manualshive.com logo in svg
background image

Inverter Pair

Wall Mounted Type B-Series

[Applied Models]

z

z

z

z

Inverter Pair : Cooling Only 

z

z

z

z

Inverter Pair : Heat Pump

z

z

z

z

Non-Inverter Pair : Cooling Only 

z

z

z

z

Non-Inverter Pair : Heat Pump

Si04-306

Service

Manual

Содержание FTKS50BVMA

Страница 1: ...Pair Wall Mounted Type B Series Applied Models z z z zInverter Pair Cooling Only z z z zInverter Pair Heat Pump z z z zNon Inverter Pair Cooling Only z z z zNon Inverter Pair Heat Pump Si04 306 Servic...

Страница 2: ...S Outdoor Unit R410A RKS50BVMA RKS50BVMB RS50BVMB RKS60BVMA RKS60BVMB RS60BVMB RKS71BVMA RKS71BVMB R22 RKD50BVM RKD50BVMA RKD50BVMT RKD18BVMS RKD60BVM RKD60BVMA RKD60BVMT RKD24BVMS RKD71BVM RKD71BVMA...

Страница 3: ...Dual Flaps Wide Angle Louvers and Auto Swing 36 1 3 Fan Speed Control for Indoor Units 37 1 4 Programme Dry Function 38 1 5 Automatic Operation 39 1 6 Night Set Mode 40 1 7 Intelligent Eye 41 1 8 Hom...

Страница 4: ...4 1 Error Codes and Description 93 4 2 Indoor Unit PCB Abnormality 94 4 3 Freeze up Protection Control or High Pressure Control 95 4 4 Fan Motor DC Motor or Related Abnormality 97 4 5 Thermistor or R...

Страница 5: ...the Panels and Plates 154 2 2 Removal of the Fan Motor Propeller Fan 158 2 3 Removal of the PCB Electrical Box 162 2 4 Removal of the Reactor 170 2 5 Removal of the Sound Blanket 172 2 6 Removal of th...

Страница 6: ...ug socket before disassembling the equipment for a repair Working on the equipment that is connected to a power supply can cause an electrical shook If it is necessary to supply power to the equipment...

Страница 7: ...the welder in a well ventilated place Using the welder in an enclosed room can cause oxygen deficiency Warning Be sure to use parts listed in the service parts list of the applicable model and approp...

Страница 8: ...s leaks be sure to locate the leak and repair it before charging the refrigerant After charging refrigerant make sure that there is no refrigerant leak If the leak cannot be located and the repair wor...

Страница 9: ...and repair it if the equipment is not properly grounded Improper grounding can cause an electrical shock Be sure to measure the insulation resistance after the repair and make sure that the resistanc...

Страница 10: ...Si04 306 List of Functions 1 Part 1 Part 1 Part 1 Part 1 List of Functions List of Functions List of Functions List of Functions 1 List of Functions 2 1 1 R410A Series 2 1 2 R22 Series 5...

Страница 11: ...ght Set Mode Horizontal Auto Swing Right and Left Worry Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error...

Страница 12: ...zontal Auto Swing Right and Left Worry Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Comfort Co...

Страница 13: ...ng Right and Left Worry Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Comfort Control Auto Fan...

Страница 14: ...ode Horizontal Auto Swing Right and Left Worry Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Co...

Страница 15: ...ntal Auto Swing Right and Left Worry Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Comfort Cont...

Страница 16: ...Free Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Comfort Control Auto Fan Speed Anticorrosion Tre...

Страница 17: ...List of Functions Si04 306 8 List of Functions...

Страница 18: ...rt 2 Part 2 Part 2 Part 2 Specifications Specifications Specifications Specifications 1 Specifications 10 1 1 Cooling Only R410A Series 10 1 2 Cooling Only R22 Series 13 1 3 Heat Pump R410A Series 17...

Страница 19: ...ht Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 19 0 21 Power Consumption Rate...

Страница 20: ...nd Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 18 0 20 Power Consumption Rated W 40 40 45 Power F...

Страница 21: ...Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 18 Power Consumption Rated W 40 40 Power Factor 96 6 96 6 Temperature Control Microcomputer Control Microcomputer Control Di...

Страница 22: ...Washable Mildew Proof Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 19 0 18 0 17 0 19 0 18 0 21 0 20 0 19 0 21 0 20 0 23 0 22 0 21 0 23 0 22 Power Consumpti...

Страница 23: ...ildew Proof Removable Washable Mildew Proof Running Current Rated A 0 19 0 18 0 17 0 19 0 18 0 21 0 20 0 19 0 21 0 20 0 23 0 22 0 21 0 23 0 22 Power Consumption Rated W 40 45 50 Power Factor 95 7 96 6...

Страница 24: ...e Mildew Proof Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current A 0 19 0 21 0 23 Power Consumption W 40 45 50 Power Factor 95 7 97 4 98 8 Temperature Control Microcomput...

Страница 25: ...Right Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current A 0 21 0 23 0 24 Power Consumption W 45 50...

Страница 26: ...ol Right Left Horizontal and Downward Right Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 17 0 17 0 19 0 19 Power Co...

Страница 27: ...ntrol Right Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 21 0 21 Power Consumption Rated W 50 50 Power Factor 99 2 99 2 Temperature Control Microco...

Страница 28: ...t Left Horizontal and Downward Right Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 20 0 18 0 20 Power Consumpti...

Страница 29: ...Direction Control Right Left Horizontal and Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 20 0 22 Power Consumption Rated W 45 50 Power Factor 96 4 97 6 Temperature Con...

Страница 30: ...ldew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 18 0 18 0 18 Power Consumption Rated W 40 40 40 40 Power Factor 96 6 96 6 96 6 96 6 Temperature Control Microcomputer Control...

Страница 31: ...le Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 19 0 18 0 17 0 19 0 18 0 19 0 18 0 17 0 19 0 18 0 21 0 20 0 19 0 21 0 20 0 21 0 20 0 19 0 21 0 20 Power Consumption R...

Страница 32: ...d Air Filter Removable Washable Mildew Proof Running Current Rated A 0 23 0 22 0 21 0 23 0 22 0 23 0 22 0 21 0 23 0 22 Power Consumption Rated W 50 50 Power Factor 98 8 98 8 99 2 98 8 98 8 98 8 98 8 9...

Страница 33: ...Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current A 0 19 0 19 0 21 0 21 Power Consumption W 40 40 45 45 Power Factor 95 7 95 7 97 4 97 4 Temperature...

Страница 34: ...orizontal and Downward Air Filter Removable Washable Mildew Proof Running Current A 0 23 0 23 Power Consumption W 50 50 Power Factor 98 8 98 8 Temperature Control Microcomputer Control Dimensions H W...

Страница 35: ...Specifications Si04 306 26 Specifications...

Страница 36: ...t 3 Printed Circuit Board Printed Circuit Board Printed Circuit Board Printed Circuit Board Connector Wiring Diagram Connector Wiring Diagram Connector Wiring Diagram Connector Wiring Diagram 1 Printe...

Страница 37: ...4 S21 Connector for centralized control HA 5 S26 S37 Connector for buzzer PCB 6 S27 S29 S36 Connector for control PCB 7 S28 Connector for signal receiver PCB 8 S32 Connector for heat exchanger thermi...

Страница 38: ...nnector Wiring Diagram 29 PCB Detail PCB 1 Control PCB indoor unit PCB 2 Signal Receiver PCB PCB 3 Buzzer PCB PCB 4 Display PCB PCB 5 Intelligent Eye sensor PCB S1 V1 FU1 S6 S8 S26 R2860 S28 S32 JC JB...

Страница 39: ...control PCB 6 S40 Connector for overload protector 7 S51 S101 Connector for service monitor PCB 8 S70 Connector for fan motor 9 S80 Connector for four way valve coil 10 S90 Connector for thermistors...

Страница 40: ...cuit Board Connector Wiring Diagram 31 PCB Detail PCB 1 Control PCB outdoor unit E AC1 FU2 3 15A H1 H2 S32 S33 S71 S31 S91 R2865 S40 S20 S90 S101 S51 S80 S10 AC2 PCB 2 Power Supply PCB Service Monitor...

Страница 41: ...Printed Circuit Board Connector Wiring Diagram Si04 306 32 Printed Circuit Board Connector Wiring Diagram MID SPM S34 S72 R2868 S70 FU201 3 15A R2869 CN14 CN11 L1 L2...

Страница 42: ...n 43 1 9 Inverter Powerful Operation 44 1 10 Other Functions 45 2 Function of Main Structural Parts 46 2 1 Function of Thermistor 46 3 Control Specification 48 3 1 Mode Hierarchy 48 3 2 Frequency Cont...

Страница 43: ...lains the conversion principle Drawing of Inverter The following drawing shows a schematic view of the inverter principle Phase Description 1 The supplied AC power source is converted into the DC powe...

Страница 44: ...ondition with a small room temperature variation Energy saving heating and cooling Once the set temperature is reached the energy saving operation enables to maintain the room temperature at low power...

Страница 45: ...w that guarantees a comfortable air distribution Auto Swing The following table explains the auto swing process for heating cooling dry and fan Outline of 3 D Airflow Alternative repetition of vertica...

Страница 46: ...During powerful operation fan operates H tap 50 90 rpm 2 Fan stops during defrost operation Automatic Air Flow Control for Heating The following drawing explains the principle for fan speed control f...

Страница 47: ...et by the microcomputer is divided into two zones Then the unit operates in the dry mode with an appropriate capacity for each zone to maintain the temperature and humidity at a comfortable level Room...

Страница 48: ...r setting temperature plus correction value correction value cooling 0 deg heating 2 deg 3 Operation ON OFF point and mode switching point are as follows Heating Cooling switching point Room temperatu...

Страница 49: ...ht Set circuit continues heating or cooling the room at the set temperature for the first one hour then automatically lowers the temperature setting slightly in the case of cooling or raises it slight...

Страница 50: ...icrocomputer doesn t have a signal from the sensor in 20 minutes it judges that nobody is in the room and operates the unit in temperature sifted 2 C from the set temperature Cooling 2 C higher Dry 1...

Страница 51: ...so as to prevent this phenomena After this 40 minutes the prohibition of the thermostat off is cancelled and it can realize the conditions to conduct thermostat off depending on the room temperature I...

Страница 52: ...the function becomes effective when the operation is started If this button is pressed in powerful operation the powerful operation is reset and this function becomes effective The HOME LEAVE button...

Страница 53: ...riod of twenty minutes Ex Powerful operation in cooling mode Operation mode Fan speed Target set temperature Cooling H tap 90 rpm 18 C Dry Dry rotating speed 50 rpm Normally targeted temperature in dr...

Страница 54: ...orizing Function This filter incorporates the benefits the Air Purifying Filter and Photocatalytic Deodorizing Filter in a single unit Combining the two filters in this way increases the active surfac...

Страница 55: ...operation must be halted 2 The discharge pipe thermistor is used for detecting the discharge thermistor disconnected C Indoor Heat Exchanger Thermistor DCN 1 The indoor heat exchanger thermistor is us...

Страница 56: ...e used in place of the inner temperature of the compressor rises abnormally the operating frequency drops or the operation must be halted 2 The discharge pipe thermistor is used for detecting the disc...

Страница 57: ...cooling including drying Note Unless specified otherwise an indoor dry operation command must be regarded as cooling operation Air conditioner control mode Forced operating mode Forced cooling for Pum...

Страница 58: ...freeze prevention defrost 3 Determine lower limit frequency Set a maximum value as an lower limit frequency among the frequency lower limits of the following functions Four way valve operating compens...

Страница 59: ...rom the frequency previously calculated 2 I control If the operating frequency is not change more than a certain fixed time adjust the frequency up and down according to the D value obtaining the fixe...

Страница 60: ...he operation stopped Detail The OFF delay of four way valve Energize the coil for 150 sec after unit operation is stopped 3 3 3 Four Way Valve Operation Compensation Outline Heat Pump Only At the begi...

Страница 61: ...essor operation stops If a drooping current is continues for 1 0 second after rushing on the drooping zone the frequency will be 2 Hz drooping Repeating the above drooping continues until the current...

Страница 62: ...start with the indoor heat exchanger temperature after 2 sec from operation start Control in Each Zone 3 7 Heating Peak cut Control Outline Heat Pump Only During heating operation the signals being se...

Страница 63: ...ling Operation When the outdoor air temperature is lower than 37 C the fan tap must be set to L 2 When Heating Operation When the outdoor air temperature is higher than 4 C the fan tap must be turned...

Страница 64: ...ing cycle reverse cycle The defrosting time or outdoor heat exchanger temperature must be more than its fixed value when finishing Detail Conditions for Starting Defrost The starting conditions must b...

Страница 65: ...charge pipe temperature control Detail The followings are the examples of control which function in each mode by the electronic expansion valve control R2833 Fully closed when power is turned ON Open...

Страница 66: ...12 6 Disconnection of the Discharge Pipe Thermistor Outline Detect a disconnected discharge pipe thermistor by comparing the discharge pipe temperature with the condensation temperature If any is dis...

Страница 67: ...t 3 12 8 Target Discharge Pipe Temperature Control Obtain the target discharge pipe temperature from the indoor and outdoor heat exchanger temperature and adjust the electronic expansion valve opening...

Страница 68: ...be regarded as gas insufficient In addition to such conventional function if the discharge temperature is higher than the target discharge pipe temperature and the electronic expansion valve is fully...

Страница 69: ...abnormal and not in the 3 minute stand by mode 2 The operating mode of the outdoor unit is the stop mode 3 The forced operation is ON The forced operation is allowed when the above and conditions are...

Страница 70: ...struction 63 2 1 Safety Precautions 63 2 2 Names of Parts 65 2 3 Preparation before Operation 68 2 4 AUTO DRY COOL HEAT FAN Operation 71 2 5 Adjusting the Air Flow Direction 73 2 6 POWERFUL Operation...

Страница 71: ...er method of using it In order to meet this expectation of the users giving sufficient explanations taking enough time can be said to reduce about 80 of the requests for servicing However good the ins...

Страница 72: ...repairs accompanying adding refrigerant check the content of the repairs with our service staff Do not attempt to install the air conditioner by your self Incorrect work will result in water leakage e...

Страница 73: ...e Incomplete draining may cause wetting of the building furniture etc Do not operate the air conditioner with wet hands Do not wash the indoor unit with excessive water only use a slightly wet cloth D...

Страница 74: ...Si04 306 Instruction System Configuration 65 2 2 Names of Parts 4 Indoor Unit Main unit control panel 7 14 11 12 13 4 3 1 2 9 10 8 6 5 16 15...

Страница 75: ...u use HOME LEAVE Operation page 16 14 Indoor Unit ON OFF switch Push this switch once to start operation Push once again to stop it The operation mode refer to the following table This switch is usefu...

Страница 76: ...Press once again to stop it 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN page 10 8 SILENT button for OUTDOOR UNIT SILENT operation page 15 9 FAN setting button It select...

Страница 77: ...lace the two old batteries together When the system is not used for a long time take the batteries out We recommend replacing once a year although if the remote controller display begins to fade or if...

Страница 78: ...Fix the holder to a wall a pillar etc with the screws supplied with the holder 3 Place the remote controller in the remote controller holder ATTENTION About remote controller Never expose the remote...

Страница 79: ...g period for example in spring or autumn turn the breaker OFF Use the air conditioner in the following conditions Operation outside this humidity or temperature range may cause a safety device to disa...

Страница 80: ...dvances the mode setting in sequence AUTO DRY COOL HEAT FAN 2 Press ON OFF button The OPERATION lamp lights up To stop operation 3 Press ON OFF button again Then OPERATION lamp goes off To change the...

Страница 81: ...d all parts of the room After the start of heating operation it takes some time before the room gets warmer In heating operation frost may occur on the outdoor unit and lower the heating capacity In t...

Страница 82: ...lap have reached the desired position press SWING button once more The display will go blank The flap will stop moving To adjust the vertical blades louvers 3 Press SWING button The display will light...

Страница 83: ...ed the flaps swinging range depends on the operation mode See the figure Three Dimensional 3 D Airflow Using three dimensional airflow circulates cold air which tends to collected at the bottom of the...

Страница 84: ...on there are some functions which are not avail able To cancel POWERFUL operation 2 Press POWERFUL button again NOTE Notes on POWERFUL operation In COOL and HEAT mode To maximize the cooling heating e...

Страница 85: ...tion 2 Press SILENT button again NOTE This function is available in COOL HEAT and AUTO modes This is not available in FAN and DRY mode POWERFUL operation and OUTDOOR UNIT SILENT operation cannot be us...

Страница 86: ...lease set the temperature and air flow rate for HOME LEAVE operation Record your preferred temperature and air flow rate 1 Press HOME LEAVE button Make sure is displayed in the remote control display...

Страница 87: ...ill be welcomed by a comfortably air conditioned room Push the HOME LEAVE Operation button again and the air conditioner will adjust capacity to the set temperature for normal operation Set the unit t...

Страница 88: ...LLIGENT EYE operation 1 Press SENSOR button To cancel the INTELLIGENT EYE operation 2 Press SENSOR button again EX C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SILENT ON CANCEL OFF SWING 1 2 SENSO...

Страница 89: ...location the speed of passersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and light reflected off of mirrors as passersby INTELLIGENT EYE operation wi...

Страница 90: ...the setting rapidly 3 Press OFF TIMER button again The TIMER lamp lights up To cancel the OFF TIMER Operation 4 Press CANCEL button The TIMER lamp goes off Notes When TIMER is set the present time is...

Страница 91: ...he setting rapidly 3 Press ON TIMER button again The TIMER lamp lights up To cancel ON TIMER operation 4 Press CANCEL button The TIMER lamp goes off To combine ON TIMER and OFF TIMER A sample setting...

Страница 92: ...it with cloth dry it up in the shade after washing 4 Attach the front grille Align the rotation dowels on the left and right of the front panel with the slots then push them all the way in Close the...

Страница 93: ...dust does not come off easily wash them with neutral detergent thinned with lukewarm water then dry them up in the shade It is recommended to clean the air filters every two weeks Air purifying filter...

Страница 94: ...outdoor unit Check that the earth wire is not disconnected or broken Check that the drain comes smoothly out of the drain hose during COOL or DRY operation If no drain water is seen water may be leak...

Страница 95: ...when the air conditioner is in defrost operation In COOL or DRY mode Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips Mists come out of the indoor unit Th...

Страница 96: ...re the air flow rate and the air direction set appropriately Is the unit set to the INTELLIGENT EYE mode page 18 Operation stops suddenly OPERATION lamp flashes Are the air filters clean Is there anyt...

Страница 97: ...It is recommended to have periodical maintenance by a specialist aside from regular cleaning by the user For specialist maintenance contact the service shop where you bought the air conditioner The m...

Страница 98: ...oor Unit 99 4 6 Signal Transmission Error between Indoor and Outdoor Units 100 4 7 OL Activation Compressor Overload 101 4 8 Compressor Lock 102 4 9 DC Fan Lock 103 4 10 Input Over Current Detection 1...

Страница 99: ...tion 2 When a signal transmission error occurs between the indoor and outdoor units In either case conduct the diagnostic procedure described in the following pages Location of Operation Lamp Troubles...

Страница 100: ...for heat pump model and cooling operation cannot be used when the outside temperature is below 5 C 10 C for Europe Diagnosis with remote controller indication 93 Equipment operates but does not cool o...

Страница 101: ...ence shown below and notifies with a long beep Note 1 A short beep and two consecutive beeps indicate non corresponding codes 2 To cancel the code display hold the timer cancel button down for 5 secon...

Страница 102: ...99 C9 Room temperature thermistor abnormality 99 Outdoor Unit E5 OL activation compressor overload 101 E6 Compressor lock 102 E7 DC fan lock 103 E8 Input over current detection 104 EA Four way valve...

Страница 103: ...tion in approximately 10 continuous seconds Supposed Causes Faulty indoor unit PCB Faulty connector connection Troubleshooting Note Connector Nos vary depending on models Connector connection check no...

Страница 104: ...according to the temperature detected by the indoor unit heat exchanger thermistor Malfunction Decision Conditions High pressure control During heating operations the temperature detected by the indoo...

Страница 105: ...r thermistor check Check the intake air filter Check the air passage YES YES R1401 Check the dust accumulation on the indoor unit heat exchanger YES YES Is there any short circuit Is it very dirty Is...

Страница 106: ...n motor operation Malfunction Decision Conditions When the detected rotation speed is less than 50 of the H tap under maximum fan motor rotation demand Supposed Causes Operation halt due to short circ...

Страница 107: ...t of fan motor connector Is motor power voltage DC 200V generated Is motor control power voltage DC 15V generated Turn off power supply and disconnect fan motor connector then turn power ON again Does...

