D

–EIMWC00408-16EN - 49/60 

 

 

 

ATTENTION

 

 

The  lubrication  system  has  been  designed  to  keep  most  of  the  oil  charge  inside  the  compressor.  During  operation, 
however,  a  small  amount  of  oil  circulates  freely  in  the  system,  conveyed  by  the  refrigerant.  The  amount  of 
replacement oil going into the compressor should therefore be equal to the quantity removed rather than the amount 
stated on the nameplate; this will avoid excess of oil during the following start-up. 
The quantity of oil removed from the compressor must be measured after having allowed the refrigerant present in the 
oil to evaporate for a suitable amount of time. To reduce the refrigerant content in the oil to a minimum, it is  advised 
that  the  electrical  resistances  be  kept  on  and  that  the  oil  be  removed  only  when  it  has  reached  a  temperature  of 
35

45°C. 

 

 

 

 

ATTENTION 

 

 
The replacement of the oil filter requires careful attention with regard to oil recovering; the oil must not be exposed to 
air for more than about 30 minutes. 
In case of doubts, verify oil acidity or, if it is not possible to carry out the measurement, replace the charge of lubricant 
with fresh oil stored in sealed tanks or in a way that meet supplier specifications. 
 

 

Fr4200 compressor 

The  compressor  oil  filter  is  located  at  the  coupling  of  the  oil  inlet  piping  and  the  compressor  body  (suction  side).  It  is 
strongly advised that it be replaced when its pressure drop exceeds 2.0 bar. The pressure drop across the oil filter is the 
difference between the compressor delivery pressure minus oil pressure. Both pressures can be controlled through the 
microprocessor for both compressors. 
 

Required materials: 

 

Oil filter  Code 95816-401   

– Quantity 1 

Gaskets kit  Code 128810988  

– Quantity 1 

 

Compatible oils: 
DAPHNE HERMET OIL FVC68D 
 
The standard oil charge for a compressor is18 litres. 

 

Oil filter replacement procedure 
Procedure to replace oil filter 

1) 

Shut down both compressors by turning the Q1 and Q2 switches to the Off position. 

2) 

Turn  the  Q0  switch  to  Off,  wait  for  the  circulation pump  to  turn  off and open the general disconnecting switch 
Q10 to cut off the machine’s electrical power supply. 

3) 

Place a label on the handle of the general disconnecting switch in order to prevent accidental start-up. 

4) 

Close the suction, discharge and liquid injection valves. 

5) 

Connect the recovery unit to the compressor and recover the refrigerant in a suitable and clean container. 

6) 

Evacuate  the  refrigerant  until  the  internal  pressure  has  turned  negative  (compared  to  atmospheric  pressure). 
The amount of refrigerant dissolved in the oil is reduced to a minimum in this way. 

7) 

Drain the oil in the compressor by opening the drain valve located under the oil separator. 

8) 

Remove the oil filter cover and remove the internal filter element. 

9) 

Replace  the  cover  and  internal  sleeve  gaskets.  Do  not  lubricate  the  gaskets  with  mineral  oil  in  order  not  to 
contaminate the system. 

10) 

Insert the new filter element. 

11) 

Reposition the filter cover and tighten the screws. The screws must be tightened alternately and progressively 
setting the torque wrench at 60 Nm. 

12) 

Charge the oil from the upper valve located on the oil separator. Considering the high hygroscopy of ester oil, it 
should be charged as quickly as possible. Do not expose ester oil to the atmosphere for more than 10 minutes. 

13) 

Close the oil charging valve. 

14) 

Connect the vacuum pump and evacuate the compressor up to a vacuum of 230 Pa. 

15) 

On reaching the above vacuum level, close the vacuum pump valve. 

16) 

Open the system’s delivery, suction and liquid injection valves. 

17) 

Disconnect the vacuum pump from the compressor. 

18) 

Remove the warning label from to the general disconnecting switch. 

19) 

Close the general disconnecting switch Q10 to supply power to the machine. 

20) 

Start the machine by following the start-up procedure described above. 

All manuals and user guides at all-guides.com

Содержание EWWD 340 C18 I-SS Series

Страница 1: ...chillers EWWD 340 C18 I SS EWWD 360 C12 I XS EWLD 320 C17 I SS 50Hz Refrigerant R 134a Original Instructions Installation Operation and Maintenance Manual D EIMWC00408 16EN All manuals and user guides...

Страница 2: ...ctrical wiring Optional 17 Guidelines for remote condenser application 18 Refrigerant piping design 18 Determining Equivalent Line Length 19 Liquid Line Sizing 20 Discharge Hot Gas Line Sizing 20 Oil...

Страница 3: ...ser Located above Chiller Unit 19 Fig 9 Condenser Located below Chiller Unit 19 Fig 10 Refrigeration cycle of the EWWD I SS Single Circuit 24 Fig 11 Refrigeration cycle of the EWLD I SS Single Circuit...

Страница 4: ...WARNING Before starting the installation of the unit please read this manual carefully Starting up the unit is absolutely forbidden if all instructions contained in this manual are not clear Key to sy...

Страница 5: ...ng warning 9 Electrical hazard symbol 5 Water circuit filling warning 10 Emergency stop Three Compressors Unit 1 Unit nameplate data 6 Hazardous Voltage warning 2 Lifting instructions 7 Manufacturer s...

Страница 6: ...symbols Important note failure to respect the instruction can damage the unit or compromise functioning Note regarding safety in general or respect of laws and regulations Note concerning electrical...

Страница 7: ...s manual The purpose of this manual is to allow the installer and the qualified operator to carry out all required operations in order to ensure proper installation and maintenance of the machine with...

Страница 8: ...n ATTENTION Storage in a condensed atmosphere can damage the electronic components Storage at ambient temperature near or below 0 C with water loops filled with water require to protect against water...

Страница 9: ...exchanger inlet The machine is supplied with safety valves that are installed on both the high and the low pressure sides of the refrigerant circuit In case of sudden stop of the unit follow the instr...

Страница 10: ...sembly All units are designed for installation indoors The machine must be installed on a robust and perfectly level foundation should the machine be installed on balconies or roofs it might be necess...

Страница 11: ...tem s highest point 4 A suitable device that can maintain the water system under pressure expansion tank etc 5 Water temperature and pressure indicators on the machine to assist the operator during se...

Страница 12: ...D EIMWC00408 16EN 12 60 Fig 3 Minimum clearance requirements for machine maintenance Fig 4 Water piping connection for condenser and heat recovery All manuals and user guides at all guides com...

Страница 13: ...e considered when designing the system as a whole 1 Continuous water flow circulation inside piping and exchangers 2 Addition of an appropriate amount of glycol inside the water circuit 3 Additional h...

Страница 14: ...g the safety valves to the drainage pipes and for their correct dimensioning Check for adequate air circulation around the machine General specifications CAUTION All electrical connections to the mach...

Страница 15: ...disconnector switch is in the closed position unused circuits are live as well CAUTION Concurrence of single phase and three phase charges and unbalance between phases can cause leakages towards grou...

Страница 16: ...oil The terminals are connected to a clean microprocessor contact The microprocessor contact has the following commutation capacity Maximum voltage 250 Vac Maximum current 2 A Resistive 2 A Inductive...

Страница 17: ...pe and must not be laid in the vicinity of the power cables so as not to induce interference with the electronic controller A digital input allows to enable the current limitation at the desired time...

Страница 18: ...ith refrigerant This prevents scale formation and the possible formation of an explosive mixture of HFC 134a and air This will also prevent the formation of toxic phosgene gas which occurs when HFC 13...

Страница 19: ...riction loss from the linear run of pipe plus the added friction loss of elbows valves etc Table 2 shows the equivalent length of pipe for various nonferrous valves and fittings Follow these steps whe...

Страница 20: ...he chiller unit and the air cooled condenser must not exceed 60 equivalent meters Liquid line risers in the system will require an additional 11 5 kPa pressure drop per meter of vertical rise When it...

Страница 21: ...led on the discharge line Reference for discharge line sizing is shown in Table 9 It has to be used for reference only for circuit working with evaporator leaving temperature equal to 7 C and condensi...

Страница 22: ...ompressed and during this process the refrigerant mixes with the oil from the oil separator The high pressure oil refrigerant mixture is introduced into the centrifuge type high efficiency oil separat...

Страница 23: ...evaporation followed by superheating Once it has reached the superheated vapour state the refrigerant leaves the evaporator and is once again taken into the compressor to repeat the cycle Controlling...

Страница 24: ...RE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD...

Страница 25: ...GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE...

Страница 26: ...ITH GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1...

Страница 27: ...2 WAY ANGLE VALVE WITH GAS CHARGE PORT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WA...

Страница 28: ...T LOW PRESSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TE...

Страница 29: ...P F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJ...

Страница 30: ...PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION...

Страница 31: ...GH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTIO...

Страница 32: ...WITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST...

Страница 33: ...P F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJ...

Страница 34: ...IGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJECTION SOL VALVE Y5 OIL PRESSURE TRANDUCER W...

Страница 35: ...IGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE LIQUID INJECTION SOL VALVE Y5 OIL PRESSURE TRANDUCER W...

Страница 36: ...TCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE WD1 ST1 SUCTION TEMPERATURE L...

Страница 37: ...SSURE SWITCH HIGH PRESSURE SWITCH F12 LP F13 HP LOW PRESSURE TRANSDUCER 0 5 7 bar HIGH PRESSURE TRANSDUCER 0 30 bar LEAVING WATER TEMPERATURE ENTERING WATER TEMPERATURE WH1 WOE WL1 WIE OIL TEMPERATURE...

Страница 38: ...s done thanks to a suitably shaped special composite material that is interposed between the main screw and the satellite The main shaft on which the main rotor is splined is supported by 2 ball beari...

Страница 39: ...ume is closed off from the suction chamber the suction stage of the compression cycle is complete 1 2 3 Compression As the main rotor turns the volume of gas trapped within the flute is reduced as the...

Страница 40: ...D EIMWC00408 16EN 40 60 Fig 26 Refrigeration capacity control mechanism of compressor Fr4 Load Unload All manuals and user guides at all guides com...

Страница 41: ...itch terminals The power supply voltage must be the same as that on the nameplate Maximum allowed tolerance 10 Voltage unbalance between the three phases must not exceed 3 The unit comes with a factor...

Страница 42: ...is 383 386 392 387 Volts 3 thus the unbalance percentage is 29 1 100 387 387 392 x below the maximum allowed 3 Oil Heaters power supply Each compressor comes with an electrical resistance located in...

Страница 43: ...pletely fully without bubbles and that the humidity indicator shows Dry Any bubbles inside the liquid sight glass might indicate a low refrigerant level or an excessive pressure drop through the filte...

Страница 44: ...ring the winter season One must remember that once the machine s power supply has been cut off the anti freeze electrical resistance cannot function Do not leave the evaporator and piping exposed to t...

Страница 45: ...unit and on the state of the pressurised refrigeration circuits carried out after ten years of use in compliance with Italian law Lgs Decree 93 2000 for all groups belonging to categories I and IV co...

Страница 46: ...D EIMWC00408 16EN 46 60 Fig 27 Installation of control devices for Fr4 compressor All manuals and user guides at all guides com...

Страница 47: ...lters and re check after 1000 running hours Continue to replace filters until the TAN is lower than 0 10 0 19 Change oil replace oil filter and filter dryer Verify at regular intervals 7 Safety valves...

Страница 48: ...e the filter cover 12 Connect the vacuum pump to the filter and pull vacuum to 230 Pa 13 Close the vacuum pump valve 14 Recharge the filter with the refrigerant recovered during emptying 15 Open the l...

Страница 49: ...edure Procedure to replace oil filter 1 Shut down both compressors by turning the Q1 and Q2 switches to the Off position 2 Turn the Q0 switch to Off wait for the circulation pump to turn off and open...

Страница 50: ...me below 2 C under any condition Also the subcooling value can change slightly as the water temperature and the suction superheating vary As the suction superheating value decreases there is a corresp...

Страница 51: ...e microprocessor will control the compressor load in order to allow it to function even if the compressor flow gas must be reduced It also contributes to the oil control logic Oil pressure transducer...

Страница 52: ...e _____ bar Suction gas temperature _____ C Suction superheating _____ C Condensation saturated temperature _____ C Discharge superheating _____ C Liquid temperature _____ C Subcooling _____ C _____ C...

Страница 53: ...s RS ST RT _____ V _____ V _____ V Unbalance _____ 100 max x Vaverage Vaverage V Compressors current Phases R S T Compressor 1 _____ A _____ A _____ A Compressor 2 _____ A _____ A _____ A Compressor 3...

Страница 54: ...propriate manner beyond its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warra...

Страница 55: ...lease check with your local requirements Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type...

Страница 56: ...ield h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label must...

Страница 57: ...Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label mus...

Страница 58: ...f metal and plastic parts All these parts must be disposed of in accordance with the local regulations in terms of disposal Lead batteries must be collected and taken to specific refuse collection cen...

Страница 59: ...D EIMWC00408 16EN 59 60 All manuals and user guides at all guides com...

Страница 60: ...products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects...

Отзывы: