SiBE28-804
Field Settings
Test Operation
115
Capacity
When "low humidity application" is selected. Field setting 16(26)-2-03:
Capacity
When "low humidity appli freeze up operation prevention" is selected. Field setting
16(26)-2-04:
Note:
• Operation range on indoor side expanded from minimum 12°CWB to 11°CWB when using LH
setting.
• Do not use a setpoint below 20°C to avoid operation out of the indoor operation range
(11°CWB).
• Be sure to set the indoor fan to high speed.
2.14 Defrost Start Setting
Refer to ‘Defrost Operation’ on P47.
Outdoor
Temp.
(°C-DB)
Indoor Temp. (°C-WB)
11
14
16
18
19
20
22
24
Capacity (% of standard point)
-15
0.62
0.76
0.86
0.95
1.00
1.02
1.07
1.11
-10
0.62
0.76
0.86
0.95
1.00
1.02
1.07
1.11
-5
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
0
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
5
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
10
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
15
0.62
0.81
0.91
1.01
1.12
1.14
1.19
1.24
20
0.62
0.81
0.91
1.07
1.10
1.12
1.16
1.21
25
0.62
0.81
0.91
1.05
1.07
1.09
1.13
1.18
30
0.61
0.81
0.91
1.01
1.04
1.06
1.10
1.14
35
0.61
0.81
0.94
0.98
1.00
1.02
1.06
1.11
40
0.61
0.81
0.90
0.94
0.96
0.98
1.02
1.06
Outdoor
Temp.
(°C-DB)
Indoor Temp. (°C-WB)
11
14
16
18
19
20
22
24
Capacity (% of standard point)
-15
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
-10
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
-5
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
0
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
5
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
10
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.26
15
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.24
20
0.51
0.68
0.78
0.95
1.01
1.06
1.16
1.21
25
0.51
0.68
0.78
0.95
1.00
1.06
1.13
1.18
30
0.51
0.68
0.78
0.95
1.00
1.05
1.10
1.14
35
0.51
0.68
0.78
0.95
1.00
1.02
1.06
1.11
40
0.51
0.67
0.78
0.94
0.96
0.98
1.02
1.06
Содержание FHQ100BUV1B x 2
Страница 1: ...SiBE28 804 SkyAir RZQ71C7V1B RZQ100 140C7V1B RZQS71 100C7V1B RZQS125 140C7V1B R 410A Heat Pump 50Hz ...
Страница 13: ...SiBE28 804 2 ...
Страница 19: ...Model Name and Power Supply SiBE28 804 8 General Information ...
Страница 29: ...Specifications SiBE28 804 18 Specifications ...
Страница 33: ...Wired Remote Controller SiBE28 804 22 Remote Controller 1 2 Installation ...
Страница 34: ...SiBE28 804 Wired Remote Controller Remote Controller 23 ...
Страница 43: ...SiBE28 804 32 Functional Description 6 Outdoor Unit Fan Speed Control 81 6 1 Outdoor Unit Fan Speed Control 81 ...
Страница 93: ...Outdoor Unit Fan Speed Control SiBE28 804 82 Functional Description ...
Страница 131: ...Test Run and Operation Data SiBE28 804 120 Test Operation ...
Страница 251: ...Troubleshooting by Remote Controller Display LED Display SiBE28 804 240 Troubleshooting ...
Страница 277: ...PCB Layout SiBE28 804 266 Appendix ...
Страница 297: ...RZQ100 140C7 RZQS125 140C7V1B SiBE28 804 286 Removal Procedure ...