16
Application Information
(5) Additional Charge
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below (unit in gram).
R22 – Cooling Only
Indoor
FDM10CXV1
FDB10CXV1
FDM15CXV1
FDB15CXV1
FDM20CXV1
FDB20CXV1
FDM25CXV1
FDB25CXV1
FDM28CXV1
Outdoor
R10CXV1
R15CXV1
R20CXV1
R25CXV1
R28CXV1
Add. Charge, g/m
16
16
16
39
41
Indoor
FDM28CXV1
FDM30CXV1
FDB30CXV1
FDM30CXV1
FDB30CXV1
FDM38CXV1
Outdoor
R30DXV1
R28CXV1
R30DXV1
R30DXY1
R35DXV1
Add. Charge, g/m
56
41
41
55
54
Indoor
FDM38CXV1
FDM40CXV1
FDB40CXV1
FDM40CXV1
FDB40CXV1
Outdoor
R40DXV1
R40DXY1
R35DXV1
R40DXV1
R40DXY1
Add. Charge, g/m
40
41
54
55
Indoor
FDM50CXV1
FDB50CXV1
FDM60CXV1
FDB60CXV1
Outdoor
R50DXY1
R61DXY1
Add. Charge, g/m
54
102
R22 – Heatpump
Indoor
FDYM10CXV1
FDYB10CXV1
FDYM15CXV1
FDYB15CXV1
FDYM20CXV1
FDYB20CXV1
FDYM20CXV1
FDYB20CXV1
FDYM25CXV1
FDYB25CXV1
Outdoor
RY10CXV1
R15CXV1
RY18CXV1
RY20CXV1
RY25CXV1
Add. Charge, g/m
22
22
16
16
40
Indoor
FDYM28CXV1
FDYM28CXV1
FDYM30CXV1
FDYB30CXV1
Outdoor
RY28CXV1
RY30DXV1
RY30DXY1
RY28CXV1
Add. Charge, g/m
41
41
41
Indoor
FDYM30CXV1
FDYB30CXV1
FDYM38CXV1
FDYM38CXV1
Outdoor
RY30DXV1
RY30DXY1
RY35DXV1
RY40DXV1
RY40DXY1
Add. Charge, g/m
55
41
57
57
Indoor
FDYM40CXV1
FDYB40CXV1
FDYM40CXV1
FDYB40CXV1
FDYM50CXV1
FDYB50CXV1
FDYM60CXV1
FDYB60CXV1
Outdoor
RY35DXV1
RY40DXV1
RY40DXY1
RY50DXY1
RY61DXY1
Add. Charge, g/m
57
55
41
56
106
The additional refrigerant charge amount recommended is a guideline for longer piping application. The
actual charge required may be different from the guideline due to different application and variation in site
conditions.
•
•
DAIKIN_R22 CC.indb 16
DAIKIN_R22 CC.indb 16
11/8/2012 11:40:04 AM
11/8/2012 11:40:04 AM
Содержание FDM10CXV1
Страница 2: ......
Страница 129: ...Outlines Dimensions 126 Model FD Y M28CXV1 Note Dimension in mm Model FD Y M38CXV1 Note Dimension in mm...
Страница 133: ...130 Wiring Diagrams Wiring Diagrams Cooling Only Indoor Unit Model FDM10CXV1 FDB10CXV1 Outdoor Unit Model R10CXV1...
Страница 134: ...131 Wiring Diagrams Indoor Unit Model FDM15CXV1 FDB15CXV1 Outdoor Unit Model R15CXV1...
Страница 135: ...132 Wiring Diagrams Indoor Unit Model FDM20 25CXV1 FDB20 25CXV1 Outdoor Unit Model R20 25CXV1...
Страница 136: ...133 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R28CXV1...
Страница 137: ...134 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXV1...
Страница 138: ...135 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXY1...
Страница 139: ...136 Wiring Diagrams Indoor Unit Model FDM38 40CXV1 FDB40CXV1 Outdoor Unit Model R35 40DXV1...
Страница 140: ...137 Wiring Diagrams Indoor Unit Model FDM38 40 50CXV1 FDB40 50CXV1 Outdoor Unit Model R40 50DXY1...
Страница 141: ...138 Wiring Diagrams Indoor Unit Model FDM60CXV1 FDB60CXV1 Outdoor Unit Model R61DXY1...
Страница 142: ...139 Wiring Diagrams Heatpump Indoor Unit Model FDYM10CXV1 FDYB10CXV1 Outdoor Unit Model RY10CXV1...
Страница 143: ...140 Wiring Diagrams Indoor Unit Model FDYM15CXV1 FDYB15CXV1 Outdoor Unit Model RY15CXV1...
Страница 144: ...141 Wiring Diagrams Indoor Unit Model FDYM20 25CXV1 FDYB20 25CXV1 Outdoor Unit Model RY18 20 25CXV1...
Страница 145: ...142 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY28CXV1...
Страница 146: ...143 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXV1...
Страница 147: ...144 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXY1...
Страница 148: ...145 Wiring Diagrams Indoor Unit Model FDYM38 40CXV1 FDYB40CXV1 Outdoor Unit Model RY35 40DXV1...
Страница 149: ...146 Wiring Diagrams Indoor Unit Model FDYM38 40 50CXV1 FDYB40 50CXV1 Outdoor Unit Model RY40 50DXY1...
Страница 150: ...147 Wiring Diagrams Indoor Unit Model FDYM60CXV1 FDYB60CXV1 Outdoor Unit Model RY61DXY1...
Страница 159: ......