D-EIMHP01601-22_00EN 13/25
10 CHECKING THE WATER CIRCUIT
The units are equipped with a water inlet and water outlet for connection to a chilled water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and national regulations.
WARNING
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive
corrosion of the water piping.
Before continuing the installation of the unit, check the following points:
•
Additional components not delivered with the unit:
1. A circulation pump must be provided in such a way that it discharges the water directly into the heat exchanger.
2. Drain traps must be provided at all low points of the system to permit complete drainage of the circuit during
maintenance or in case of shut down.
3. Anti-vibration systems in all water piping connected to the chiller are recommended to avoid straining the piping and
transmitting vibration and noise.
•
Additional water piping delivered with the unit
All additional water piping must be installed on the system according to the piping diagram as mentioned in the operation manual. The
flow switch must be connected as described on the wiring diagram. See also chapter "Before starting".
Figure 8- Water piping evaporator-plastic bag 1
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge
2x Flow switch pipe
1xFlow
1x T-joint
Figure 9-Water piping condenser-plastic bag (2)
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge