Si04-306
Troubleshooting
Service Diagnosis
115
Troubleshooting
Check No.6
Refer to P.128
Check No.7
Refer to P.129
Check No.9
Refer to P.130
Turn off the power and turn it on
again.
Check No. 6
Check the thermistor resistance
value.
Replace the fin thermistor.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R2850)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error again or outdoor unit
fan activated?
YES
l
Fin thermistor
NO
Slightly dirty
Check No. 9
Check the outdoor unit
fan or related.
Malfunctioning
Radiation fin dirty?
Too dirty
Functioning
Thermistor as
specified in its characteristic
chart?
Above 80˚C?
NO
YES
NO
YES
Check the radiation fin
temperature.
Check No. 7
Check the installation condition.
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 78˚C and stops itself when
it drops below 70˚C.
Содержание FTKS50BVMA
Страница 17: ...List of Functions Si04 306 8 List of Functions...
Страница 35: ...Specifications Si04 306 26 Specifications...
Страница 143: ...Check Si04 306 134 Service Diagnosis...
Страница 187: ...Outdoor Unit Si04 306 178 Removal Procedure...
Страница 191: ...Others Si04 306 182 Others...
Страница 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS...
Страница 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS...