12
Application Information
(2) Installation of Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve
maximum cooling capacity, the location selected for outdoor unit should ful
fi
ll the following requirements:
Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit
cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow suf
fi
cient space for
maintenance around the unit.
Ensure that there is no obstruction of air
fl
ow into or out of the unit. Remove obstacles which block air
intake or discharge.
The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering
the condensing temperature.
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
The location must not be susceptible to dust or oil mist.
Installation Clearance
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to
smooth air
fl
ow. Select the coolest possible place where intake air should not be hotter than the outside
temperature (max. 45
˚
C).
ALL MODEL
A
B
C
D
Minimum Distance
300 mm
1000 mm
300 mm
500 mm
If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt
(coastal area), sulphide gas (near hot spring, oil re
fi
nery plant), such substances may lead to
failure of the unit.
•
•
•
•
•
•
•
DAIKIN_R22 CC.indb 12
DAIKIN_R22 CC.indb 12
11/8/2012 11:40:03 AM
11/8/2012 11:40:03 AM
Содержание FDM10CXV1
Страница 2: ......
Страница 129: ...Outlines Dimensions 126 Model FD Y M28CXV1 Note Dimension in mm Model FD Y M38CXV1 Note Dimension in mm...
Страница 133: ...130 Wiring Diagrams Wiring Diagrams Cooling Only Indoor Unit Model FDM10CXV1 FDB10CXV1 Outdoor Unit Model R10CXV1...
Страница 134: ...131 Wiring Diagrams Indoor Unit Model FDM15CXV1 FDB15CXV1 Outdoor Unit Model R15CXV1...
Страница 135: ...132 Wiring Diagrams Indoor Unit Model FDM20 25CXV1 FDB20 25CXV1 Outdoor Unit Model R20 25CXV1...
Страница 136: ...133 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R28CXV1...
Страница 137: ...134 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXV1...
Страница 138: ...135 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXY1...
Страница 139: ...136 Wiring Diagrams Indoor Unit Model FDM38 40CXV1 FDB40CXV1 Outdoor Unit Model R35 40DXV1...
Страница 140: ...137 Wiring Diagrams Indoor Unit Model FDM38 40 50CXV1 FDB40 50CXV1 Outdoor Unit Model R40 50DXY1...
Страница 141: ...138 Wiring Diagrams Indoor Unit Model FDM60CXV1 FDB60CXV1 Outdoor Unit Model R61DXY1...
Страница 142: ...139 Wiring Diagrams Heatpump Indoor Unit Model FDYM10CXV1 FDYB10CXV1 Outdoor Unit Model RY10CXV1...
Страница 143: ...140 Wiring Diagrams Indoor Unit Model FDYM15CXV1 FDYB15CXV1 Outdoor Unit Model RY15CXV1...
Страница 144: ...141 Wiring Diagrams Indoor Unit Model FDYM20 25CXV1 FDYB20 25CXV1 Outdoor Unit Model RY18 20 25CXV1...
Страница 145: ...142 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY28CXV1...
Страница 146: ...143 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXV1...
Страница 147: ...144 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXY1...
Страница 148: ...145 Wiring Diagrams Indoor Unit Model FDYM38 40CXV1 FDYB40CXV1 Outdoor Unit Model RY35 40DXV1...
Страница 149: ...146 Wiring Diagrams Indoor Unit Model FDYM38 40 50CXV1 FDYB40 50CXV1 Outdoor Unit Model RY40 50DXY1...
Страница 150: ...147 Wiring Diagrams Indoor Unit Model FDYM60CXV1 FDYB60CXV1 Outdoor Unit Model RY61DXY1...
Страница 159: ......