Страница 108: ...an 120 ohms or below about 50 C more than 1 860 kohms Note The values vary slightly in some models Supposed Causes Faulty connector connection Faulty thermistor Faulty PCB Troubleshooting Check No 6 R...

Страница 109: ...al transmission error due to breaking of wire in the connection wires between the indoor and outdoor units wire No 2 Troubleshooting Check No 10 Refer to P 131 Check the outdoor unit s LED A Check the...

Страница 110: ...leshooting Check No 4 Refer to P 126 Check No 5 Refer to P 127 Check No 6 Refer to P 128 Check No 11 Refer to P 131 Insert the thermistor in position Replace the discharge pipe thermistor Replace the...

Страница 111: ...curs 16 times Clearing condition Continuous run for about 5 minutes normal Supposed Causes Compressor locked Troubleshooting Turn off the power Disconnect the harnesses U V and W Inverter checker Part...

Страница 112: ...for about 5 minutes normal Supposed Causes Fan motor breakdown Harness or connector disconnected between fan motor and PCB or in poor contact Foreign matters stuck in the fan Troubleshooting Check No...

Страница 113: ...ing CT input with the compressor running continues for 2 5 seconds CT input Above 20 A The system will be shut down if the error occurs 16 times Clearing condition Continuous run for about 5 minutes n...

Страница 114: ...bove its stop level NO YES Normal NO YES Any LED off YES NO Check with the inverter checker Turn off the power and reconnect the harnesses Turn on the power again and get restarted Turn off the power...

Страница 115: ...to see if they function within their normal ranges in the operating mode Malfunction Decision Conditions A following condition continues over 1 minute after operating 10 minutes Cooling dry operation...

Страница 116: ...er switch before connect or disconnect connector or parts damage may be occurred Four way valve coil disconnected loose YES YES NO Functioning NO Check No 11 Check the refrigerant line Malfunctioning...

Страница 117: ...lowing 60 minute compressor running time total time Supposed Causes Refrigerant shortage Four way valve malfunctioning Discharge pipe thermistor defective heat exchanger or outdoor temperature thermis...

Страница 118: ...elay cable disconnected Compressor itself defective Outdoor unit PCB defective Stop valve closed Input voltage out of specification Troubleshooting Check No 13 Refer to P 132 Replace the outdoor unit...

Страница 119: ...on Conditions The compressor running frequency is below 55 Hz and the CT input is below 0 1 V The input current is also below 1 25 A If this error repeats 4 times the system will be shut down The erro...

Страница 120: ...tch before connect or disconnect connector or parts damage may be occurred Running current as shown at right with relay cable 1 or 2 YES Current guideline 2 sec Time Rising with increasing frequency C...

Страница 121: ...ture Malfunction Decision Conditions The thermistor input is above 4 96 V or below 0 04 V with the power on Error J3 is judged if the discharge pipe thermistor temperature is smaller than the condense...

Страница 122: ...emperature thermistor l Outdoor air thermistor Replace the following thermistor l Indoor unit heat exchanger thermistor Replace the outdoor unit PCB Replace the indoor unit PCB R2849 Caution Be sure t...

Страница 123: ...in thermistor with the compressor off Malfunction Decision Conditions With the compressor off the radiation fin temperature is above 80 C above 75 C in the case of 7 1kW class Reset is made when the t...

Страница 124: ...ion Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Error again or outdoor unit fan activated YES l Fin thermistor NO Slightly dirty Check No 9...

Страница 125: ...diation fin temperature with the compressor on is above 90 C If a radiation fin temperature rise takes place 4 times successively the system will be shut down The error counter will reset itself if th...

Страница 126: ...r the power transistor Replace the fan motor Correct the connectors and fan motor leads Replace the outdoor unit PCB Clean up the radiation fin R2851 Caution Be sure to turn off power switch before co...

Страница 127: ...s running An output over current input is fed from the output over current detection circuit to the microcomputer The system will be shut down if the error occurs 16 times Clearing condition Continuou...

Страница 128: ...cted for part replacement for example and the system is interrupted by an output over current take the following procedure Error again NO YES NO YES Voltage as rated YES NO Short circuit or breakage b...

Страница 129: ...ssor running frequency Voltage However when the status of running frequency 55 Hz is kept on for a certain time Note The values are different from model to model Gas shortage detection II If a gas sho...

Страница 130: ...xchanger thermistor 1 Replace the PCB 2 Replace the compressor Procedure complete R2853 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred...

Страница 131: ...n Continuous run for about 60 minutes normal Supposed Causes Supply voltage not as specified Over voltage detector or DC voltage detection circuit defective PAM control part s defective Troubleshootin...

Страница 132: ...ng sensed by the heat exchanger thermistor exceeds the limit Malfunction Decision Conditions Activated when the temperature being sensed by the heat exchanger thermistor rises above 60 C Deactivated w...

Страница 133: ...the connector or fan motor lead wires Replace the heat exchanger thermistor Replace PCB Replace the electronic expansion valve or coil Replace the PCB Change the air outlet grille position Change the...

Страница 134: ...connection 2 Check motor control voltage output pins 2 1 7 6 5 4 3 2 1 Motor power supply voltage Unused Unused P 0V reference potential Motor control voltage 15 VDC Rotation command voltage 1 5 VDC...

Страница 135: ...ter Check the conductivity between pins 1 3 and 6 and between pins 2 4 and 5 If there is no conductivity between the pins the EV coil is faulty 4 If no EV generates latching sound in the above step 2...

Страница 136: ...t PCB Replace the four way valve coil Replace the four way valve R2856 NO Four way valve coil Cooling dry No continuity Heating Continuity YES YES Four way valve coil resistance at 1500 ohms NO S80 vo...

Страница 137: ...s on the PCB and measure the resistance of each thermistor using tester The relationship between normal temperature and resistance is shown in the graph and the table below Thermistor R25 C 20k B 3950...

Страница 138: ...r Change the installation location or direction Check the outside air temperature temperature of air taken in by the outdoor unit The outside air temperature shall be 43 C or lower Check the allowable...

Страница 139: ...valve Replace the pipe installed at the site Clean Replace the compressor R1443 YES YES YES NO NO NO NO At the heat exchanger and air filter dirty Is the stop valve open Is the connection pipe deforme...

Страница 140: ...form disturbance near the zero cross sections circled in Fig 2 5 1 9 Inverter Units Refrigerant System Check Check No 11 Fig 1 Fig 2 Refrigerant system check Check for gas leaks See the section on ins...

Страница 141: ...rning off the circuit breaker z If unavoidably necessary to touch a live part make sure the power transistor s supply voltage is below 50 V using the tester z For the UVW make measurements at the Fast...

Страница 142: ...eing applied 1 Stop the operation first and then the power off and disconnect the connector S70 2 Make sure there is about DC 270 V between pins 4 and 7 3 With the system and the power still off recon...

Страница 143: ...Check Si04 306 134 Service Diagnosis...

Страница 144: ...es 141 1 4 Removal of the Electrical Box PCB Swing Motor 143 1 5 Removal of the Heat Exchanger 149 1 6 Removal of the Fan Rotor Fan Motor 152 2 Outdoor Unit 154 2 1 Removal of the Panels and Plates 15...

Страница 145: ...before disassembling work Step Procedure Points 1 Features When the signal receiver catches a signal from the remote controller it produces beep sound and the operation lamp blinks 2 Remove the air f...

Страница 146: ...ir filters with displaying FRONT on the front side Insert two claws of the air filter completely 3 Remove an air purifying filter with photocatalytic deodorizing function 1 Push up the bottom of an ai...

Страница 147: ...While opening the front panel further than it stops release both axes and remove the front panel Slide the front panel side to side to release each axis Align the right and left axes with grooves in...

Страница 148: ...sassembling work Step Procedure Points 1 Remove the service cover 1 Loosen the screw and remove the service cover by the knob No field setting switch is inside it You can remove the front grille witho...

Страница 149: ...ee hooks on the center and the both sides of the upper part Refer to the removal procedure in a reverse way when reassembling 3 Pull the upper part of the front grille out and lift the lower part up a...

Страница 150: ...zontal blades 1 Open the horizontal blades It has no fixing screws inside blades though previous models had 2 Undo the left pivot of the horizontal blades 3 Bend the horizontal blades slightly and rel...

Страница 151: ...ndoor Unit Si04 306 142 Removal Procedure 2 Remove the vertical blades 1 Undo the right and left pivots 2 Undo the three claws 3 Pull the vertical blades rightwards and remove it Step Procedure Points...

Страница 152: ...re to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the front grille Parts layout 2 Remove the drip proof plate 1 Loosen the scr...

Страница 153: ...gs Loosen the screw and remove the terminal strip board You can remove the electrical box without detaching the terminal strip board Screw M4 25 2 Disconnect the connectors for fan motor S1 3 Disconne...

Страница 154: ...ft and undo the back claw The electrical box has a claw on its back 6 Pull the electrical box out towards you Hook the back claw of the electrical box when reassembling 7 Loosen the screw on the elect...

Страница 155: ...e lower side Release the claws on the upper side 10 Cut the clamp 11 The receiver units contain four PCBs Remove each PCB with releasing claws Disconnect every connector from each PCB Remove the recei...

Страница 156: ...two claws on the upper side Remove the control PCB 2 Control PCB indoor unit S1 connector for the fan motor S21 HA S26 connector for the room temperature thermistor S32 connector for the heat exchange...

Страница 157: ...ing motor for vertical blades 1 Release the swing axis on the right side Releasing the swing axis 2 Loosen the two screws and detach the swing motor assembly 3 Loosen the two screws and remove the swi...

Страница 158: ...ending on the model into refrigerant cycle Contaminating of air or other gas causes abnormal high pressure in refrigerating cycle and this results in pipe breakage or personal injuries Pay attention s...

Страница 159: ...the indoor unit from the installation plate 3 Remove the piping fixture 1 Release the claw on the upper side of the piping fixture on the back of the unit 4 Remove the heat exchanger 1 Widen the auxil...

Страница 160: ...claws on the right side and release 4 Pull the heat exchanger to the front side and undo the claws completely and then lift it Caution When removing or reinstalling heat exchanger be sure to wear pro...

Страница 161: ...f all power supplies before disassembling work Step Procedure Points 1 Remove the right side panel 1 Loosen the two screws You can remove the fan rotor without detaching the right side panel 2 Lift th...

Страница 162: ...otor and the bottom frame 2 When reassembling the fan motor align the end of the connector with the height of for play 4 Remove the bearing 1 Remove the fan rotor The bearing is on the left side 2 Loo...

Страница 163: ...ure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the panels and plates Take care not to cut your finger by the fins of the h...

Страница 164: ...cedure 155 The front grille has four claws Slide the discharge grille upwards and remove it 3 Loosen the six screws of the front panel 4 Push the front panel and undo the claw Lift the clamp plate and...

Страница 165: ...claw and then the left side claws Remove the front panel Lift the front panel and remove it while pushing the right side panel inwards Lift the front panel and undo the left side claws Fit the left si...

Страница 166: ...Removal Procedure 157 2 Remove the stop valve cover 1 Loosen the screw of the stop valve cover 2 Pull down the stop valve cover to undo the claws and remove it The stop valve cover has six claws Step...

Страница 167: ...work Step Procedure Points Remove the top panel and the front panel 1 Remove the electrical box cover This procedure is not necessary to remove the propeller fan only 1 Loosen the screw on the back of...

Страница 168: ...Si04 306 Outdoor Unit Removal Procedure 159 2 Remove the fan motor 1 Disconnect the connector for fan motor S70 2 The illustration shows arrangement of the fan motor lead wire Step Procedure Points...

Страница 169: ...rocedure 3 Unscrew the washer fitted nut M10 of the propeller fan with a spanner Align mark of the propeller fan with D cut section of the motor shaft when reassembling 4 Remove the four screws from t...

Страница 170: ...06 Outdoor Unit Removal Procedure 161 5 Pull the fan motor out Put the lead wire through the back of the motor when reassembling so as not to be entangled with the propeller fan Step Procedure Points...

Страница 171: ...disassembling work Step Procedure Points Remove the top panel and the front panel 1 Remove the right side panel Terminal strip number black 1 power supply white 2 power supply red 3 transmission yell...

Страница 172: ...part and the one claw of the upper back when reassembling 2 Disconnect harnesses 1 Loosen the fixing screw of the cable way board Service monitor PCB Step Procedure Points R2701 Claw R2702 Claws S52...

Страница 173: ...trip HE2 yellow green to the terminal strip earth HAC1 black from the control PCB AC1 HE1 yellow green from the control PCB E Power supply PCB 4 Disconnect the connectors of the front side S20 electro...

Страница 174: ...wo claws and release the control PCB from the ditch of the front side 7 Disconnect the harnesses while opening the control PCB S10 to the terminal strip AC2 to the terminal strip 8 Disconnect the conn...

Страница 175: ...r unit S10 to the terminal strip S20 electronic expansion valve S31 to CN14 of the SPM S32 to CN11 of the SPM S33 to S34 of the MID S40 overload protector S51 to S52 of the service monitor PCB S71 to...

Страница 176: ...Si04 306 Outdoor Unit Removal Procedure 167 11 Disconnect the relaying wire connector for the compressor 12 Release the clamp by pliers 13 Disconnect the reactor harness Step Procedure Points R2715...

Страница 177: ...Outdoor Unit Si04 306 168 Removal Procedure 14 Pull the clamp and draw the thermistor harness out from the back of the electrical box 15 Loosen the screw of the electrical box Step Procedure Points...

Страница 178: ...Si04 306 Outdoor Unit Removal Procedure 169 16 Release the clamp of the four way valve harness 17 Lift the electrical box and remove it Step Procedure Points R2720...

Страница 179: ...0 minutes or more after turning off all power supplies before disassembling work Step Procedure Points Remove the electrical box 1 Remove the partition plate 1 Release the clamp by pliers 2 Loosen the...

Страница 180: ...Si04 306 Outdoor Unit Removal Procedure 171 3 Lift the partition plate and remove it 4 Loosen the screw Slide the reactor and remove it from the partition plate Step Procedure Points...

Страница 181: ...e disassembling work Step Procedure Points 1 Disconnect the harness of each thermistor 2 Release the discharge pipe thermistor Pay attention to the direction of the clip so as not to touch the lead wi...

Страница 182: ...the sound blanket side outer are torn easily remove the blanket carefully 5 Remove the sound blanket top upper 6 Remove the sound blanket top lower 7 Remove the sound blanket side inner Since the pipi...

Страница 183: ...brazing Braze it quickly when no nitrogen gas can be used 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected by heat For t...

Страница 184: ...putty Before working make sure that the refrigerant is empty in the circuit 3 Heat up the two brazed parts of the electronic expansion valve and disconnect Be sure to apply nitrogen replacement when h...

Страница 185: ...ait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the terminal cover 2 Disconnect the lead wires of the compressor Be careful so as n...

Страница 186: ...rise toxic gas Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Be careful so as not to burn the compressor terminals or the name plate 5 Heat up the...

Страница 187: ...Outdoor Unit Si04 306 178 Removal Procedure...

Страница 188: ...Si04 306 Others 179 Part 8 Part 8 Part 8 Part 8 Others Others Others Others 1 Others 180 1 1 Test Run from the Remote Controller 180 1 2 Jumper Settings 181...

Страница 189: ...1 Measure the supply voltage and make sure that it falls in the specified range 2 Trial operation should be carried out in either cooling or heating mode 3 Carry out the test operation in accordance w...

Страница 190: ...the drip proof plate 4 tabs 4 Cut the address jumper JA on the control PCB Wireless remote controller 1 Slide the front cover and take it off 2 Cut the address jumper J4 1 2 2 Jumper Setting R2871 R2...

Страница 191: ...Others Si04 306 182 Others...

Страница 192: ...Appendix 183 Part 9 Part 9 Part 9 Part 9 Appendix Appendix Appendix Appendix 1 Piping Diagrams 184 1 1 Indoor Units 184 1 2 Outdoor Units 186 2 Wiring Diagrams 190 2 1 Indoor Units 190 2 2 Outdoor Un...

Страница 193: ...60BVM FTK X D60BVMA FTK X D60BVMT FTKD18BVMS FIELD PIPING FIELD PIPING 12 7CuT 6 4CuT CROSS FLOW FAN FAN MOTOR 7 9CuT INDOOR UNIT 12 7CuT M REFRIGERANT FLOW ON HEAT EXCH THERMISTOR HEATING COOLING 4D0...

Страница 194: ...185 FTKD71BVM FTK X D71BVMA FTK X D71BVMT FTKD 24 28 BVMS 15 9CuT FIELD PIPING FIELD PIPING 9 5CuT CROSS FLOW FAN FAN MOTOR 7 9CuT INDOOR UNIT 12 7CuT M HEAT EXCHANGER ON HEAT EXCH THERMISTOR REFRIGER...

Страница 195: ...S STOP VALVE VALVE MOTOR OPERATED STOP VALVE LIQUID FIELD PIPING FIELD PIPING REFRIGERANT FLOW 12 7CuT 6 4CuT COOLING 3D037835A OUTDOOR UNIT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7...

Страница 196: ...GAS STOP VALVE STOP VALVE LIQUID FIELD PIPING FIELD PIPING REFRIGERANT FLOW 12 7 CuT 6 4 CuT COOLING 3D037851A OUTDOOR UNIT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT DISC...

Страница 197: ...ERATED STOP VALVE LIQUID FIELD PIPING FIELD PIPING REFRIGERANT FLOW 12 7 CuT 6 4 CuT HEATING COOLING 3D034262C OUTDOOR UNIT 12 7CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT DISCHARGE P...

Страница 198: ...OP VALVE LIQUID FIELD PIPING FIELD PIPING REFRIGERANT FLOW 6 4 CuT 12 7 CuT 3D037849A COOLING HEATING 12 7CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT DISCHARGE PIPE THERMISTOR EXCHANG...

Страница 199: ...INTED CIRCUIT BOARD PROTECTIVE EARTH X1M 3 2 1 THE MAIN POWER SUPPLY IS ON AGAIN TURNED OFF AND THEN BACK NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF FIELD WIRING CAUTION 3 2 1 3D038065C OUTDOOR...

Страница 200: ...IS ON AGAIN TURNED OFF AND THEN BACK NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF FIELD WIRING CAUTION 3 2 1 OUTDOOR 3D038466A CONTROLLER WIRELESS REMOTE PCB4 PCB3 LED1 H1P R1T t S37 S38 LED2 H2P...

Страница 201: ...Wiring Diagrams Si04 306 192 Appendix FTKD 18 24 28 BVMS...

Страница 202: ...72 S71 1 BLU 8 8 FU201 3 15A RED 1 1 S70 BRN W V U N 7 1 8 RED S33 S34 YLW WHT BLU RED BRN ORG RED BRN BLU YLW X11A 10 10 BLU YLW BRN BLU RED 1 3D037866D GRY V S40 1 3 M1F M1C M M BLK 4 W U Q1L BLK N...

Страница 203: ...Wiring Diagrams Si04 306 194 Appendix RKD 18 24 28 BVMS...

Страница 204: ...transistor check 132 thermistor resistance check 128 turning speed pulse input on the outdoor unit PCB check 133 check No 01 125 check No 02 125 check No 04 126 check No 05 127 check No 06 128 check...

Страница 205: ...28 30 G gas piping 149 H H1 30 H2 30 H6 109 H8 110 H9 112 HA 28 147 HAC1 30 164 hall IC 37 97 HE1 30 164 HE2 30 164 heat exchanger 151 154 heat exchanger thermistor 46 47 99 113 heating peak cut cont...

Страница 206: ...113 reactor 171 receiver units 146 remote controller 92 removal procedure 135 right side panel 152 162 room temperature thermistor 99 RTH1 28 S S1 28 144 147 S10 30 165 166 S101 30 165 166 S102 30 166...

Страница 207: ...imer operation 81 top panel 154 troubleshooting 86 93 troubleshooting with the LED indication 90 turning speed pulse input on the outdoor unit PCB check 133 U U0 120 U2 122 U4 100 V V1 28 V3 30 varist...

Страница 208: ...alve performance check 127 freeze up protection control 53 freeze up protection control or high pressure control 95 frequency control 49 frequency principle 34 H heating peak cut control 53 high press...

Страница 209: ...sion error between indoor and outdoor units 100 SPM 32 T target discharge pipe temperature control 58 thermistor cooling only model 47 heat pump model 46 thermistor or related abnormality indoor unit...

Страница 210: ...3 Japan Tokyo office Shinjuku Sumitomo Bldg 6 1 Nishi Shinjuku 2 chome Shinjuku ku Tokyo 163 0235 Japan Zandvoordestraat 300 B 8400 Oostende Belgium z For further improvement specifications or designs...

Отзывы: