Installation and operation manual

7

EUWAC5~10FZ

Packaged air-cooled water chillers

4PW14037-1D

B

EFORE

 

OPERATION

Checks before initial start-up 

After the installation of the water chiller, check the following before
switching on the circuit breaker:

1

Field wiring

Make sure that the field wiring between the local supply panel
and the water chiller has been carried out according to the
instructions described in the chapter “

Installing the unit

”,

according to the wiring diagram and according to European and
national regulations.

2

Additional interlock contact

An additional interlock contact S11L should be provided (e.g.
flow switch or contact of pump motor contactor). Make sure that
it has been installed between the appropriate terminals (refer to
the wiring diagram supplied with the unit). S11L should be a
normal open contact.

3

Fuses or protection devices

Check that the fuses or the locally installed protection devices
are of the size and type specified in the chapter “

Installing the

unit

”. Make sure that neither a  fuse nor a protection device has

been bypassed.

4

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

5

Internal wiring

Visually check the switch box on loose connections or damaged
electrical components.

6

Fixation

Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.

7

Damaged equipment

Check the inside of the unit on damaged components or
squeezed pipes. 

8

Refrigerant leak 

Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local Daikin dealer.

9

Oil leak 

Check the compressor on oil leakage. If there is an oil leak, call
your local Daikin dealer.

10

Air inlet/outlet

Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material. Clean the inside
of the ducts and make sure that the air ducts are properly
installed.

11

Protective guard

Check that the protective guard(s) is (are) properly installed in
front of the air outlet(s).

12

Drain disposal

Check the proper operation of the drain. Pour some water into
the drain pan and check whether the water evacuates freely
through the drain.

Water supply

Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the chapter “

Installing the unit

”.

Make sure that the water is of the quality as mentioned in the chapter

Installing the unit

”.

Purge the air at the high points of the system and check the operation
of the circulation pump and the flow switch.

Power supply connection and crankcase heating 

To switch on the crankcase heater proceed as follows:

1

Switch on the circuit breaker on the local supply panel. Make
sure that the unit is “OFF”.

2

The crankcase heater is switched on automatically.

3

Check the supply voltage on the supply terminals L1, L2, L3, (N)
by means of a voltmeter. The voltage should correspond to the
voltage indicated on the identification label of the unit. If the
voltmeter reads values which are not within the ranges specified
in the technical data, check the field wiring and replace the
supply cables if necessary.

4

Check the LED on the reverse phase protector. If it lights up, the
phase order is correct. If not, switch off the circuit breaker and
call a licensed electrician to connect the wires of the power
supply cable in the correct phase order.

After six hours, the unit is ready for operation.

General recommendations

Before switching on the unit, read following recommendations:

1

When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.

2

The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.

O

PERATION

The EUWAC units are equipped with a digital controller offering a
user-friendly way to set up, use and maintain the unit.

This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.

Make sure that the circuit breaker on the power supply
panel of the water chiller is switched off.

In order to avoid compressor damage, it is necessary to
switch on the crankcase heater for at least six hours
before starting the compressor after a long period of stand-
still.

Содержание EUWAC8FZW1

Страница 1: ...INSTALLATION AND OPERATION MANUAL EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1 Packaged air cooled water chillers...

Страница 2: ...D E F G H I J K L M N O P Q R EUWAC5FZ mm 243 311 243 1345 343 125 765 71 58 629 108 25 796 605 735 578 600 795 EUWAC8FZ mm 163 800 162 1290 267 98 815 71 60 951 111 25 1125 605 288 975 600 1122 EUWAC...

Страница 3: ...en i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob u...

Страница 4: ...and used for cooling applications only The units are available in 3 standard sizes with nominal cooling capacities ranging from 11 2 to 22 6 kW The EUWAC packaged air cooled water chillers can be comb...

Страница 5: ...dboard box and attached on a wooden pallet At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account...

Страница 6: ...the water circuit 1 Use clean pipes only 2 Hold the pipe end downwards when removing burrs 3 Cover the pipe end when inserting it through a wall so that no dust and dirt enter WATER CHARGE FLOW AND Q...

Страница 7: ...d that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equip me...

Страница 8: ...lter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the expansion valve and tubes Thermostatic expansion valve The liquid refrigerant coming from th...

Страница 9: ...ter becomes too low in order to prevent freezing of the water during operation When the outlet water temperature returns to normal the protector resets automatically but the controller needs to be res...

Страница 10: ...er operation of the drain Pour some water into the drain pan and check whether the water evacuates freely through the drain Water supply Fill the water piping taking into account the minimum water vol...

Страница 11: ...9 Consulting actual operational information on page 9 Resetting alarms on page 9 Resetting warnings on page 10 Switching the EUWAC unit on To switch the EUWAC unit on proceed as follows 1 When the on...

Страница 12: ...er temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of direct parameters without saving the modified parameter The inlet water t...

Страница 13: ...t of direct parameters is accessible by pressing the R key for approximately 5 seconds When scrolling through the list of direct parameters using the A and or Z key the parameters appear in the follow...

Страница 14: ...aying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifications The i...

Страница 15: ...t other user parameters before saving the modifications select another user parameter using the A and or Z key and then repeat from instruction 3 onwards 7 To save the modifications press the E key To...

Страница 16: ...without saving the modifications The inlet water temperature reappears on the display TROUBLESHOOTING This section provides useful information for diagnosing and correct ing certain troubles which may...

Страница 17: ...freely Air flow in the unit too low or outdoor temperature too high Clean the air heat exchanger properly RESET After temperature decrease the thermal protector is reset automatically If the protecto...

Страница 18: ...leak is detected call your local Daikin dealer Check the working pressure of the unit Refer to paragraph Working pressure on page 8 in the chapter Switching the EUWAC unit on 6 Compressor Check on oi...

Страница 19: ...5 10 5 15 20 15 30 25 40 35 50 C 45 5 Hp 8 Hp 10 Hp General specifications IN OUT IN OUT IN OUT Nominal air flow m3 min 70 70 100 100 125 125 long side W mm 763 341 952 802 1102 938 short side P mm 6...

Страница 20: ...ESP External static pressure AF Air flow 1 ESP with pulley closed factory setting 2 ESP with pulley 1 turn open 3 ESP with pulley 2 turns open 4 ESP with pulley 3 turns open 5 ESP with pulley 4 turns...

Страница 21: ...4 4 6 7 16 11 10 12 13 6 7 16 11 10 12 13 2 15 4 5 2 15 3 9 8 1 14 9 8 1 14 5 5 M1C P S4LP 6 P S1HP 7 1 3 9 8 5 4 2 10 10 R3T R4T M11F M11F EUWAC5 EUWAC8 10...

Страница 22: ...4PW14037 1D Copyright Daikin...

Отзывы: