TECHNICAL DATA

Split-Sky Air

FH(Y)GZ/BZ/FHYP-B

Ceiling Suspended Unit

Содержание FH35GZ

Страница 1: ...TECHNICAL DATA Split Sky Air FH Y GZ BZ FHYP B Ceiling Suspended Unit...

Страница 2: ...es an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities products and services and to assist in maintaining...

Страница 3: ...l drawings 9 4 Piping diagrams 13 5 Wiring diagrams 14 6 Sound level 16 Sound level data Sound pressure spectrum 7 Accessories 19 Standard accessories Optional accessories 8 Control systems 21 9 Safet...

Страница 4: ...he outdoor unit can easily be mounted on a roof a terrace or placed against an outside wall For equal distribution in larger rooms up to 3 indoor units can be connected to 1 outdoor They are operated...

Страница 5: ...min 13 13 16 medium m3 min low m3 min 10 10 13 Speed steps 2 steps 2 steps 2 steps high rpm low rpm Type Sirocco fan Qty x model 1 x 3D12K1AA1 1 x 3D12K1AA1 1 x 4D12K1AA1 Qty x motor output W 1 x 62 1...

Страница 6: ...55 FAN Air flow rate cooling high m3 min 17 24 30 medium m3 min low m3 min 14 20 25 Speed steps 2 steps 2 steps 2 steps high rpm low rpm Type Sirocco fan Qty x model 1 x 4D12K1AA1 1 x 3D12K2AA1 1 x 4D...

Страница 7: ...RP100B7V1 W1 T1 RP125B7W1 T1 CURRENT Nominal running current cooling A Maximum running current A For indoor units only FHYP71BV1 FHYP100BV1 FHYP125BV1 POWER SUPPLY V1 V1 V1 NOMINAL DISTRIBUTION SYSTE...

Страница 8: ...ating high m3 min 13 13 13 13 16 16 medium m3 min low m3 min 10 10 10 10 13 13 Speed cooling heating steps 2 steps high rpm low rpm Type Sirocco fan Qty x model 1 x 4D12K1AA1 Qty x motor output W 1 x...

Страница 9: ...5 58 58 60 60 low dB A 51 51 53 53 55 55 FAN Air flow rate cooling heating high m3 min 17 17 24 24 30 30 medium m3 min low m3 min 14 14 20 20 25 25 Speed cooling heating steps 2 steps 2 steps 2 steps...

Страница 10: ...A heating A For indoor units only FHYP71BV1 FHYP100BV1 FHYP125BV1 POWER SUPPLY V1 V1 V1 NOMINAL DISTRIBUTION SYSTEM VOLTAGE Phase 1 1 1 Frequency Hz 50 50 50 Voltage V 220 240 220 240 220 240 NOTES 1...

Страница 11: ...ection from the front 3TW20524 1A Suspension position FH35BZV1 FHYP35 45BV1 View from the front 780 From the floor side 2500 or more Required space Note 1 Location of unit s name plate bottom of fan h...

Страница 12: ...position Required space Required space Note 2 FH60BZV1 View from the front 780 From the floor side 2500 or more Required space Note 1 Location of unit s name plate bottom of fan housing inside the su...

Страница 13: ...g position Required space Required space Note 2 FHYP100BV1 View from the front 780 From the floor side 2500 or more Required space Note 1 Location of unit s name plate bottom of fan housing inside the...

Страница 14: ...ion opening lid 10 Upward piping and wiring connection opening lid 11 Right side pipe connection slit hole 12 Left back drain pipe connection slit hole 13 Right side drain pipe connection slit hole 14...

Страница 15: ...4 15 9 FHYP60 71BV1 9 5 15 9 FHYP100 125BV1 9 5 19 1 To outdoor unit Indoor unit O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe Heat exchanger Re...

Страница 16: ...e selector switch SS1 SS2 by installation manual and engeneering materials etc Receiver display unit Note 6 Note 6 Note 7 2TW21006 1C FHY35 45GZ7V1 33S Limit switch swing flap A1P Printed circuit boar...

Страница 17: ...dress set Connector for optional parts X15A Connector float switch X25A Connector drain pump X30A Connector interface adaptor for sky air series X33A Connector adaptor for wiring X35A Connector group...

Страница 18: ...pressure level Sound power level H cooling heating 230V Measuring location 50Hz Heat pump H cooling heating L cooling heating FHY35GZ7 38 38 33 33 54 54 FHY45GZ7 39 39 34 34 55 55 FHYP35B 37 37 32 32...

Страница 19: ...level Octave band sound pressure level FHY35GZ FHY45GZ Octave band center frequency Hz Octave band center frequency Hz 4D028280 4D028281 4D028282 DU423 489 DU425 4156A approximate threshold hearing f...

Страница 20: ...threshold hearing for continuous noise approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise H L H L H L Note 1 Operation sound is measured in an anecho...

Страница 21: ...on manual Operation manual Quantity 1 of each 1 pc Shape j 8 For gas pipe j 7 For liquid pipe j 8 Large j 7 Small Remote control cord 1 set Staple x4 flat head screw X4 Drain hose 1 pc Clamp 1 pc Wash...

Страница 22: ...Remark FHYP BV1 FH BZV1 35 45 60 71 100 125 Replacement long life filter KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160 Drain up kit KDU50B50VE KDU50B71VE KDU50B125VE L type piping kit for upward direc...

Страница 23: ...8 Control systems 8 1 Wired remote control BRC1B517 FH Y GZ BRC1B517 Remote control Fig 1 BRC1B517 Ceiling Suspended Unit R 407C FH Y GZ BZ FHYP B 10 8 8 1 21 Split Sky Air Indoor Units...

Страница 24: ...This display shows PROGRAMMED TIME of the system start or stop 9 DISPLAY O SET TEMPERATURE This display shows the set temperature 10 DISPLAY B C FAN SPEED The display shows the set fan speed 11 DISPL...

Страница 25: ...he desired MODE NO With the E button 3 During group control when setting by each indoor unit push the G button and select the INDOOR UNIT NO To be set This operation is unnecessary when setting by gro...

Страница 26: ...V 5A 250V 5A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 20 OFF 130 5 ON 83 20 OFF 130 5 ON 83 20 OFF 130 5 ON 83 20 OFF 130 5 ON 83 20 OFF 130 5 ON 83 20 3D006611C 10 Insta...