Figure 2 - Operating Limits: 

 

 

 

Water Temperature exiting the Evaporator (°C) 

 

– Operation with Water 

-

  

Operation with  Water Solution  

– 

Heat pump unit operating limit

 

 
 

 
Safety 

The unit must be firmly secured to the soil. 
It is essential to observe the following instructions: 

 

It is forbidden to access the electrical components 
without having opened the main switch and 
switched off the power supply. 

 

It is forbidden to access the electrical components 
without using an insulating platform. Do not access 
the electrical components if water and/or moisture 
are present. 

 

The sharp edges can cause injuries. Avoid direct 
contact and use adequate protection device 

 

Do not insert solid object in the water pipes.  

 

A mechanical filter must be installed on the water 
pipe connected to the heat exchanger inlet. 

 

The unit is supplied with high  pressure switches 
and/or safety valves, that are installed both on the 
high-pressure and on the low-pressure sides of the 
refrigerant circuit: 

be careful. 

 

It is absolutely forbidden to remove the protections 
of moving parts. 

 

In case of a sudden stop. follow the instructions listed in 
the 

Control Panel Instruction Manual 

which is part of 

the on-board documentation. 
 
It is strongly recommended  that the installation and 
maintenance operations not be performed along but 
with other people.  
In case of accidental injury or unease, it is necessary to: 

  keep calm 

  Press the alarm button, if present at the installation 

site, or open the main switch 

  move the injured person in a warm place far from 

the unit and in rest position 

  contact immediately emergency rescue personnel of 

the building or the Health Emergency Service 

  wait without leaving the injured person alone until 

the rescue operators come 

  Give all necessary information to the  rescue 

operators. 

 

Positioning and assembly 

The unit must be installed on a sturdy and perfectly 
level foundation. For the earthing, a resistant base is 
cement must be created with a width greater than that 
of the unit. This base must be able to support  its 
weight. 

Anti-vibration supports must be installed between the 
frame of the unit and the cement base of the steel 
beams; for their installation follow the dimensional 
drawing provided with the unit. 
The frame of theunit must be perfectly levelled during 
installation, if necessary using shims to be inserted 
under the anti-vibrators.  
Before the first start-up, it is mandatory that the 
installation be verified as being level and horizontal 
using a laser level or another suitable instrument.    
The error in the levelness and the horizontal position 
must not be greater than 5 mm per unit up to 7 metres 
and 10mm per unit over 7 metres. 

If the unit is installed in places that are easily accessible 
to people and animals, we recommend that  protection 
grates be assemble all around to prevent free access. 
To guarantee the best performance in the place of 
installation, the following precautions and instructions 
must be respected:

 

- Make sure to provide a strong and solid foundation to 
reduce noise and vibrations. 
- Avoid installing the unit in areas that could be 
dangerous during maintenance operations, such as 
platforms without parapets, railings or areas not 
complying with the requirements to leave a clearance 
space all the way around it. 
Respect the minimum access distances around the unit:  
- 1500 mm in front of the electric panel; 
- 1000 mm on all the other sides.  
For further solutions, please consult manufacturer 
representative. 

  

  

W

a

te

te

m

per

a

ture

 e

nt

e

ri

ng

 t

he Conde

nse

(°C)

 

Содержание EWHQ100G

Страница 1: ...n manual EWWQ090G EWWQ720L Water cooled scroll chillers EWLQ090G EWLQ720L Condenserless EWHQ100G EWHQ400G Heat pump scroll chillers Refrigerant R410A D EIMWC01206 15EN REV 00 Date Supersedes EWLQ G L Condenserless water cooled chillers ...

Страница 2: ... unit can be seasonally inverted General Information All the units are delivered together withwiring diagrams certifieddrawings nameplateandDoC DeclarationofConformity Thesedocumentslistallthe technicaldataoftheunitacquiredandCONSTITUTEAN INTEGRALANDESSENTIALPARTOFTHISMANUAL In case of any discrepancy between this manual and the equipment s documents please refer to on board documents In case of a...

Страница 3: ...it Identification of the labels 1 Manufacturer s logo 5 Hazardous voltage warning 2 Type of coolant in the circuit s 6 Non flammable gas symbol 3 Electrical hazard symbol 7 Identification data of the unit 4 Tighten electrical cables warning 8 Instructions for handling lifting With the exception of the unit s name plate which is always in the same position the other plates may be in different posit...

Страница 4: ...gency Service wait without leaving the injured person alone until the rescue operators come Give all necessary information to the rescue operators Positioning and assembly The unit must be installed on a sturdy and perfectly level foundation For the earthing a resistant base is cement must be created with a width greater than that of the unit This base must be able to support its weight Anti vibra...

Страница 5: ...the unit very slowly keeping it perfectly level Avoid bumping and or shaking the unit during the handling and loading unloading operations from the transportation vehicle push or pull the unit only using the base frame Secure the unit inside the truck to prevent it from moving and causing damages Do not allow any part of the unit to fall during loading unloading All units have lifting points marke...

Страница 6: ...ure 4 Handling of the double circuit unit Alternative handling method 1 Remove before installation 2 Use lifting hooks with closing device exclusively The hooks must be safely fastened before performing the handling 3 Fork lift ...

Страница 7: ...oes not exceed the design pressure of the water side heat exchangers and install a safety valve on the pipe of the water 12 Install a suitable expansion CAUTION To avoid damages install a filter that can be inspected on the water pipes at the entry to the heat exchangers Insulation of the pipes The complete water circuit including all the pipes must be insulated to avoid condensate from forming an...

Страница 8: ...ponsible for any damages or malfunctions of the equipment The quality of the water must comply with the specifications listed in the following table Circulating water Water supply Possible problems Elements to be checked pH at 25 C 6 8 8 0 6 8 8 0 Corrosion limescale Electrical conductivity mS m at 25 C 40 30 Corrosion limescale Chlorine ion mg Cl l 50 50 Corrosion Sulfate ion mg SO4 l 50 50 Corro...

Страница 9: ... installed must therefore ensure that the overall content of water allows the unit t operate continuously and therefore greater environmental comfort The minimum water content per unit must be calculated with a certain approximation using the following formula For units with 2 compressors M litres 12 153 x DT C 22 168 x P kW For units with 4 compressors M litres 0 32 x DT C 1 36 x P kW Where M min...

Страница 10: ...f other components of the system or other appliances in general 2 Plan an electrical circuit for the connection of the unit This circuit must be protected with the necessary safety devices that is a main switch an SB fuse on each phase and a leakage towards earth detector The recommended fuses are listed in the wiring diagram provided with the unit Turn off the switch of the main insulator before ...

Страница 11: ...equence and operation of all the safety devices The user must keep a log system booklet of the operating data of the unit installed and of all the periodic maintenance and service activities If the operator notes abnormal or unusual operating conditions he is advised to consult the authorized technical service of the manufacturer Periodic maintenance The periodic maintenance activities minimum are...

Страница 12: ...rranty All the units are tested at the factory and guaranteed for a specific period of time These units have been developed and constructed according to high quality standards ensuring years of failure free operation However it is important to ensure proper and periodical maintenance in accordance with all the procedures listed in this manual and with good practice of machines maintenance We stron...

Страница 13: ...nstalled in an aggressive environment perform this activity monthly The following are considered aggressive environments place with high concentration of industrial exhaust gas in the air Place close to the sea salt air Place close to a desert where there is a risk of sand storms Other aggressive environments 5 Safety valve Check that the cap and seal have not been tampered with Check that the saf...

Страница 14: ... collection centres This manual is a technical aid and does not represent a binding offer We cannot guarantee explicitly or implicitly the completeness accuracy or reliability of its contents All data and specifications contained herein may be modified without notice The data communicated at the time of the order shall hold firm The manufacturer shall assume no liability whatsoever for any direct ...

Страница 15: ...Frequency Drive condenser pump VFD 3 Way Valve VFD 3 Way Valve VFD Fans D L Limit of charge DI Digital Inputs DO Digital Outputs DPS Digital Setpoint EF External Fault EFS Evaporator Flow Switch GA General Alarm KPC 1 Pump 1 condenser water KPC 2 Pump 2 condenser water KPE 1 Pump 1 evaporator water S O Exclusion of the set point 1 HP Version only Cooling Heating Remote 2 VFD 2 ON OFF Moto Evaporat...

Страница 16: ...re A Typical single refrigerant circuit The input and output of the water of the condenser and the evaporator are approximate Consult the dimensional drawings of the unit for the exact hydraulic connections ...

Страница 17: ... Figure B Typical single refrigerant circuit of the moto evaporating version The input and output of the water of the evaporator are approximate Consult the dimensional drawings of the unit for the exact hydraulic connections ...

Страница 18: ... Figure C Typical single refrigerant circuit for Heat Pump The input and output of the water of the condenser and the evaporator are approximate Consult the dimensional drawings of the unit for the exact hydraulic connections ...

Страница 19: ...er 17 Refrigerant inlet connection from the remote condenser 18 Condenser leaving water connection 19 Condenser entering water connection 20 Evaporator leaving water connection 21 Evaporator entering water connection 22 Heat recovery leaving water connection 23 Heat recovery entering water connection DT Discharge temperature control CP High pressure transducer F13 High pressure switch ST Temperatu...

Страница 20: ...acy reliability or fitness for particular purpose of its content and the products and services presented therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted by Daikin Europe N...

Отзывы: