VACUUMING AND CHARGING

Vacuuming is necessary to eliminate all moisture and air from the system. The series II Outdoor Unit is provided with flare 
valve fittings.

Vacuuming The Piping And The Indoor Unit

Except for the outdoor unit which is pre-charged with refrigerant, 
the indoor unit and the refrigerant connection pipes must be air-
purged because the air containing moisture that remains in the 
refrigerant cycle may cause malfunction of the compressor.

Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the vacuum 
pump.
Connect the charging gauge to the service port of the 3-way 
valve.
Start the vacuum pump. Evacuate for approximately 30 
minutes. The evacuation time varies with different vacuum 
pump capacity. Confirm that the charging gauge needle has 
moved towards -760mmHg.

Caution

If the gauge needle does not move to -760mmHg, be sure to 
check for gas leaks (using the refrigerant detector) at flare type 
connection of the indoor and outdoor unit and repair the leak 
before proceeding to the next step.
Close the valve of the changing gauge and stop the vacuum 
pump.
On the outdoor unit, open the suction valve (3 way) and liquid 
valve (2 way) (in anti-clockwise direction) with 4mm key for 
hexagon sacked screw.

Charge Operation

This operation must be done by using a gas cylinder and a precise 
weighing machine. The additional charge is topped-up into the 
outdoor unit using the suction valve via the service port.

Remove the service port cap.
Connect the low pressure side of the charging gauge to the 
suction service port center of the cylinder tank and close the 
high pressure side of the gauge. Purge the air from the service 
hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into the unit, 
close the low pressure side and the gas cylinder valve.
Disconnect the service hose from service port. Put back the 
service port cap.





Refrigerant Piping

Outdoor Unit 3 ways valve

Allen key

Service Port

Flare nut

HIGH PRESSURE GAUGE

GAUGE MANIFOLD

LOW PRESSURE GAUGE

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

-760mmHg

HANDLE 

LO

CHARGE HOSE

VACUUM PUMP 
ADAPTER FOR 
COUNTER FLOW 
PREVENTION

LIQUID VALVE

GAS VALVE 
(3-WAY)

CHECK VALVE

CONFIGURATION OF AIR 
PURGE BY CHARGING

HIGH PRESSURE GAUGE

LOW PRESSURE GAUGE

GAUGE MANIFOLD

-760mmHg

HANDLE 

LO

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

CHARGE HOSE

LIQUID VALVE

GAS VALVE 
(3-WAY)

CHECK VALVE

CONFIGURATION OF AIR 
PURGE BY CHARGING

1 IM-5CKE-0912(0)DAIKIN-EN.indd   18

1 IM-5CKE-0912(0)DAIKIN-EN.indd   18

9/28/12   2:04:19 PM

9/28/12   2:04:19 PM

Содержание FCRN50EXV1

Страница 1: ...TYPE AIR CONDITIONER E Series IM 5CKE 0912 0 DAIKIN Part No R08019038169 English Fran ais Deutsch Italiano Espa ol T rk e Installation Manual R410A Split Type Air Conditioner Manuel D installation Cli...

Страница 2: ...101 113 603 126 60 71C 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S 50C 164 15 34 23 362 73 75 60 71C 164 15 34 23 362 73 75 Dimension Model A B C D E F G H I J K 50 60...

Страница 3: ...in mm I J J D M B G O Dimension Model A B C D E F G H I J K L M N O 90 100 125D 1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28 N N K A L E F H C 1 IM 5CKE 0912 0 DAIKIN EN indd 2 1 IM 5CKE 0912...

Страница 4: ...e Do not overcharge the unit This unit is factory pre charged Overcharge will cause over current or damage to the compressor Ensure that the unit s panel is closed after service or installation Unsecu...

Страница 5: ...e g onto the inside of the service cover 1 factory refrigerant charge of the product see unit name plate 2 2 additional refrigerant amount charged in the field 3 total refrigerant charge 4 contains fl...

Страница 6: ...or when moving it after opening Do not move the unit from packaging while moving until it reaches the installation site Use safe material or protection plates when unpacking it or lifting it to avoid...

Страница 7: ...on the ceiling and fix the hanging rod The installation template is extended according to temperature and humidity Check on dimensions in use The dimensions of the installation template are the same...

Страница 8: ...connector on the indoor unit Drain Test NOTE This Indoor Unit uses a drain pump for condensed water drainage Install the unit horizontally to prevent water leakage or condensation around the air outl...

Страница 9: ...d off before servicing the unit Use screwdriver to unlock the screw on the cover lock grille Remove the cover lock grille and open the intake grille for the service purpose Install the intake grille a...

Страница 10: ...ve wire cover by removing 2 screws as shown in Figure C Wires will go through the hole as shown in Figure D and E respectively without crossing the height of the hole After that wire cover will be ass...

Страница 11: ...Ensure that there is no obstruction of air flow into or out of the unit Remove obstacles which block air intake or discharge The location must be well ventilated so that the unit can draw in and distr...

Страница 12: ...ir Inlet Air Discharge A B Obstacle Obstacle MADE IN MALAYSIA Service Space Obstacle C D Obstacle BASE A DRAIN ELBOW PLUG DRAIN ELBOW Model Indoor FCRN FCQN 50E 60E 71E 100E 100E 125E Outdoor RN RR RY...

Страница 13: ...th the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool Refer Figure III Fix the pipe...

Страница 14: ...Block Power Supply Cable ELECTRICAL WIRING CONNECTION IMPORTANT These values are for information only They should be checked and selected to comply with local and or national codes and regulations Th...

Страница 15: ...2 5 4 Recommended time delay fuse A 25 30 Model Indoor FCRN 100E 125E Outdoor RR 100D 125D Voltage range Indoor FCRN 220 240V 1Ph 50Hz Outdoor RR 380 415V 3N 50Hz Power supply cable size mm2 Number o...

Страница 16: ...of conductors 2 5 5 2 5 5 2 5 5 Recommended time delay fuse A 13 18 25 FCQN 100E RQ 90 100D 1 PH There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm...

Страница 17: ...or Unit Terminal Block Power Supply Cable Outdoor Coil Sensor FCQN 100 125E RQ 100 125D 3 PH Model Indoor FCQN 100E 125E Outdoor RQ 100D 125D Voltage range Indoor FCQN 220 240V 1Ph 50Hz Outdoor RQ 380...

Страница 18: ...ozone layer The working pressure of this new refrigerant is 1 6 times higher than conventional refrigerant R22 thus proper installation servicing is essential Never use refrigerant other than R410Ain...

Страница 19: ...i clockwise direction with 4mm key for hexagon sacked screw Charge Operation This operation must be done by using a gas cylinder and a precise weighing machine The additional charge is topped up into...

Страница 20: ...irst few hours or the damage done during field charging may show up some time later Other typical field charging problems include undercharging overcharging moisture or air in the system etc In time e...

Страница 21: ...d Manifold valve A are both open A There are many ways of charging liquid in a controlled manner into the suction side Use valve A on the manifold gauge set Use the valve on the refrigerant cylinder C...

Страница 22: ...ct Keep the introduction of fresh air intake within 20 of total air flow Also provide a chamber and use a booster fan Sealing Material It is possible to seal one of the four air discharge outlet seali...

Страница 23: ...or Code 1 Room Sensor Open or Short Blink 1 time Blink Fan Blink E1 2 Indoor Coil Sensor Open Blink 2 times Blink Sleep Blink E2 3 Outdoor Coil Sensor Open Blink 3 times Blink Dry Blink E3 4 Compresso...

Страница 24: ...he unit with Scroll Compressor can only rotate in one direction For this reason a protective device phase protector is fitted to prevent incorrect wiring of the electrical phases When the three phases...

Страница 25: ...o the unit Check the following fault conditions and causes for some simple troubleshooting tips Fault Causes Action The compressor does not start operate after 3 minutes from starting the air conditio...

Страница 26: ...nen Ger te bleiben dem Hersteller jederzeit vorbehalten Nel caso ci fossero conflitti nell interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue la versione in lingua inglese...

Отзывы: