CG-SVX04C-E4
27
Operation
Control System
The control is through the TRACER
CH532 control module.
Unit operations
- Check the chilled water pump(s)
operates
- Start up the unit following
procedure described in the CH532
controller user guide. The unit will
operate correctly when there is
sufficient water flow. The
compressors will start up if the
evaporator water leaving
temperature is above the control
module setpoint.
Weekly start up
- Check the chilled water pump(s)
operates
- Start up the unit following
procedure described in the CH532
controller user guide.
Weekend shutdown
- If the unit needs to be shut down
for a short period of time, stop the
unit following procedure described
in the CH532 controller user guide.
(See "Clock" menu)
- If the unit is shut down for a
longer period, see under
"Seasonal shutdown", below.
- Ensure that all safeties are taken to
prevent frost damages during
negative ambient temperature.
- Do not put the general disconnect
switches to off, except if the unit is
drained. Daikin does not
recommend draining the unit, due
to the fact that it increases tube
corrosion.
Seasonal shutdown
- Check water flows and interlocks.
- Check glycol % in the chilled water
circuit if glycol presence is required
- Carry out leak test.
- Carry out oil analysis
- Record operating pressures,
temperatures, amperages and
voltage.
- Check operation of
machines/compare conditions of
operation against original
commissioning data.
- Stop the unit following procedure
described in the CH532 controller
user guide.
- Ensure that all safeties are taken to
prevent frost damages during
negative ambient temperature.
- Fill out the visit log sheet and
review with the operator - Do not
put the general disconnect switch
to off, except if the unit is drained.
Daikin does not recommend
draining the unit, due to the fact
that it increases tube corrosion.
Seasonal start-up
- Check water flows and interlocks.
- Check Ethylene glycol % in the
chilled water circuit if glycol
presence is required
- Check operational set points and
performance.
- Calibrate controls.
- Check operation of all safety
devices.
- Inspect contacts and tighten
terminals.
- Megger the motor compressor
windings.
- Record operating pressures,
temperatures, amperages and
voltage.
- Carry out leak test.
- Check configuration of unit control
module.
- Change the oil as required based
upon results of the oil analysis
made during seasonal shutdown
Get the 8 condition measurements at
the same time, on each circuit.
- HP
- LP
- Suction temperature
- Discharge temperature
- Liquid temperature
- Water entering temperature
- Water leaving temperature
- Outdoor ambient temperature
Then calculate the sub-cooling and
superheat. No diagnosis can be
accurate with one of these records
missing.
- Check operation of
machines/compare conditions of
operation against original
commissioning data.
- Fill out the visit log sheet and
review with the operator
Содержание EWAP/EWYP 060-260
Страница 212: ...1 2 3 Daikin EWAP EWYP 212 CG SVX04C EL...
Страница 213: ...CG SVX04C EL 213 Daikin 3 7 Daikin...
Страница 214: ...214 CG SVX04C EL Daikin...
Страница 215: ...CG SVX04C EL 215 212 216 225 225 225 225 228 230 230 230 232 E 232 237 237 237 238 239 240...
Страница 225: ...Daikin 5 I MAX 4 060 6 075 260 8 1 2 CG SVX04C EL 225...
Страница 230: ...230 CG SVX04C EL Daikin Daikin AISI 316 1 4401 Daikin Daikin J 1 2 1 2 C 8 1 2 3 1 C 2 C LP...
Страница 232: ...232 CG SVX04C EL megger 500V DC 2 TRACER CH532 megger 500V DC 500 CH532 15 Daikin 2 Daikin 9 11 50 E To Daikin 11 11 1 2...
Страница 233: ...CG SVX04C EL 233 Daikin 4 7 C R407C 2 10 C R407C R407C 15 23 C 3 C R407C J J Daikin 2 2 5 60 Daikin Daikin Daikin 30...
Страница 237: ...CG SVX04C EL 237 TRACER CH532 CH532 CH532 CH532 off Daikin CH532 off Daikin megger 8 HP LP...
Страница 238: ...238 CG SVX04C EL 500 megger Daikin Daikin Daikin Daikin Daikin Daikin Daikin 60 C 20000 25000...
Страница 239: ...CG SVX04C EL 239 Daikin...
Страница 240: ...240 CG SVX04C EL Daikin A H B H H...
Страница 241: ...CG SVX04C EL 241 E H K Daikin...
Страница 332: ...1 2 3 Daikin EWAP EWYP 332 CG SVX04C RU...
Страница 333: ...CG SVX04C RU 333 Daikin 3 7 Daikin...
Страница 334: ...334 CG SVX04C RU...
Страница 335: ...CG SVX04C RU 335 332 336 345 345 345 345 348 350 350 350 352 352 357 357 357 358 359 360...
Страница 345: ...Daikin 5 I MAX 4 060 6 075 260 8 1 1 2 2 CG SVX04C RU 345...
Страница 350: ...350 CG SVX04C RU Daikin Daikin AISI 316 1 4401 Daikin Daikin 1 2 1 2 C 8 8 1 2 3 1 2 C...
Страница 352: ...352 CG SVX04C RU 500 2 TRACER 532 500 500 CH532 15 Daikin 2 9 11 50 Daikin 11 1 11 1 1 2...
Страница 353: ...CG SVX04C RU 353 Daikin R407C 4 7 C R407C 2 10 C R407C 15 23 C R407 3 C Daikin 2 2 5 60 Daikin Daikin Daikin 30...
Страница 357: ...CG SVX04C RU 357 TRACER CH532 CH532 CH532 CH532 Clock Daikin CH532 Daikin 8 HP LP...
Страница 358: ...358 CG SVX04C RU 5 50 00 0 Daikin Daikin Daikin Daikin Daikin 60 C 20000 25000...
Страница 359: ...CG SVX04C RU 359 Daikin...
Страница 360: ...360 CG SVX04C RU Daikin A A B B C C a b a b a b...
Страница 361: ...CG SVX04C RU 361 D D E E F F G G H H I I J J K K a b a b Daikin a b a b...