English
4
3. Optional accessories
•
For this indoor unit, the optional remote controller is necessary. In case of downward air inlet, the dec-
oration panel and the canvas for decoration panel are necessary.
(Refer to “4. PREPARATIONS BEFORE INSTALLATION”)
•
Remote controller
NOTE
•
If the customer wishes to use a remote controller that is not listed on the table, select a suitable remote
controller after consulting catalogs and technical materials.
•
Use the decoration panel which apply to the below table.
∗
When using the canvas duct for the decoration panel, the decoration panel needs at least 42.5 cm
of ceiling space.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
b. Items to be checked at time of delivery
∗
Also review the “1. SAFETY CONSIDERATIONS”
Remote controller
BRC1C61
Model
Min. height above ceiling
Decoration panel
Canvas duct for
decoration panel
Color
White
FBQ60BV1
FBQ71BV1
FBQ60BVL
FBQ71BVL
∗
BYBS71DJW1
KSAJ25K80
35 cm or more
Installation not required
∗
Items to be checked
If not properly done, what is likely to occur
Check
Are the indoor unit and outdoor unit fixed
firmly?
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond
to that shown on the name plate?
The unit may malfunction or the compo-
nents burn out.
Are wiring and piping correct?
The unit may malfunction or the compo-
nents burn out.
Is the unit safely grounded?
It may result in electric shock.
Is wiring size according to specifications?
The unit may malfunction or the compo-
nents burn out.
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional
refrigerant charge noted down?
The refrigerant charge in the system is not
clear.
Items to be checked
Check
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
01_EN_3P156215-4C.fm Page 4 Saturday, May 14, 2005 9:17 AM