6 Commissioning

Installation manual

16

EWAQ+005BAVP

Packaged air-cooled water chillers and packaged air to water heat

pumps

4P469106-1 – 2017.01

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Checklist before commissioning

Do  NOT  operate  the  system  before  the  following  checks  are  OK.
Depending  on  the  system  layout,  not  all  components  may  be
available.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The 

control box

 is properly mounted.

The 

option box

 is properly mounted.

Only if you use the optional backup heater:

The 

backup heater

 is properly mounted.

The following 

field wiring

 has been carried out according

to  the  available  documentation  and  the  applicable
legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between the outdoor unit and the control box

▪ Between the control box and the option box

▪ Between the control box and the backup heater

▪ Between the local supply panel and the control box

▪ Between the local supply panel and the option box

▪ Between the outdoor unit and the valves

▪ Between the control box and the room thermostat

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

Only if you use the optional backup heater:

Depending  on  the  backup  heater  type, 

backup  heater

circuit  breaker

  F1B  (on  the  switch  box  of  the  backup

heater) is turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There are no 

water leaks

 inside the outdoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

pressure relief valve

 purges water when opened.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"3.2 Preparing water piping" on page 4

.

If 

glycol

  was  added  to  the  system,  confirm  the  correct

glycol concentration, and check if glycol setting [E‑0D]=1.

NOTICE

▪ Make  sure  glycol  setting  [E-0D]  matches  the  liquid

inside the water circuit (0=water only, 1=water+glycol).
If  the  glycol  setting  is  NOT  set  correctly,  the  liquid
inside the piping can freeze.

▪ When  glycol  is  added  to  the  system,  but  the  glycol

concentration is lower than prescribed, the liquid inside
the piping can still freeze.

INFORMATION

The  software  is  equipped  with  an  "installer-on-site"  mode
([4‑0E]),  that  disables  automatic  operation  by  the  unit.  At
first  installation,  setting  [4‑0E]  is  by  default  set  to  "1",
meaning  automatic  operation  is  disabled.  All  protective
functions  are  then  disabled.  If  the  user  interface  home
pages  are  off,  the  unit  will  NOT  operate  automatically.  To
enable  automatic  operation  and  the  protective  functions,
set [4‑0E] to "0".

12 hours after the first power-on, the unit will automatically
set  [4‑0E]  to  "0",  ending  "installer-on-site"  mode  and
enabling  the  protective  functions.  If  –  after  first
installation  –  the  installer  returns  to  the  site,  the  installer
has to set [4‑0E] to "1" manually.

6.2

Checklist during commissioning

The 

minimum  flow  rate

  is  guaranteed  in  all  conditions.

See  "To  check  the  water  volume  and  flow  rate"  in

"3.2 Preparing water piping" on page 4

.

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

6.2.1

To perform an air purge

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page and room temperature home page are turned OFF.

1

Go  to  [A.7.3]: 

  >  Installer  settings  >  Commissioning  >  Air

purge.

2

Set the type.

3

Select Start air purge and press 

.

4

Select OK and press 

.

NOTICE

The  outdoor  unit  is  equipped  with  a  manual  air  purge
valve. The air purge procedure requires manual action.

NOTICE

When  purging  air  with  the  manual  air  purge  valve  of  the
unit, collect any fluid that might leak out of the valve. If this
fluid is NOT collected, it might drip on internal components
and damage the unit.

Содержание EWAQ004BAVP

Страница 1: ... Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ004BAVP EWAQ005BAVP EWYQ004BAVP EWYQ005BAVP ...

Страница 2: ...ormatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoši ražotāja norādījumiem atbilst sekojošiem standartiem un c...

Страница 3: ...ser 17 7 1 About locking and unlocking 18 To activate or deactivate a function lock 18 To activate or deactivate button lock 18 8 Technical data 19 8 1 Piping diagram Outdoor unit 19 8 2 Wiring diagram Outdoor unit 20 1 About the documentation 1 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light...

Страница 4: ...r unit Mind the following spacing guidelines 1200 250 400 250 400 250 350 350 mm mm a b b a a Air outlet b Air inlet INFORMATION If shut off valves are installed on the unit provide a minimum space of 400 mm at the air inlet side If shut off valves are NOT installed on the unit provide a minimum space of 250 mm Do NOT install the unit in sound sensitive areas e g near a bedroom so that the operati...

Страница 5: ...er interface 2 b Optional equipment 4 Remote outdoor sensor 2 c Field supplied components 5 Space heating cooling operation control or shut off valve 2 e Interconnection cable 6 Interconnection cable between outdoor unit and control box 2 d a Refer to name plate on outdoor unit b Cable section 0 75 mm till 1 25 mm maximum length 500 m Applicable for both single user interface and dual user interfa...

Страница 6: ...In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to install the unit on brackets to the wall 250 400 300 250 400 mm a a Maximum snowfall height 4 2 2 To install the outdoor unit CAUTION Do NOT rem...

Страница 7: ... in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate cannot freeze INFORMATION For information on the available options contact your dealer NOTICE Provide at least 300 mm of free space below the unit Additionally make ...

Страница 8: ...expected outdoor temperature Prevent from bursting Prevent from freezing 20 C 25 25 C 30 NOTICE The addition of glycol applies to BOTH cooling only models EWAQ004 005BAVP AND reversible models EWYQ004 005BAVP and is independent of cooling or heating operation ALWAYS add glycol if negative outdoor temperatures are expected The required concentration might differ depending on the type of glycol ALWA...

Страница 9: ...e 16 6 Refill the circuit until the pressure is 2 0 bar 7 Repeat steps 5 and 6 until no more air is purged and there are no more pressure drops 8 Close the drain and fill valve 9 Disconnect the water supply hose from the drain and fill valve 4 3 4 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction o...

Страница 10: ...tdoor unit If control box EKCB07CAV3 is part of the system you can also connect the user interface to the control box To do this connect the user interface to control box terminals X2M 20 21 and then connect the control box to the outdoor unit by connecting X2M 20 21 to outdoor unit terminals X5M 1 2 INFORMATION For details on how to connect the user interface to the control box refer to the insta...

Страница 11: ...ences the following The calculations of the software What you can see on and do with the user interface How You can configure the system via the user interface First time Quick wizard When you turn ON the user interface for the first time via the indoor unit a quick wizard starts to help you configure the system Afterwards If necessary you can make changes to the configuration afterwards INFORMATI...

Страница 12: ...button 01 02 06 0a 0e 00 03 07 0b 0f 00 00 04 08 0c 00 01 05 09 0d 20 Overview settings Confirm Adjust Scroll 5 Repeat previous steps if you have to modify other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 2 Basic configura...

Страница 13: ...can send a separate heating cooling thermo ON OFF condition Option box EK2CB07CAV3 Code Description A 2 2 F 1 C 02 External backup heater source 0 No None 1 Bivalent Gas boiler oil boiler 2 N A 3 N A Code Description A 2 2 F 2 C 09 Alarm output 0 Normally open The alarm output will be powered when an alarm occurs 1 Normally closed The alarm output will NOT be powered when an alarm occurs This inst...

Страница 14: ...cording to the difference between desired and actual room temperature This allows better matching of the heat pump capacity to actual required capacity and results in less start stop cycles of the heat pump and more economic operation N A 8 06 Leaving water temperature maximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water tem...

Страница 15: ...ype Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Backup heater Operation mode Enable BUH step 2 Equilibrium temp Prefer kWh ...

Страница 16: ...e pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 4 If glycol was added to the system confirm the correct glycol concentration and check if glycol setting E 0D 1 NOTICE Make sure glycol setting E 0D matches the liquid inside the water circuit 0 water only 1 water glycol If th...

Страница 17: ...settings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually press select OK and press Possible actuator test runs Backup heater step 1 test Backup heater step 2 test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoi...

Страница 18: ...ser to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific function to prevent people from changing its settings Button lock Locks all buttons to prevent users from changing settings To activate or deactivate a function lock 1 Press to go to the menu structure 2 ...

Страница 19: ...9 CuT 7 9 CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrigerant flow Cooling Heating Liquid stop valveV Plate heat exchanger Gas stop valve with service port Air purge Flow sensor Pump Flow switch Outlet Shut off valve with drain fill valve E...

Страница 20: ...tor W Connector X11A X12A Connector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU Blue BRN Brown GRN Green ORG Orange PPL Purple RED Red WHT White YLW Yellow Outdoor unit hydro module English Translation 1 Connection diagram 1 Connection diagram Compress...

Страница 21: ... contact X M K1 Terminal strip X Y Connector K1A Relay for heating K2A Relay for cooling Optional Field supply Control box option backup heater English Translation 1 Connection diagram 1 Connection diagram BUH option Backup heater option Control box Control box Only for Only for 2 Notes 2 Notes Earth wiring 15 Wire number 15 Field supply 1 Several wiring possibilities Option Wiring depending on mo...

Страница 22: ...30V 230V 230V Control box External room thermostat main zone signal signal signal 2 or 3 core 2 core 2 core Power limitation demand input 4 Power limitation demand input 3 Power limitation demand input 2 Power limitation demand input 1 Only for normal power supply installation Only for preferential kWh rate power supply installation normal kWh rate power supply for unit 230 V or L N earth Backup h...

Страница 23: ......

Страница 24: ...4P469106 1 2017 01 Copyright 2017 Daikin ...

Отзывы: