Daikin EWYD-4Z B Скачать руководство пользователя страница 13

D

–EIMHP01201-18_04EN - 13/24 

 

Fig. 4 - Unit Levelling 

 

 
For installation on the ground, a strong concrete base, at least 250 mm thickness and wider than the unit must be provided. 
This base must be able to support the weight of the unit. 
 
The  unit  must be installed above  antivibrating mounts  (AVM),  rubber  or spring types.  The  unit  frame  must  be perfectly 
levelled above the AVM.  
Installation such as in the figure above must always be avoided. In case the AV

M’s are not adjustable the flatness of the 

unit frame must be guaranteed by using metal plate spacers. 
Before unit  commissioning,  the  flatness  must be  verified  by  using a  laser  levelling  device  or  other similar  devices.  The 
flatness shall not be over 5 mm for units within 7 m length and 10 mm for units over 7 m. 
If the unit is installed in places that are easily accessible to people and animals, it is advisable to install protection grids for 
the condenser and compressor sections. 
To ensure best performance on the installation site, the following precautions and instructions must be followed: 

  Avoid air flow recirculation. 

  Make sure that there are no obstacles to hamper air flow. 

  Make sure to provide a strong and solid foundation to reduce noise and vibrations. 

  Avoid installation in particularly dusty environments, in order to reduce soiling of condensers coils. 

  The water in the system must be particularly clean and all traces of oil and rust must be removed. A mechanical water 

filter must be installed on the unit

’s inlet piping. 

 

3.4 

Minimum space requirements 

It is fundamental to respect minimum distances on all units in order to ensure optimum ventilation to the condenser. Limited 
installation space could reduce the normal air flow, thus significantly reducing the machine’s performance and considerably 
increasing consumption of electrical energy. 

When deciding where to position the machine and to ensure a proper air flow, the following factors must be taken into 
consideration: avoid any warm air recirculation and insufficient air supply to the air-cooled condenser. 

Both these conditions can cause an increase of condensing pressure, which leads to a reduction in energy efficiency and 
refrigerating  capacity.  Thanks  to  the  geometry  of  their  air-cooled  condensers,  the  units  are  less  affected  by  poor  air 
circulation conditions. 

Also, the 

software has particularly the ability to compute the machine’s operating conditions to optimise the load under 

abnormal operating circumstances. 

Every side of the machine must be accessible for post-installation maintenance operations. Figure 4 shows the minimum 
space required. 

Vertical air discharge must not be obstructed as this would significantly reduce capacity and efficiency. 

If the machine is surrounded by walls or obstacles of the same height as the machine, it must be installed at a distance of 
at least 2500 mm. If these obstacles are higher, the machine must be installed at a distance of at least 3000 mm. 

Should  the  machine  be  installed  without  observing  the  recommended  minimum  distances  from  walls  and/or  vertical 
obstacles, there could be a combination of warm air recirculation and/or insufficient supply to the air-cooled condenser 
which could cause a reduction of capacity and efficiency. 

In any case, the microprocessor will allow the machine to adapt itself to new operating conditions and deliver the maximum 
capacity available under any given circumstances, even if the lateral distance is lower than recommended. 

Содержание EWYD-4Z B

Страница 1: ...ns REV 04 Date December 2019 Supersedes D EIMHP01201 18_03EN Multipurpose unit with Inverter Driven Single Screw Compressor EWYD 4ZB Refrigerant R 134a Installation Operation and Maintenance Manual D...

Страница 2: ...connections 18 3 10 1 Cable requirements 18 3 10 2 Interconnection cables 18 3 10 3 Phase unbalance 19 4 OPERATION 19 Operator s responsibilities 19 5 MAINTENANCE 19 5 1 Routine maintenance 19 5 2 Uni...

Страница 3: ...D EIMHP01201 18_04EN 3 24 Fig 1 Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Страница 4: ...HEAT EXCHANGER COLD WATER 9 SHELL TUBE HEAT EXCHANGER HOT WATER 10 PRESSURE RELIEF VALVE Psat 24 5 bar CHANGEOVER DEVICE OPTIONAL 11 PRESSURE RELIEF VALVE Psat 15 5 bar CHANGEOVER DEVICE OPTIONAL 12...

Страница 5: ...e electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7 Un...

Страница 6: ...cuits close the section of the piping concerned and drain the fluid gradually to stabilise the pressure at the atmospheric level 12 do not use your hands to check possible refrigerant leaks 13 disable...

Страница 7: ...our pressure from evaporation pressure to condensation pressure Evaporator where the low pressure liquid refrigerant evaporates to cool the water Condenser where the high pressure vapour refrigerant c...

Страница 8: ...ntact factory for further details For operation with temperature at the outlet of the cold heat exchanger below 4 C the unit must operate with glycol mixture ethylene or propylene glycol The glycol pe...

Страница 9: ...be able to operate outside the above envelope with compressors unloading Please contact factory for further details For operation with temperature at the outlet of the cold heat exchanger below 4 C th...

Страница 10: ...ts around the unit 1 1 Noise The unit is a source of noise mainly due to rotation of compressors and fans The noise level for each model size is listed in sales documentation If the unit is correctly...

Страница 11: ...ith 4 lifting points The drawing shows only the 6 fans version For the 4 fans version the lifting mode is the same Unit with 6 lifting points The drawing shows only the 12 fans version The lifting mod...

Страница 12: ...D EIMHP01201 18_04EN 12 24 Unit with 8 lifting points...

Страница 13: ...he condenser Limited installation space could reduce the normal air flow thus significantly reducing the machine s performance and considerably increasing consumption of electrical energy When decidin...

Страница 14: ...mmended For further solutions please consult Daikin technicians The minimum distances reported above ensure functionality of the unit in most applications However there are specific situations which i...

Страница 15: ...is working quite normally Fig 6 Multiple Chiller Installation In order to avoid the hot air recirculation due to dominant winds the installation where all units are aligned to the dominant wind is pre...

Страница 16: ...as possible to the unit as in Fig 7 If the water filter is installed in another part of the water system the Installer has to guarantee the cleaning of the water pipes between the water filter and th...

Страница 17: ...when the evaporator and or condenser water flow is lower than 50 of nominal flow rate For a proper unit operation the water flow rate of both heat exchangers evaporator and condenser must always recir...

Страница 18: ...er harmonics such as an inverter or phase cut ground losses can increase to much higher values about 2 A The protections for the power supply system must be designed according to the values mentioned...

Страница 19: ...g data for every installed unit Another record should also be kept of all the periodical maintenance and servicing activities If the operator notes abnormal or unusual operating conditions he is advis...

Страница 20: ...nt leakage X Verify refrigerant flow using the liquid sight glass Sight glass full X Verify filter dryer pressure drop X Verify oil filter pressure drop Note 5 X Analyse compressor vibrations X Analys...

Страница 21: ...it is necessary to wash periodically the frame surfaces with water and suitable detergents In case of part of unit frame paint came off it is important to stop its progressive deterioration by repain...

Страница 22: ...nd its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warranty limits 1 The unit...

Страница 23: ...label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the total refrigerant charge 1 2 3 calculate the greenhouse gas emis...

Страница 24: ...nt and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicit...

Отзывы: