Refrigerant charge 

 

 ATTENTION

 

 

The units have been designed to operate with R134a refrigerant. DO NOT USE refrigerants other than R134a. 

 

                                                                          

    

WARNING

 

 

The addition or removal of refrigerant gas must be carried out in compliance with the laws and regulations in force. 

 

 ATTENTION

 

 

When refrigerant gas is added to or removed from the system, ensure proper water flow through the evaporator for 
the  entire  charge/discharge  time.  Interrupting  the  water  flow  during  this  procedure  would  cause  the  evaporator  to 
freeze with consequent breakage of its internal piping. 
Damage caused by freezing makes the warranty void. 
 

 

 

WARNING

 

 
Removal of the refrigerant and replenishing operations must be performed by technicians who are qualified to use the 
appropriate materials for this unit. Unsuitable maintenance can result in uncontrolled losses in pressure and fluid. Do 
not  disperse  the  refrigerant  and  lubricating  oil  in  the  environment.  Always  be  equipped  with  a  suitable  recovery 
system. 

 
The units ship with a full refrigerant charge, but in some cases it might be necessary to replenish the machine in the field. 
 

 

ATTENTION

 

Always verify the causes of a loss of refrigerant. Repair the system if necessary then recharge it. 

 
The  machine  can  be  replenished  under  any  stable  load  condition  (preferably  between  70  and  100%)  and  under  any 
ambient  temperature  condition  (preferably  above  20°C).  The  machine  should  be  kept  running  for  at  least  5  minutes  to 
allow the condensation pressure to stabilise. 
The subcooling value is about 3-4°C. 
Once  the  subcooling  section  has  been  completely  filled,  additional  refrigerant  will  not  increase  system  efficiency. 
However, a small additional quantity of refrigerant (1

2 kg) makes the system slightly less sensitive. 

 

N.B.

:  Subcooling  varies  and  requires  a  few  minutes  to  re-stabilise.  However,  subcooling  should  not  come  below  2°C 

under  any  condition.  Also,  the  subcooling  value  can  change  slightly  as  the  water  temperature  and  the  suction 
superheating vary. As the suction superheating value decreases, there is a corresponding decrease in subcooling.  
 
One of the two following scenarios can arise in a machine without refrigerant: 

1. 

If the refrigerant level is slightly low, flow of bubbles can be seen through the liquid sight glass.  Replenish 
the circuit as described in the replenishment procedure. 

2. 

If the gas level in the machine is moderately low, the corresponding circuit could have some low-pressure 
stops. Replenish the corresponding circuit as described in the replenishment procedure. 

 

Refrigerant filling procedure 

1) 

If  the  machine  has  lost  refrigerant,  it  is  necessary  to  first  establish  the  causes  before  carrying  out  any 
replenishment operation. The leak must be found and repaired. Oil stains are a good indicator, as they can 
appear in the vicinity of a leak. However, this is not necessarily always a good search criterion. Searching 
with soap and water can be a good method for medium to large leaks, while an electronic leak detector is 
required to find small leaks. 

2) 

Add refrigerant to the system through the service valve on the suction pipe or through the Schrader valve 
located on the evaporator inlet pipe. 

3) 

The  refrigerant  can  be  added  under  any  load  condition  between  25  and  100%  of  the  system  capacity. 
Suction superheating must be beteen 4 and 6°C. 

4) 

Add enough refrigerant to fill the liquid sight glass entirely, so that no flow of bubbles can be seen anymore. 
Add an extra 2 

 3 kg of refrigerant as a reserve, to fill the subcooler if the compressor is operating at 50 

– 

100% load. 

5) 

Check the subcooling value by reading the liquid pressure and the liquid temperature near the expansion 
valve. The subcooling value must be between 3 and 5°C. The subcooling value will be lower at 75 

 100% 

load and higher at 50% load. 

6) 

Overcharging the system will cause a rise in the compressor’s discharge pressure. 

All manuals and user guides at all-guides.com

Содержание EWWD 340 C18 I-SS Series

Страница 1: ...chillers EWWD 340 C18 I SS EWWD 360 C12 I XS EWLD 320 C17 I SS 50Hz Refrigerant R 134a Original Instructions Installation Operation and Maintenance Manual D EIMWC00408 16EN All manuals and user guides...

Страница 2: ...ctrical wiring Optional 17 Guidelines for remote condenser application 18 Refrigerant piping design 18 Determining Equivalent Line Length 19 Liquid Line Sizing 20 Discharge Hot Gas Line Sizing 20 Oil...

Страница 3: ...ser Located above Chiller Unit 19 Fig 9 Condenser Located below Chiller Unit 19 Fig 10 Refrigeration cycle of the EWWD I SS Single Circuit 24 Fig 11 Refrigeration cycle of the EWLD I SS Single Circuit...

Страница 4: ...WARNING Before starting the installation of the unit please read this manual carefully Starting up the unit is absolutely forbidden if all instructions contained in this manual are not clear Key to sy...

Страница 5: ...ng warning 9 Electrical hazard symbol 5 Water circuit filling warning 10 Emergency stop Three Compressors Unit 1 Unit nameplate data 6 Hazardous Voltage warning 2 Lifting instructions 7 Manufacturer s...

Страница 6: ...symbols Important note failure to respect the instruction can damage the unit or compromise functioning Note regarding safety in general or respect of laws and regulations Note concerning electrical...

Страница 7: ...s manual The purpose of this manual is to allow the installer and the qualified operator to carry out all required operations in order to ensure proper installation and maintenance of the machine with...

Страница 8: ...n ATTENTION Storage in a condensed atmosphere can damage the electronic components Storage at ambient temperature near or below 0 C with water loops filled with water require to protect against water...

Страница 9: ...exchanger inlet The machine is supplied with safety valves that are installed on both the high and the low pressure sides of the refrigerant circuit In case of sudden stop of the unit follow the instr...

Страница 10: ...sembly All units are designed for installation indoors The machine must be installed on a robust and perfectly level foundation should the machine be installed on balconies or roofs it might be necess...

Страница 11: ...tem s highest point 4 A suitable device that can maintain the water system under pressure expansion tank etc 5 Water temperature and pressure indicators on the machine to assist the operator during se...

Страница 12: ...D EIMWC00408 16EN 12 60 Fig 3 Minimum clearance requirements for machine maintenance Fig 4 Water piping connection for condenser and heat recovery All manuals and user guides at all guides com...

Страница 13: ...e considered when designing the system as a whole 1 Continuous water flow circulation inside piping and exchangers 2 Addition of an appropriate amount of glycol inside the water circuit 3 Additional h...

Страница 14: ...g the safety valves to the drainage pipes and for their correct dimensioning Check for adequate air circulation around the machine General specifications CAUTION All electrical connections to the mach...

Страница 15: ...disconnector switch is in the closed position unused circuits are live as well CAUTION Concurrence of single phase and three phase charges and unbalance between phases can cause leakages towards grou...

Страница 16: ...oil The terminals are connected to a clean microprocessor contact The microprocessor contact has the following commutation capacity Maximum voltage 250 Vac Maximum current 2 A Resistive 2 A Inductive...

Страница 17: ...pe and must not be laid in the vicinity of the power cables so as not to induce interference with the electronic controller A digital input allows to enable the current limitation at the desired time...

Страница 18: ...ith refrigerant This prevents scale formation and the possible formation of an explosive mixture of HFC 134a and air This will also prevent the formation of toxic phosgene gas which occurs when HFC 13...

Страница 19: ...riction loss from the linear run of pipe plus the added friction loss of elbows valves etc Table 2 shows the equivalent length of pipe for various nonferrous valves and fittings Follow these steps whe...

Страница 20: ...he chiller unit and the air cooled condenser must not exceed 60 equivalent meters Liquid line risers in the system will require an additional 11 5 kPa pressure drop per meter of vertical rise When it...

Страница 21: ...led on the discharge line Reference for discharge line sizing is shown in Table 9 It has to be used for reference only for circuit working with evaporator leaving temperature equal to 7 C and condensi...

Страница 22: ...ompressed and during this process the refrigerant mixes with the oil from the oil separator The high pressure oil refrigerant mixture is introduced into the centrifuge type high efficiency oil separat...

Страница 23: ...evaporation followed by superheating Once it has reached the superheated vapour state the refrigerant leaves the evaporator and is once again taken into the compressor to repeat the cycle Controlling...

Страница 24: ...RE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD...

Страница 25: ...GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE...

Страница 26: ...ITH GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1...

Страница 27: ...2 WAY ANGLE VALVE WITH GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WA...

Страница 28: ...T LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TE...

Страница 29: ...P F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJ...

Страница 30: ...PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION...

Страница 31: ...GH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTIO...

Страница 32: ...WITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST...

Страница 33: ...P F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJ...

Страница 34: ...IGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJECTION SOL VALVE Y5 OIL PRESSURE TRANDUCER W...

Страница 35: ...IGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJECTION SOL VALVE Y5 OIL PRESSURE TRANDUCER W...

Страница 36: ...TCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE L...

Страница 37: ...SSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE...

Страница 38: ...s done thanks to a suitably shaped special composite material that is interposed between the main screw and the satellite The main shaft on which the main rotor is splined is supported by 2 ball beari...

Страница 39: ...ume is closed off from the suction chamber the suction stage of the compression cycle is complete 1 2 3 Compression As the main rotor turns the volume of gas trapped within the flute is reduced as the...

Страница 40: ...D EIMWC00408 16EN 40 60 Fig 26 Refrigeration capacity control mechanism of compressor Fr4 Load Unload All manuals and user guides at all guides com...

Страница 41: ...itch terminals The power supply voltage must be the same as that on the nameplate Maximum allowed tolerance 10 Voltage unbalance between the three phases must not exceed 3 The unit comes with a factor...

Страница 42: ...is 383 386 392 387 Volts 3 thus the unbalance percentage is 29 1 100 387 387 392 x below the maximum allowed 3 Oil Heaters power supply Each compressor comes with an electrical resistance located in...

Страница 43: ...pletely fully without bubbles and that the humidity indicator shows Dry Any bubbles inside the liquid sight glass might indicate a low refrigerant level or an excessive pressure drop through the filte...

Страница 44: ...ring the winter season One must remember that once the machine s power supply has been cut off the anti freeze electrical resistance cannot function Do not leave the evaporator and piping exposed to t...

Страница 45: ...unit and on the state of the pressurised refrigeration circuits carried out after ten years of use in compliance with Italian law Lgs Decree 93 2000 for all groups belonging to categories I and IV co...

Страница 46: ...D EIMWC00408 16EN 46 60 Fig 27 Installation of control devices for Fr4 compressor All manuals and user guides at all guides com...

Страница 47: ...lters and re check after 1000 running hours Continue to replace filters until the TAN is lower than 0 10 0 19 Change oil replace oil filter and filter dryer Verify at regular intervals 7 Safety valves...

Страница 48: ...e the filter cover 12 Connect the vacuum pump to the filter and pull vacuum to 230 Pa 13 Close the vacuum pump valve 14 Recharge the filter with the refrigerant recovered during emptying 15 Open the l...

Страница 49: ...edure Procedure to replace oil filter 1 Shut down both compressors by turning the Q1 and Q2 switches to the Off position 2 Turn the Q0 switch to Off wait for the circulation pump to turn off and open...

Страница 50: ...me below 2 C under any condition Also the subcooling value can change slightly as the water temperature and the suction superheating vary As the suction superheating value decreases there is a corresp...

Страница 51: ...e microprocessor will control the compressor load in order to allow it to function even if the compressor flow gas must be reduced It also contributes to the oil control logic Oil pressure transducer...

Страница 52: ...e _____ bar Suction gas temperature _____ C Suction superheating _____ C Condensation saturated temperature _____ C Discharge superheating _____ C Liquid temperature _____ C Subcooling _____ C _____ C...

Страница 53: ...s RS ST RT _____ V _____ V _____ V Unbalance _____ 100 max x Vaverage Vaverage V Compressors current Phases R S T Compressor 1 _____ A _____ A _____ A Compressor 2 _____ A _____ A _____ A Compressor 3...

Страница 54: ...propriate manner beyond its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warra...

Страница 55: ...lease check with your local requirements Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type...

Страница 56: ...ield h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label must...

Страница 57: ...Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label mus...

Страница 58: ...f metal and plastic parts All these parts must be disposed of in accordance with the local regulations in terms of disposal Lead batteries must be collected and taken to specific refuse collection cen...

Страница 59: ...D EIMWC00408 16EN 59 60 All manuals and user guides at all guides com...

Страница 60: ...products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects...

Отзывы: