Daikin EWYD-4Z B Скачать руководство пользователя страница 16

D

–EIMHP01201-18_04EN - 16/24 

 
NOTE: Daikin cannot be considered responsible in case of malfunctions generated by hot air recirculation or insufficient 
airflow as result of improper installation if the above recommendations are ignored. 
 

3.5 

  Noise and sound protection 

The unit is a source of noise mainly due to rotation of compressors and fans. 
The noise level for each model size is listed in sales documentation. 
If the unit is correctly installed, operated and maintained the noise emission level do not require any special protection 
device to operate continuously close to the unit without any risk. 
In  cases  where  the  installation  is  subject  to  compliance  with  special  sound  requirements,  it  may  be  necessary  to  use 
additional noise attenuation devices, it is necessary to isolate the unit from its base with extreme care, correctly applying 
the anti-vibration elements (supplied as optional). Flexible joints must be installed on the water connections, as well. 

 
3.6 

Water piping 

Piping must be designed with the lowest number of elbows and the lowest number of vertical changes of direction. In this 
way, installation costs are reduced considerably and system performance is improved. 
The water system must have: 
1.  Anti-vibration mountings in order to reduce transmission of vibrations to the structures. 
2.  Isolating valves to isolate the unit from the water system during maintenance. 
3.  Flow switch, in order to protect the unit must be protected against freezing by continuous monitoring of the water flow 

in the evaporator. In most cases, on-site the flow switch is set to produce an alarm only when the water pump switches 
OFF and the water flow fall to zero. it is recommended to adjust the flow switch in order to produce a “Water Loss 
Alarm” when the water flow reaches 50% of the nominal value, in this case the evaporator is protected against the 
freezing and the flow switch can detect  the water filter clogging.   

4.  Manual or automatic air venting devic

e at the system’s highest point; drain device at the system’s lowest point.  

5. 

Neither the evaporator nor the heat recovery device must be positioned at the system’s highest point. 

6.  A suitable device that can maintain the water system under pressure (expansion tank, etc.). 
7.  Water temperature and pressure indicators to assist the operator during service and maintenance. 
8.  A filter or device that can remove particles from the fluid. The use of a filter extends the life of the evaporator and pump 

and helps to keep the water system in a better condition. 

The water filter must be installed as close as possible to 

the unit

, as in Fig. 7. If the water filter is installed in another part of the water system, the Installer has to guarantee the 

cleaning of the water pipes between the water filter and the evaporator.  

9.  Recommended maximum opening for strainer mesh is: 

 

0,87 mm (DX S&T) 

 

1,0 mm (BPHE) 

 

1,2 mm (Flooded) 

10. Evaporator  and  condenser  have  an  electrical  resistance  with  a  thermostat  that  ensures  protection  against  water 

freezing at ambient temperatures as low as 

–16°C.  

11. All the other water piping/devices outside the unit must therefore be protected against freezing. 
12. The  heat  recovery  device  must  be  emptied of  water  during  the  winter  season,  unless  an  ethylene glycol  mixture  in 

appropriate percentage is added to the water circuit. 

13. If  case  of  unit  substitution,  the  entire  water  system  must  be  emptied  and  cleaned  before  the  new  unit  is  installed. 

Regular tests and proper chemical treatment of water are recommended before starting up the new unit. 

14. In the event that glycol is added to the water system as anti-freeze protection, pay attention to the fact that suction 

pressure will be lower, the unit

’s performance will be lower and water pressure drops will be greater. All unit-protection 

systems, such as anti-freeze, and low-pressure protection will need to be readjusted. 

15. Before insulating water piping, check that there are no leaks. 
 

3.7 

Water treatment 

Before putting the unit into operation, clean the water circuit. 
The  evaporator  and  the  condenser  must  not  be  exposed  to  flushing  velocities  or  debris  released  during  flushing.  It  is 
recommended that a suitably sized bypass and valve arrangement is installed to allow flushing of the piping system. The 
bypass can be used during maintenance to isolate the heat exchanger without disrupting flow to other units. 

Any damage due to the presence of foreign bodies or debris in the shell&tube heat exchangers will not be covered 
by warranty

. Dirt, scales, corrosion debrits and other material can accumulate inside the heat exchanger and reduce its 

heat exchanging capacity. Pressure drop can increase as well, thus reducing water flow. Proper water treatment therefore 
reduces  the  risk  of  corrosion, erosion,  scaling,  etc..  The  most  appropriate  water  treatment  must  be  determined  locally, 
according to the type of system and water characteristics. 
The manufacturer is not responsible for damage to or malfunctioning of equipment caused by failure to treat water or by 
improperly treated water. 
 

Table 1 - Acceptable water quality limits 

pH (25°C) 

6,8

8,0 

  Total Hardness (mg CaCO

3

 / l) 

 200 

Electrical conductivity 

S/cm (25°C) 

800 

  Iron (mg Fe / l) 

 1.0 

Chloride ion (mg Cl 

/ l) 

200 

  Sulphide ion (mg S

2 - 

/ l) 

None 

Sulphate ion (mg SO

2

4

 - 

/ l) 

200 

  Ammonium ion (mg NH

4

+

 / l) 

 1.0 

Alkalinity (mg CaCO

/ l) 

100 

  Silica (mg SiO

2

 / l) 

 50 

 

Содержание EWYD-4Z B

Страница 1: ...ns REV 04 Date December 2019 Supersedes D EIMHP01201 18_03EN Multipurpose unit with Inverter Driven Single Screw Compressor EWYD 4ZB Refrigerant R 134a Installation Operation and Maintenance Manual D...

Страница 2: ...connections 18 3 10 1 Cable requirements 18 3 10 2 Interconnection cables 18 3 10 3 Phase unbalance 19 4 OPERATION 19 Operator s responsibilities 19 5 MAINTENANCE 19 5 1 Routine maintenance 19 5 2 Uni...

Страница 3: ...D EIMHP01201 18_04EN 3 24 Fig 1 Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Страница 4: ...HEAT EXCHANGER COLD WATER 9 SHELL TUBE HEAT EXCHANGER HOT WATER 10 PRESSURE RELIEF VALVE Psat 24 5 bar CHANGEOVER DEVICE OPTIONAL 11 PRESSURE RELIEF VALVE Psat 15 5 bar CHANGEOVER DEVICE OPTIONAL 12...

Страница 5: ...e electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7 Un...

Страница 6: ...cuits close the section of the piping concerned and drain the fluid gradually to stabilise the pressure at the atmospheric level 12 do not use your hands to check possible refrigerant leaks 13 disable...

Страница 7: ...our pressure from evaporation pressure to condensation pressure Evaporator where the low pressure liquid refrigerant evaporates to cool the water Condenser where the high pressure vapour refrigerant c...

Страница 8: ...ntact factory for further details For operation with temperature at the outlet of the cold heat exchanger below 4 C the unit must operate with glycol mixture ethylene or propylene glycol The glycol pe...

Страница 9: ...be able to operate outside the above envelope with compressors unloading Please contact factory for further details For operation with temperature at the outlet of the cold heat exchanger below 4 C th...

Страница 10: ...ts around the unit 1 1 Noise The unit is a source of noise mainly due to rotation of compressors and fans The noise level for each model size is listed in sales documentation If the unit is correctly...

Страница 11: ...ith 4 lifting points The drawing shows only the 6 fans version For the 4 fans version the lifting mode is the same Unit with 6 lifting points The drawing shows only the 12 fans version The lifting mod...

Страница 12: ...D EIMHP01201 18_04EN 12 24 Unit with 8 lifting points...

Страница 13: ...he condenser Limited installation space could reduce the normal air flow thus significantly reducing the machine s performance and considerably increasing consumption of electrical energy When decidin...

Страница 14: ...mmended For further solutions please consult Daikin technicians The minimum distances reported above ensure functionality of the unit in most applications However there are specific situations which i...

Страница 15: ...is working quite normally Fig 6 Multiple Chiller Installation In order to avoid the hot air recirculation due to dominant winds the installation where all units are aligned to the dominant wind is pre...

Страница 16: ...as possible to the unit as in Fig 7 If the water filter is installed in another part of the water system the Installer has to guarantee the cleaning of the water pipes between the water filter and th...

Страница 17: ...when the evaporator and or condenser water flow is lower than 50 of nominal flow rate For a proper unit operation the water flow rate of both heat exchangers evaporator and condenser must always recir...

Страница 18: ...er harmonics such as an inverter or phase cut ground losses can increase to much higher values about 2 A The protections for the power supply system must be designed according to the values mentioned...

Страница 19: ...g data for every installed unit Another record should also be kept of all the periodical maintenance and servicing activities If the operator notes abnormal or unusual operating conditions he is advis...

Страница 20: ...nt leakage X Verify refrigerant flow using the liquid sight glass Sight glass full X Verify filter dryer pressure drop X Verify oil filter pressure drop Note 5 X Analyse compressor vibrations X Analys...

Страница 21: ...it is necessary to wash periodically the frame surfaces with water and suitable detergents In case of part of unit frame paint came off it is important to stop its progressive deterioration by repain...

Страница 22: ...nd its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warranty limits 1 The unit...

Страница 23: ...label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the total refrigerant charge 1 2 3 calculate the greenhouse gas emis...

Страница 24: ...nt and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicit...

Отзывы: