Algorithm & Control
19
2.4 Fan Mode
•
Compressor and Outdoor Fan OFF. Indoor Fan remains ON.
•
Only High, Medium and Low fan speeds are allowed.
•
When changing cool mode to fan mode, the compressor will stop and outdoor fan stops based on fan
OFF control.
•
Compressor only ON if the minimum stop time is > 3 minutes and the user change back to cool mode.
•
Fan speed will maintain same as during fan mode.
2.5 Auto Mode
Automatic Cooling / Heating Function
When the automatic operation is selected with the remote controller, the microcomputer automatically
determines the operation mode as cooling or heating according to the room temperature and the set
temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set temperature.
For heat pump only
Mode switching point:
•
From Heating to Cooling
Tr ≥ Ts + 2.5°C (4.5°F)
•
From Cooling to Heating
Tr ≤ Ts – 2.5°C (4.5°F)
During initial operation
•
Cooling operation: Tr > Ts
•
Heating operation: Tr < Ts
2.6 Cold Draft Prevention
During each thermal cut in cycle, the indoor fan speed will modulate according to the indoor heat exchanger
temperature shown as below:
[36°C/96.8°F]
[33°C/91.4°F]
[25°C/77°F]
[20°C/68°F]
[15°C/59°F]
Temperature of
indoor heat
exchanger
Upper limitation of fan speed