Piping Works And Flaring Technique

Do not use contaminated or damaged copper tubing. If any pipings, evaporator or condenser had been exposed or had been 
opened for 15 seconds or more, the system must be vacuumed. Generally, do not remove plastic, rubber plugs and brass 
nuts from the valves, fittings, tubings and coils until it is ready to connect suction or liquid line into valves or fittings.

If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is 
being done. This will eliminate soot formation on the inside walls of the copper tubings.

Cut the pipe stage by stage, advancing the blade of the pipe cutter slowly. Extra force and deep cut will cause more distortion 
on the pipe and thus extra burr. See Figure I.

Remove burrs from cut edges of the pipes with remover 
as shown in Figure II. This will avoid unevenness on the 
flare faces which will cause gas leak. Hold the pipe on 
top position and burr remover at lower position to prevent 
metal chips from entering the pipe.

Insert the flare nuts, mounted on the connection parts 
of both the indoor unit and outdoor unit, into the copper 
pipes.

The exact length of pipe protruding from the top surface 
of the swaging block is determined by the flaring tool. 
Refer Figure III. 

Fix the pipe firmly on the flare die. Match the centers of 
both the flare die and the flaring punch, and then tighten 
the flaring punch fully.

Piping Connection To The Units

Align the center of the piping and tighten the flare nut 
sufficiently with fingers. Refer Figure IV.

Finally, tighten the flare nut with the torque wrench until 
the wrench clicks.

When tightening the flare nut with the torque wrench, 
ensure that the tightening direction follows the arrow 
indicated on the wrench.

The refrigerant pipe connection are insulated by closed 
cell polyurethane.

Pipe Size (mm/in)

Torque, Nm/(ft-lb)

6.35 (1/4")

18 (13.3)

9.52 (3/8")

42 (31.0)

12.70 (1/2")

55 (40.6)

15.88 (5/8")

65 (48.0)

19.05 (3/4")

78 (57.6)

Ø Tube, D

A (mm)

Inch

mm

Imperial

(Wing-nut Type)

Rigid

(Clutch Type)

1/4"

6.35

1.3

0.7

3/8"

9.52

1.6

1.0

1/2"

12.70

1.9

1.3

5/8"

15.88

2.2

1.7

3/4"

19.05

2.5

2.0

Figure III

Copper Tube

Swaging Block

Spanar

Torque Wrench

Indoor Piping

Flare Nut

Flared Tube

Flare Joint

Figure IV

D

A

1/4t

Cutting Copper Tube

Figure I

Figure II

Remove Burr

1 IM-5CKE-0912(0)DAIKIN-EN.indd   12

1 IM-5CKE-0912(0)DAIKIN-EN.indd   12

9/28/12   2:04:18 PM

9/28/12   2:04:18 PM

Содержание FCRN50EXV1

Страница 1: ...TYPE AIR CONDITIONER E Series IM 5CKE 0912 0 DAIKIN Part No R08019038169 English Fran ais Deutsch Italiano Espa ol T rk e Installation Manual R410A Split Type Air Conditioner Manuel D installation Cli...

Страница 2: ...101 113 603 126 60 71C 855 730 328 520 179 46 93 149 101 113 603 126 Dimension Model M N O P Q R S 50C 164 15 34 23 362 73 75 60 71C 164 15 34 23 362 73 75 Dimension Model A B C D E F G H I J K 50 60...

Страница 3: ...in mm I J J D M B G O Dimension Model A B C D E F G H I J K L M N O 90 100 125D 1030 826 400 410 57 72 90 40 746 142 60 26 448 22 28 N N K A L E F H C 1 IM 5CKE 0912 0 DAIKIN EN indd 2 1 IM 5CKE 0912...

Страница 4: ...e Do not overcharge the unit This unit is factory pre charged Overcharge will cause over current or damage to the compressor Ensure that the unit s panel is closed after service or installation Unsecu...

Страница 5: ...e g onto the inside of the service cover 1 factory refrigerant charge of the product see unit name plate 2 2 additional refrigerant amount charged in the field 3 total refrigerant charge 4 contains fl...

Страница 6: ...or when moving it after opening Do not move the unit from packaging while moving until it reaches the installation site Use safe material or protection plates when unpacking it or lifting it to avoid...

Страница 7: ...on the ceiling and fix the hanging rod The installation template is extended according to temperature and humidity Check on dimensions in use The dimensions of the installation template are the same...

Страница 8: ...connector on the indoor unit Drain Test NOTE This Indoor Unit uses a drain pump for condensed water drainage Install the unit horizontally to prevent water leakage or condensation around the air outl...

Страница 9: ...d off before servicing the unit Use screwdriver to unlock the screw on the cover lock grille Remove the cover lock grille and open the intake grille for the service purpose Install the intake grille a...

Страница 10: ...ve wire cover by removing 2 screws as shown in Figure C Wires will go through the hole as shown in Figure D and E respectively without crossing the height of the hole After that wire cover will be ass...

Страница 11: ...Ensure that there is no obstruction of air flow into or out of the unit Remove obstacles which block air intake or discharge The location must be well ventilated so that the unit can draw in and distr...

Страница 12: ...ir Inlet Air Discharge A B Obstacle Obstacle MADE IN MALAYSIA Service Space Obstacle C D Obstacle BASE A DRAIN ELBOW PLUG DRAIN ELBOW Model Indoor FCRN FCQN 50E 60E 71E 100E 100E 125E Outdoor RN RR RY...

Страница 13: ...th the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool Refer Figure III Fix the pipe...

Страница 14: ...Block Power Supply Cable ELECTRICAL WIRING CONNECTION IMPORTANT These values are for information only They should be checked and selected to comply with local and or national codes and regulations Th...

Страница 15: ...2 5 4 Recommended time delay fuse A 25 30 Model Indoor FCRN 100E 125E Outdoor RR 100D 125D Voltage range Indoor FCRN 220 240V 1Ph 50Hz Outdoor RR 380 415V 3N 50Hz Power supply cable size mm2 Number o...

Страница 16: ...of conductors 2 5 5 2 5 5 2 5 5 Recommended time delay fuse A 13 18 25 FCQN 100E RQ 90 100D 1 PH There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm...

Страница 17: ...or Unit Terminal Block Power Supply Cable Outdoor Coil Sensor FCQN 100 125E RQ 100 125D 3 PH Model Indoor FCQN 100E 125E Outdoor RQ 100D 125D Voltage range Indoor FCQN 220 240V 1Ph 50Hz Outdoor RQ 380...

Страница 18: ...ozone layer The working pressure of this new refrigerant is 1 6 times higher than conventional refrigerant R22 thus proper installation servicing is essential Never use refrigerant other than R410Ain...

Страница 19: ...i clockwise direction with 4mm key for hexagon sacked screw Charge Operation This operation must be done by using a gas cylinder and a precise weighing machine The additional charge is topped up into...

Страница 20: ...irst few hours or the damage done during field charging may show up some time later Other typical field charging problems include undercharging overcharging moisture or air in the system etc In time e...

Страница 21: ...d Manifold valve A are both open A There are many ways of charging liquid in a controlled manner into the suction side Use valve A on the manifold gauge set Use the valve on the refrigerant cylinder C...

Страница 22: ...ct Keep the introduction of fresh air intake within 20 of total air flow Also provide a chamber and use a booster fan Sealing Material It is possible to seal one of the four air discharge outlet seali...

Страница 23: ...or Code 1 Room Sensor Open or Short Blink 1 time Blink Fan Blink E1 2 Indoor Coil Sensor Open Blink 2 times Blink Sleep Blink E2 3 Outdoor Coil Sensor Open Blink 3 times Blink Dry Blink E3 4 Compresso...

Страница 24: ...he unit with Scroll Compressor can only rotate in one direction For this reason a protective device phase protector is fitted to prevent incorrect wiring of the electrical phases When the three phases...

Страница 25: ...o the unit Check the following fault conditions and causes for some simple troubleshooting tips Fault Causes Action The compressor does not start operate after 3 minutes from starting the air conditio...

Страница 26: ...nen Ger te bleiben dem Hersteller jederzeit vorbehalten Nel caso ci fossero conflitti nell interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue la versione in lingua inglese...

Отзывы: