Front panel shaft

5.2.2

To re-install the front panel

1

Attach the front panel. Align the shafts with the slots and push
them all the way in.

2

Close  the  front  panel  slowly;  press  at  both  sides  and  at  the
centre.

5.2.3

To remove the front grille

CAUTION

Wear  adequate  personal  protective  equipment  (protective
gloves,  safety  glasses,…)  when  installing,  maintaining  or
servicing the system.

1

Remove the front panel to remove the air filter.

2

Remove 2 screws from the front grille.

3

Push  down  the  3  upper  hooks  marked  with  a  symbol  with  3
circles.

a

b

a

a

Upper hook

b

Symbol with 3 circles

4

We  recommend  opening  the  flap  before  removing  the  front
grille.

5

Place both hands under the centre of the front grille, push it up
and then toward you.

Содержание FTXF20C5V1B

Страница 1: ...Installation Manual Daikin room air conditioners English Installation Manual Daikin room air conditioners FTXF20C5V1B FTXF25C5V1B FTXF35C5V1B FTXF42C5V1B...

Страница 2: ...vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbils...

Страница 3: ...m a test run in winter season 14 11 Disposal 14 12 Technical data 15 12 1 Wiring diagram 15 12 1 1 Unified wiring diagram legend 15 1 About the documentation 1 1 About this document INFORMATION Make s...

Страница 4: ...ay cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Cha...

Страница 5: ...witch box cover before turning on the power supply Commissioning see 10 Commissioning 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while w...

Страница 6: ...oor and keep the following requirements in mind for distances from the walls and the ceiling 50 50 30 mm 5 1 2 Additional installation site requirements of the outdoor unit in cold climates Protect th...

Страница 7: ...the centres of the drilling points on the wall using a tape measure Position the end of tape measure at symbol 4 Finish the installation by securing the mounting plate on the wall using M4 25L screws...

Страница 8: ...a field supplied hose with inner 16 mm Do NOT forget to use a heat insulation tube on the indoor section of the extension hose a a b c 16 16 a Drain hose supplied with the indoor unit b Heat insulatio...

Страница 9: ...check for water leaks 6 Piping installation 6 1 Preparing refrigerant piping 6 1 1 Refrigerant piping requirements NOTICE The piping and other pressure containing parts shall be suitable for refriger...

Страница 10: ...ection cable d Liquid pipe e Liquid pipe insulation f Finishing tape g Drain hose NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 3 Checking the refri...

Страница 11: ...ning the indoor unit 46 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the interc...

Страница 12: ...Note Take care that the interconnection cable does NOT get caught in the indoor unit 3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4...

Страница 13: ...matches the voltage on the identification label of the unit The specified wires are used for the interconnection cable The indoor unit receives the signals of the user interface There are NO loose con...

Страница 14: ...automatically restarts immediately after power is restored For FTXF ATXF CTXF units 1 Press to switch the system on 2 Press the centre of and simultaneously 3 Press twice Result will appear on the dis...

Страница 15: ...D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symb...

Страница 16: ...on Manual 16 FTXF20 42C5V1B Daikin room air conditioners 3P519299 9X 2020 12 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferri...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P519299 9X 2020 12 Copyright 20...

Отзывы: