background image

9

English

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below

After the work is finished, make sure to check that there is no gas leak.

When you keep on tightening the flare nut with a spanner, there is a point where the
tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown
below:

Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas 
leakage by thoroughly studying the following figure and using the attached heat insulating materials for 
fitting (4) and (5). (Fasten both ends with the clamps (9).) 

(Refer to Fig. 8)

Wrap the sealing pad (7) only around the insulation for the joints on the gas piping side. 

(Refer to Fig. 8)

CAUTION

For local insulation, be sure to insulate local piping all the way into the pipe connections inside the machine.

Exposed piping may cause condensation or burns on contact.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING

“Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal 

(BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.”

(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based 

flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrig-

erant oil.)

Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the 
piping.
If you brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, 
and could cause system malfunction.

When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or 
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared 
or a flanged connection.

Pipe size

Further tightening angle

Recommended arm length of tool

φ

 6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ

 9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ

 12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ

 15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

(9) Clamp (attached) (×4)

Gas pipe

Liquid pipe

(5)Insulation for fitting (attached) 
   (for liquid line)

(4) Insulation for fitting (attached)
     (for gas line)

Attach to the bottom
(For both gas piping 
 and liquid piping)

(7) Middle sealing pad (attached)
     (Wrap from the bottom up)

Fig. 8

01_EN_3P156215-4C.fm  Page 9  Saturday, May 14, 2005  9:17 AM

Содержание FBQ60BV1

Страница 1: ...FBQ60BV1 FBQ60BVL FBQ71BV1 FBQ71BVL SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE 00_C...

Страница 2: ...caution may result in injury or damage to the equipment WARNING Ask your dealer or qualified personnel to carry out installation work Do not try to install the air conditioner yourself Improper instal...

Страница 3: ...aves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireless kit transmitting distance can result shorter than expected in rooms with elec tronic fluoresce...

Страница 4: ...de Where volatile flammable gas like thinner or gasoline is used Where machines can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as tha...

Страница 5: ...35 cm or more Installation not required Items to be checked If not properly done what is likely to occur Check Are the indoor unit and outdoor unit fixed firmly The unit may drop vibrate or make noise...

Страница 6: ...e gas leakage Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual for the outdoor unit CAUTION Keep indoor unit outdoor unit power sup...

Страница 7: ...ure by changing the initial setting from the remote controller Refer to the section entitled 10 FIELD SETTING Indoor unit Suspension bolt 4 1000 Indoor unit 1050 Suspension bolt pitch Pipe 630 145 Sus...

Страница 8: ...Fig 3 2 Check the unit is horizontally level Refer to Fig 4 CAUTION The indoor unit is equipped with a built in drain pump and float switch Verify that it is level by using a level or a water filled...

Страница 9: ...either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while wor...

Страница 10: ...copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine base...

Страница 11: ...rain pipe from sagging space hanging wires every 1 to 1 5 m CAUTION Water pooling in the drainage piping can cause the drain to clog Use the attached drain hose 3 and Metal clamp 1 Insert the drain ho...

Страница 12: ...n the water inlet lid add approximately 1000 cc of water gradually and check drainage flow Refer to Fig 16 NOTE Use the drain outlet for maintenance to drain water from the drain pan WHEN ELECTRIC WIR...

Страница 13: ...performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit and...

Страница 14: ...g the units Doing so may cause malfunction Remote controller cord Control box Control box lid WIRING DIAGRAM Fig 18 CAUTION After wiring adhere the attached small sealing pad 13 around the wires as sh...

Страница 15: ...Observe the notes when wiring to the terminal block for wiring the units Use a round crimp style terminal with insulation sleeve for connection to the terminal block for wiring the units In case it ca...

Страница 16: ...be used connect a shielded portion with the grounding terminal for remote controller inside the control box Also connect the ground for the remote control to a grounded metal part 3 For group control...

Страница 17: ...able 4 4 When implementing group control When using as a pair unit or as a parent unit for simultaneous operation multi you may simultaneous start stop group control up to 16 unit with the remote cont...

Страница 18: ...y and decoration panel 12 TEST OPERATION Refer to the section of FOR THE FOLLOWING ITEMS TAKE SPECIAL CARE DURING CON STRUCTION AND CHECK AFTER INSTALLATION IS FINISHED After finishing the constructio...

Страница 19: ...recognized NOTE 2 NOTE 1 In case wired remote controller Press the INSPECTION TEST OPERATION button on remote con troller starts flashing and changes the inspection mode 2 Keep down the ON OFF button...

Страница 20: ...function outdoor unit H9 Outdoor air thermistor faulty outdoor unit J3 Discharge pipe thermistor faulty outdoor unit J5 Suction pipe thermistor faulty outdoor unit J6 Heat exchanger thermistor faulty...

Страница 21: ...the fan mounted on the outdoor unit may start operation independent of the remote controller operation U5 Transmission error indoor unit remote controller Transmission is improper between the indoor...

Страница 22: ...DAPTOR FOR SKY AIR SERIES CONTROL BOX TO BP UNIT INDOOR UNIT WIRED REMOTE CONTROLLER OPTIONAL PARTS NOTE 7 NOTE 7 CONNECTER DISCRIMINATION COLOUR FOR COMPONENTS CONNECTER COLOUR FOR COMPONENTS CONNECT...

Страница 23: ...0506 HT 3P156215 4C EM04A076B 00_CV_3P156215 4C fm Page 2 Saturday May 14 2005 10 52 AM...

Отзывы: