Installer reference guide

4

EPRA14~18D + ET23E

Daikin Altherma 3 H HT F

4P644739-1A – 2022.03

10.3.5

Setpoint screen............................................................................................................................................... 133

10.3.6

Detailed screen with values ........................................................................................................................... 134

10.3.7

Schedule screen: Example.............................................................................................................................. 134

10.4

Weather-dependent curve ............................................................................................................................................. 138
10.4.1

What is a weather-dependent curve? ........................................................................................................... 138

10.4.2

2-points curve................................................................................................................................................. 139

10.4.3

Slope-offset curve........................................................................................................................................... 140

10.4.4

Using weather-dependent curves.................................................................................................................. 141

10.5

Settings menu ................................................................................................................................................................. 143
10.5.1

Malfunctioning ............................................................................................................................................... 143

10.5.2

Room............................................................................................................................................................... 144

10.5.3

Main zone ....................................................................................................................................................... 148

10.5.4

Additional zone............................................................................................................................................... 159

10.5.5

Space heating/cooling .................................................................................................................................... 164

10.5.6

Tank................................................................................................................................................................. 173

10.5.7

User settings ................................................................................................................................................... 181

10.5.8

Information..................................................................................................................................................... 186

10.5.9

Installer settings ............................................................................................................................................. 187

10.5.10

Commissioning ............................................................................................................................................... 209

10.5.11

User profile ..................................................................................................................................................... 209

10.5.12

Operation........................................................................................................................................................ 209

10.5.13

WLAN .............................................................................................................................................................. 210

10.6

Menu structure: Overview user settings........................................................................................................................ 213

10.7

Menu structure: Overview installer settings.................................................................................................................. 214

11 Commissioning

215

11.1

Overview: Commissioning .............................................................................................................................................. 215

11.2

Precautions when commissioning .................................................................................................................................. 216

11.3

Checklist before commissioning..................................................................................................................................... 216

11.4

Checklist during commissioning ..................................................................................................................................... 217
11.4.1

Minimum flow rate......................................................................................................................................... 217

11.4.2

Air purge function........................................................................................................................................... 218

11.4.3

Operation test run.......................................................................................................................................... 221

11.4.4

Actuator test run ............................................................................................................................................ 222

11.4.5

Underfloor heating screed dryout ................................................................................................................. 223

12 Hand-over to the user

227

13 Maintenance and service

228

13.1

Maintenance safety precautions.................................................................................................................................... 228

13.2

Yearly maintenance ........................................................................................................................................................ 228
13.2.1

Yearly maintenance outdoor unit: overview ................................................................................................. 228

13.2.2

Yearly maintenance outdoor unit: instructions............................................................................................. 229

13.2.3

Yearly maintenance indoor unit: overview.................................................................................................... 229

13.2.4

Yearly maintenance indoor unit: instructions ............................................................................................... 229

13.3

To drain the domestic hot water tank............................................................................................................................ 232

13.4

About cleaning the water filter in case of trouble ......................................................................................................... 232
13.4.1

To remove the water filter ............................................................................................................................. 233

13.4.2

To clean the water filter in case of trouble.................................................................................................... 233

13.4.3

To install the water filter ................................................................................................................................ 234

14 Troubleshooting

236

14.1

Overview: Troubleshooting ............................................................................................................................................ 236

14.2

Precautions when troubleshooting ................................................................................................................................ 236

14.3

Solving problems based on symptoms........................................................................................................................... 237
14.3.1

Symptom: The unit is NOT heating or cooling as expected........................................................................... 237

14.3.2

Symptom: Hot water does NOT reach the desired temperature.................................................................. 238

14.3.3

Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 238

14.3.4

Symptom: The system is making gurgling noises after commissioning ........................................................ 239

14.3.5

Symptom: The pump is blocked..................................................................................................................... 239

14.3.6

Symptom: The pump is making noise (cavitation)......................................................................................... 240

14.3.7

Symptom: The pressure relief valve opens.................................................................................................... 240

14.3.8

Symptom: The water pressure relief valve leaks........................................................................................... 241

14.3.9

Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 241

14.3.10

Symptom: The pressure at the tapping point is temporarily unusually high................................................ 242

14.3.11

Symptom: Tank disinfection function is NOT completed correctly (AH-error)............................................. 242

14.4

Solving problems based on error codes ......................................................................................................................... 243
14.4.1

To display the help text in case of a malfunction .......................................................................................... 243

14.4.2

Error codes of the unit ................................................................................................................................... 243

15 Disposal

248

Содержание ETVZ16E6V7

Страница 1: ...reference guide Daikin Altherma 3 H HT F EPRA14D V3 EPRA16D V3 EPRA18D V3 EPRA14D W1 EPRA16D W1 EPRA18D W1 ETVZ16S18E 6V ETVZ16S23E 6V ETVZ16S18E 9W ETVZ16S23E 9W A B C Z 1 2 3 9 https daikintechnical...

Страница 2: ...erview Application guidelines 33 6 2 Setting up the space heating cooling system 34 6 2 1 Multiple rooms Two LWT zones 35 6 3 Setting up an auxiliary heat source for space heating 37 6 4 Setting up th...

Страница 3: ...ng 84 8 2 7 To fill the domestic hot water tank 87 8 2 8 To insulate the water piping 88 9 Electrical installation 89 9 1 About connecting the electrical wiring 89 9 1 1 Precautions when connecting th...

Страница 4: ...ly maintenance outdoor unit overview 228 13 2 2 Yearly maintenance outdoor unit instructions 229 13 2 3 Yearly maintenance indoor unit overview 229 13 2 4 Yearly maintenance indoor unit instructions 2...

Страница 5: ...o manually open the electronic expansion valves 249 15 1 2 Recovery mode 250 16 Technical data 252 16 1 Service space Outdoor unit 253 16 2 Piping diagram Outdoor unit 254 16 3 Piping diagram Indoor u...

Страница 6: ...manual Outdoor unit Installation instructions Format Paper in the box of the outdoor unit Installation manual Indoor unit Installation instructions Format Paper in the box of the indoor unit Installe...

Страница 7: ...s professional standbyme daikin eu Daikin e Care Mobile app for installers and service technicians that allows you to register configure and troubleshoot heating systems The mobile app can be download...

Страница 8: ...r inspecting the unit Symbols used in the documentation Symbol Explanation Indicates a figure title or a reference to it Example 1 3 Figure title means Figure 3 in chapter 1 Indicates a table title or...

Страница 9: ...and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Hand over to the user What to give and explain to the user Main...

Страница 10: ...electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optional equipment and spare parts made or approved by Daikin WARNING Make sure installation testing and...

Страница 11: ...ing places In potentially explosive atmospheres In places where there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the eq...

Страница 12: ...han the specified amount of refrigerant When the refrigerant system is to be opened refrigerant MUST be treated according to the applicable legislation NOTICE Make sure refrigerant piping installation...

Страница 13: ...more information NOTICE Make sure water quality complies with EU directive 2020 2184 2 1 5 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover conne...

Страница 14: ...WARNING After finishing the electrical work confirm that each electrical component and terminal inside the electrical components box is connected securely Make sure all covers are closed before start...

Страница 15: ...the radio waves a distance of 1 meter may NOT be sufficient NOTICE ONLY applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility o...

Страница 16: ...1 Service space Outdoor unit 4253 Indoor unit See 7 1 3 Installation site requirements of the indoor unit 456 Special requirements for R32 see 7 1 1 Installation site requirements of the outdoor unit...

Страница 17: ...ns from this manual See 7 4 Mounting the indoor unit 471 Piping installation see 8 Piping installation 473 WARNING Field piping method MUST be in accordance with the instructions from this manual See...

Страница 18: ...cal connections to the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N pha...

Страница 19: ...d by the installer according to the applicable legislation WARNING Be aware that the domestic hot water temperature at the hot water tap will be equal to the value selected in field setting 2 03 after...

Страница 20: ...he respective circuit breaker When a safety device was activated stop the unit and find out why the safety device was activated before resetting it NEVER shunt safety devices or change their values to...

Страница 21: ...39 1A 2022 03 Disposal see 15 Disposal 4248 WARNING Rotating fan Before powering ON or servicing the outdoor unit make sure that the discharge grille covers the fan as protection against a rotating fa...

Страница 22: ...its final installation position to prevent damage during transport Prepare in advance the path along which you want to bring the unit to its final installation position In this chapter 4 1 Outdoor un...

Страница 23: ...in Altherma 3 H HT F 4P644739 1A 2022 03 Forklift or pallet truck Enter the pallet from the heavy side Manually After unpacking carry the unit using the slings attached to the unit See also 4 1 2 To u...

Страница 24: ...4 About the box Installer reference guide 24 EPRA14 18D ETVZ16S18 23E Daikin Altherma 3 H HT F 4P644739 1A 2022 03 4 1 2 To unpack the outdoor unit 1 2 3 4...

Страница 25: ...ain socket c Shut off valve with integrated filter d Thermistor fixture for installations in areas with low ambient temperatures e Compressor cover piece f Installation manual Outdoor unit g Disposal...

Страница 26: ...ure bypass valve c Mounting plate screw for demand PCB EKRP1AHTA and digital I O PCB EKRP1HBAA d General safety precautions e Addendum book for optional equipment f Indoor unit installation manual g O...

Страница 27: ...nce guide 27 EPRA14 18D ETVZ16S18 23E Daikin Altherma 3 H HT F 4P644739 1A 2022 03 b a a b a Handles at the back of the unit b Handles at the bottom of the unit Carefully tilt the unit to the back so...

Страница 28: ...8 5 1 2 Identification label Indoor unit 29 5 2 Combining units and options 29 5 2 1 Possible combinations of indoor unit and outdoor unit 29 5 2 2 Possible options for the outdoor unit 29 5 2 3 Possi...

Страница 29: ...del series 6V Backup heater model 7 Model series 5 2 Combining units and options INFORMATION Certain options may NOT be available in your country 5 2 1 Possible combinations of indoor unit and outdoor...

Страница 30: ...Remote sensor for wireless thermostat EKRTETS You can use the remote indoor temperature sensor EKRTETS only in combination with the wireless thermostat EKRTR1 or EKRTRB For installation instructions s...

Страница 31: ...PC It gives the possibility to update the hydro software and EEPROM For installation instructions see Installation manual of the PC cable 10 1 2 To connect the PC cable to the switch box 4126 Heat pum...

Страница 32: ...om that you want to control For installation instructions see the installation and operation manual of the Human Comfort Interface HCI as room thermostat and the addendum book for optional equipment S...

Страница 33: ...ential kWh rate power supply 46 6 6 Setting up the power consumption control 47 6 6 1 Permanent power limitation 48 6 6 2 Power limitation activated by digital inputs 49 6 6 3 Power limitation process...

Страница 34: ...osed contact thermo ON open contact thermo OFF 6 2 Setting up the space heating cooling system The heat pump system supplies leaving water to heat emitters in one or more rooms Because the system offe...

Страница 35: ...pical installation consists of underfloor heating at a lower temperature and radiators at a higher water temperature In this document Main zone Zone with the lowest design temperature in heating and t...

Страница 36: ...r unit The desired room temperature is set via the external thermostat and the thermostatic valves of the radiators in each room The heating demand signal from the external thermostat is connected to...

Страница 37: ...h the heat pump system 6 3 Setting up an auxiliary heat source for space heating INFORMATION Bivalent is only possible in case of 1 leaving water temperature zone with room thermostat control OR exter...

Страница 38: ...the auxiliary boiler controller to maximum 70 C Install an aquastat valve in the return water flow of the heat pump Set the aquastat valve to close above 70 C and to open below 70 C Install non retur...

Страница 39: ...tivation of indoor unit field supply K2A Auxiliary relay for activation of boiler field supply Indoor Indoor unit Auto Automatic Boiler Boiler NOTICE Make sure the auxiliary contact has enough differe...

Страница 40: ...e 15 C Selecting the volume and desired temperature for the DHW tank consists of 1 Determining the DHW consumption equivalent hot water volume at 40 C 2 Determining the volume and desired temperature...

Страница 41: ...ower the desired DHW tank temperature The heat pump itself can produce domestic hot water of maximum 63 C 57 C if outdoor temperature is low The electrical resistance integrated in the heat pump can i...

Страница 42: ...nfiguration 4123 6 4 4 DHW pump for instant hot water Setup a b c d a Cold water IN b Hot water OUT shower field supply c DHW pump field supply d Recirculation connection By connecting a DHW pump inst...

Страница 43: ...during disinfection see 2 03 in the field settings table you can connect a DHW pump and heater element as shown above If applicable legislation requires disinfection of the water piping until the tap...

Страница 44: ...roduced heat will NOT be calculated nor will it be displayed on the user interface The produced heat is calculated internally based on The leaving and entering water temperature The flow rate Setup an...

Страница 45: ...ption make sure ALL power input of the system is covered by the electrical power meters 6 5 3 Normal kWh rate power supply General rule One power meter that covers the entire system is sufficient Setu...

Страница 46: ...he electrical meter cannot easily be installed in the electrical cabinet 230 V and 400 V three phase grids are combined very uncommon because of technical limitations of power meters Connection and se...

Страница 47: ...kWh rate power supply c Power meter L1 N d Power meter L1 L2 L3 N e Fuse L1 N f Fuse L1 L2 L3 N g Outdoor unit L1 N h Indoor unit L1 N i Backup heater L1 L2 L3 N S1S Preferential kWh rate power supply...

Страница 48: ...e heat pump will reduce performance NOTICE Set a minimum power consumption of 3 6 kW to guarantee Defrost operation Otherwise if defrosting is interrupted several times the heat exchanger will freeze...

Страница 49: ...limitation level Example To limit the maximum power of the entire house lighting domestic appliances space heating a b A B C 1 2 3 4 5 A8P A Outdoor unit B Indoor unit C Energy management system a Pow...

Страница 50: ...d and turned OFF first The system limits power consumption in the following order 1 Turns OFF the backup heater 2 Limits the outdoor unit 3 Turns OFF the outdoor unit Example If the configuration is a...

Страница 51: ...nal temperature sensor You can connect one external temperature sensor It measures the indoor or outdoor ambient temperature We recommend to use an external temperature sensor in the following cases I...

Страница 52: ...sensor and the addendum book for optional equipment Configuration Select outdoor sensor 9 B When the power saving functionality of the outdoor unit is active see Power saving function 4207 the outdoor...

Страница 53: ...the outdoor unit 64 7 3 3 To provide the installation structure 64 7 3 4 To install the outdoor unit 65 7 3 5 To provide drainage 66 7 3 6 To install the discharge grille 67 7 3 7 To remove the disch...

Страница 54: ...y start rotating very fast until it breaks It is recommended to install a baffle plate when the air outlet is exposed to wind It is recommended to install the outdoor unit with the air inlet facing th...

Страница 55: ...ing c Outdoor unit d Windbreaker The outdoor unit is designed for outdoor installation only and for the following ambient temperatures Cooling mode 10 43 C Heating mode 28 35 C Special requirements fo...

Страница 56: ...d at least 100 mm above the maximum expected level of snow See 7 3 Mounting the outdoor unit 463 for more details In heavy snowfall areas it is very important to select an installation site where the...

Страница 57: ...ank full of water into account Make sure in the event of a water leak water cannot cause any damage to the installation space and surroundings Do NOT install the unit in places such as In places where...

Страница 58: ...3 3 1 1 2 3 4 3 7 2 3 To remove the transportation stay NOTICE If the unit is operated with the transportation stay attached abnormal vibration or noise may be generated The transportation stays prot...

Страница 59: ...essor mounting bolt and tighten to 10 1 N m of torque 4 b a a a a a a Screw b Transportation stay 4 Remove the screws a 5 from the transportation stay b Put 4 screws a aside for later use see 7 2 4 To...

Страница 60: ...close the outdoor unit NOTICE When closing the outdoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 1 1 2 3 2 4 4 3 3 3 1 7 2 6 To open the indoor unit Overview a b d c e a...

Страница 61: ...face panel Open the hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent dama...

Страница 62: ...you need access to the high voltage components remove the high voltage switch box cover 4 T25 7 2 7 To lower the switch box on the indoor unit During the installation you will need access to the insi...

Страница 63: ...e switch box 2 Put the switch box back into place 3 Reinstall the top panel 4 Reinstall the side panels 5 Reinstall the front panel 6 Reconnect the cables to the user interface panel 7 Reinstall the u...

Страница 64: ...oor unit INFORMATION Also read the precautions and requirements in the following chapters 2 General safety precautions 410 7 1 Preparing the installation site 453 7 3 3 To provide the installation str...

Страница 65: ...ition See 7 3 7 To remove the discharge grille and put the grille in safety position 469 8 0 0 479 a 150 mm 4 M12 a Make sure not to cover the drain hole in the bottom plate of the unit 7 3 4 To insta...

Страница 66: ...it Avoid drain water flowing over the footpath so that it does NOT become slippery in case of ambient freezing temperatures If you install the unit on a frame install a waterproof plate within 150 mm...

Страница 67: ...se the drain plug with O ring and a hose for drainage 1 2 a b c c 3 d a Drain hole b O ring delivered as accessory c Drain plug delivered as accessory d Hose field supply NOTICE O ring Make sure the O...

Страница 68: ...rews 3 2 5 N m Install the upper part of the discharge grille NOTICE Vibrations Make sure the upper part of the discharge grille is attached seamlessly to the lower part to prevent vibrations 4 Align...

Страница 69: ...e grille in safety position WARNING Rotating fan Before powering ON or servicing the outdoor unit make sure that the discharge grille covers the fan as protection against a rotating fan See 7 3 6 To i...

Страница 70: ...0 EPRA14 18D ETVZ16S18 23E Daikin Altherma 3 H HT F 4P644739 1A 2022 03 4 3 Rotate the lower part of the discharge grille 4 Align the ball stud and hook on the grille with their counterparts on the un...

Страница 71: ...INFORMATION Also read the precautions and requirements in the following chapters 2 General safety precautions 410 7 1 Preparing the installation site 453 7 4 3 To install the indoor unit 1 Lift the i...

Страница 72: ...o an appropriate drain according to the applicable legislation You can route the drain hose through the left or right side panel Prerequisite The user interface panel and front panel have been removed...

Страница 73: ...ng 83 8 2 5 To fill the water circuit 84 8 2 6 To protect the water circuit against freezing 84 8 2 7 To fill the domestic hot water tank 87 8 2 8 To insulate the water piping 88 8 1 Preparing water p...

Страница 74: ...ternal static pressure of the pump See 16 Technical data 4252 for the external static pressure curves of the indoor unit Water flow You can find the minimum required water flow for indoor unit operati...

Страница 75: ...properly so that they do NOT make contact with each other This to prevent galvanic corrosion Valve Change over time When using a 2 way valve or a 3 way valve in the water circuit the maximum change ov...

Страница 76: ...0 3 H 10 bar 8 1 3 To check the water volume and flow rate The indoor unit has an expansion vessel of 10 litre with a factory set pre pressure of 1 bar To make sure that the unit operates properly Yo...

Страница 77: ...NOTICE The maximum water volume depends on whether glycol is added to the water circuit For more information on the addition of glycol refer to 8 2 6 To protect the water circuit against freezing 484...

Страница 78: ...case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the indoor unit If the indoor unit is at the hi...

Страница 79: ...e pre pressure take following guidelines into account Only use dry nitrogen to set the expansion vessel pre pressure Inappropriate setting of the expansion vessel pre pressure will lead to malfunction...

Страница 80: ...r piping to the outdoor unit 2 Connecting the water piping to the indoor unit 3 Connecting the recirculation piping 4 Connecting the drain hose to the drain 5 Filling the water circuit 6 Filling the d...

Страница 81: ...on of the valve at the water inlet is mandatory Mind the flow direction of the valve NOTICE Install air purge valves at all local high points Indoor unit NOTICE Do NOT use excessive force when connect...

Страница 82: ...to install shut off valves to domestic cold water in and domestic hot water out connections These shut off valves are field supplied NOTICE To avoid damage to the surroundings in case of water leakag...

Страница 83: ...accordance with the applicable legislation An expansion vessel should be installed on the cold water inlet in accordance with the applicable legislation It is recommended to install the pressure relie...

Страница 84: ...evention 4195 Drain prevention Only applicable when Bivalent is enabled C 02 1 This function prevents the opening of freeze protection valves in the water piping to the outdoor unit when the auxiliary...

Страница 85: ...l absorbs water from its environment Therefore do NOT add glycol that has been exposed to air Leaving the cap off the glycol container causes the concentration of water to increase The glycol concentr...

Страница 86: ...eeze When water is at standstill inside the system the system is very likely to freeze and get damaged Glycol and the maximum allowed water volume Adding glycol to the water circuit reduces the maximu...

Страница 87: ...15 cm 10 cm c Isolation of water inside the house when there is a power interruption Normally closed valves located indoors near the piping entry exit points can prevent that all water from indoor pip...

Страница 88: ...below table as a minimum with 0 039 W mK Piping length m Minimum insulation thickness mm 20 19 20 30 32 30 40 40 40 50 50 For other cases the minimum insulation thickness can be determined using the...

Страница 89: ...tricity meters 109 9 3 5 To connect the domestic hot water pump 110 9 3 6 To connect the alarm output 111 9 3 7 To connect the space cooling heating ON OFF output 112 9 3 8 To connect the changeover t...

Страница 90: ...o NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING Rotating fan Before powerin...

Страница 91: ...type Installation method Single core wire c b c a a A AA A a Curled single core wire b Screw c Flat washer Stranded conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c...

Страница 92: ...ates seasonal rates W rmepumpentarif in Germany and Austria This equipment allows for connection to such preferential kWh rate power supply delivery systems Consult with the electricity company acting...

Страница 93: ...ntial kWh rate power supply activation power supply is interrupted immediately or after some time by the electricity company In this case the indoor unit must be powered by a separate normal power sup...

Страница 94: ...ength may cause electrical shock or leakage 3 Insert the cables at the back of the unit and route them through the factory mounted cable sleeves into the switch box d c2 b2 c1 b1 a1 a2 a1 a2 Power sup...

Страница 95: ...BLU YLW GRN b a L N a Power supply cable field supply b Field wiring F1B Overcurrent fuse field supply Recommended fuse 2 pole 32 A fuse C curve Q1DI Earth leakage circuit breaker 30 mA field supply...

Страница 96: ...Drain tube heater cable Make sure the heating element of the drain tube heater is completely inside the drain tube Route the cable through the frame Connect the wires to the terminal block and the ea...

Страница 97: ...4A to X806A X806A X804A X805A INFORMATION Power saving function The power saving function is only applicable for V3 models For more information about the power saving function 9 F or overview field se...

Страница 98: ...GRN a Power supply cable field supply b Field wiring F1B Overcurrent fuse field supply Recommended fuse 4 pole 16 A or 20 A fuse C curve Q1DI Earth leakage circuit breaker 30 mA field supply 2 Interc...

Страница 99: ...Drain tube heater cable Make sure the heating element of the drain tube heater is completely inside the drain tube Route the cable through the frame Connect the wires to the terminal block and the ea...

Страница 100: ...16S18 23E Daikin Altherma 3 H HT F 4P644739 1A 2022 03 1 2 9 2 2 To reposition the air thermistor on the outdoor unit This procedure is only necessary in areas with low ambient temperatures Required a...

Страница 101: ...alarm output 4111 Space cooling heating operation control See 9 3 7 To connect the space cooling heating ON OFF output 4112 Changeover to external heat source control See 9 3 8 To connect the changeov...

Страница 102: ...ion manual of the heat pump convector options Addendum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Ext thermostat type For the additional...

Страница 103: ...thermostat Addendum book for optional equipment Wired room thermostat without multi zoning base unit Installation manual of the wired room thermostat Addendum book for optional equipment Wired room th...

Страница 104: ...nnection cable main power supply In case of preferential kWh rate power supply Interconnection cable main power supply Wires 3 GND 1 5 mm Normal kWh rate power supply Wires 1N Maximum running current...

Страница 105: ...s INFORMATION In case of preferential kWh rate power supply connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kW...

Страница 106: ...ical equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with in...

Страница 107: ...BRN GRY BLU1 BLU2 6V 6T1 3 230 V SWB 3 50 Hz 230 V AC 4 3 6 5 2 1 K5M 14 13 1 2 3 4 5 6 7 8 F1B I I I I Q1DI L1 L2 L3 X6M BRN GRY BLU1 BLU2 9W 3N 400 V 3N 50 Hz 400 V AC SWB Q1DI L1 L2 L3 N 1 2 3 4 5...

Страница 108: ...pump convectors install a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied b...

Страница 109: ...s 12 V DC pulse detection voltage supplied by PCB 9 A Energy metering INFORMATION In case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X...

Страница 110: ...5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open the following see 7 2 6 To op...

Страница 111: ...put Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 9 D Alarm output 1 Open the following see 7 2 6 To open the indoor unit 460 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connec...

Страница 112: ...tie mountings 9 3 7 To connect the space cooling heating ON OFF output Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 1 Open the following see 7 2 6 To open the indoor unit 460 1 Top panel 1 2 3 2 User...

Страница 113: ...ings 9 3 8 To connect the changeover to external heat source INFORMATION Bivalent is only possible in case of 1 leaving water temperature zone with room thermostat control OR external room thermostat...

Страница 114: ...mountings 9 3 9 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power limitation digital inputs 12 V DC 12 mA detection voltage supplied by PCB 9 9 Power consumption c...

Страница 115: ...TA is required 3 Fix the cable with cable ties to the cable tie mountings 9 3 10 To connect the safety thermostat normally closed contact 1 Open the following see 7 2 6 To open the indoor unit 460 1 T...

Страница 116: ...fety thermostat is typically a thermostatically controlled valve with a normally closed contact When the water temperature in the main zone is too high the contact will open and the user interface wil...

Страница 117: ...tat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFORMATION ALWAYS configure the safety thermostat for the...

Страница 118: ...art Grid contacts Wires Smart Grid pulse meter 0 5 mm Wires low voltage Smart Grid contacts 0 5 mm 9 8 4 3 Benefit kWh power supply Smart grid 9 8 5 Smart grid operation mode 9 8 6 Allow electrical he...

Страница 119: ...rt grid operation mode 9 8 6 Allow electrical heaters 9 8 7 Enable room buffering 9 8 8 Limit setting kW The wiring of the Smart Grid in case of high voltage contacts is as follows S4S 3 4 X5M X5M 13...

Страница 120: ...s a b c d e K1A K2A X10M 2 4 K1A K2A Relays X10M Terminal block a Screws for X10M b Screws for K1A and K2A c Sticker to put on the high voltage wires d Wires between the relays and X5M AWG22 ORG e Wir...

Страница 121: ...cables with cable ties to the cable tie mountings If necessary bundle excessive cable length with a cable tie 9 3 12 To connect the WLAN cartridge delivered as accessory D Wireless gateway 1 Insert t...

Страница 122: ...9 Electrical installation Installer reference guide 122 EPRA14 18D ETVZ16S18 23E Daikin Altherma 3 H HT F 4P644739 1A 2022 03 Without low voltage cables With low voltage cables...

Страница 123: ...weather dependent curves 141 10 5 Settings menu 143 10 5 1 Malfunctioning 143 10 5 2 Room 144 10 5 3 Main zone 148 10 5 4 Additional zone 159 10 5 5 Space heating cooling 164 10 5 6 Tank 173 10 5 7 U...

Страница 124: ...hods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the bre...

Страница 125: ...be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user permission l...

Страница 126: ...ng the hydro software and EEPROM Prerequisite The EKPCCAB4 kit is required 1 Connect the USB connector of the cable to your PC 2 Connect the plug of the cable to X10A on A1P of the switch box of the i...

Страница 127: ...ettings 4187 Backup heater type 9 3 1 Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 10 5 5 Space heating cooling 4164 Glycol Filled system overview field setting E 0D 10 5 9 Installer set...

Страница 128: ...y 3 9 Setpoint mode 3 4 Heating WD curve 3 5 if applicable Cooling WD curve 3 6 if applicable Schedule 3 1 WD curve type 3 C read only Tank Heat up mode 5 6 10 5 6 Tank 4173 Comfort setpoint 5 2 Eco s...

Страница 129: ...j e2 l k1 k2 k3 45 d e1 g3 g2 h1 g1 f i2 i3 i4 h2 i1 a2 a1 e3 b c Possible actions on this screen Go through the list of the main menu Go to the main menu screen Enable disable breadcrumbs Item Descr...

Страница 130: ...n zone i1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Unit operation is decided...

Страница 131: ...on A malfunction occurred See 14 4 1 To display the help text in case of a malfunction 4243 for more information a If the corresponding operation for example space heating is not active the circle is...

Страница 132: ...e heating cooling Shows the applicable symbol of your unit Put the unit in heating mode or cooling mode You cannot change the mode on heating only models 5 Tank Set the domestic hot water tank tempera...

Страница 133: ...3 Additional zone screen 45 C 3 Additional zone 5 Tank temperature screen 50 C 5 Tank Explanation a1 d d e d e c a2 b1 b2 Possible actions on this screen Go through the list of the submenu Go to the...

Страница 134: ...The procedures to program other schedules are similar To program the schedule overview Example You want to program the following schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 Prerequisite The ro...

Страница 135: ...Sat Wed Fri Thu Tue Sun User defined 1 2 Select Delete Delete Rename Select 3 Select OK to confirm To clear the content of a day schedule 1 Select the day of which you want to clear the content For ex...

Страница 136: ...lear an action set its time as the time of the previous action 4 Confirm the changes Result The schedule for Monday is defined The value of the last action is valid until the next programmed action In...

Страница 137: ...his action for all other weekdays Mon Sat Wed Fri Thu Tue Sun User defined 1 C To program the schedule for Saturday and copy it to Sunday 1 Select Saturday 2 Select Edit 3 Use the left dial to select...

Страница 138: ...ndent if the desired leaving water or tank temperature is determined automatically by the outdoor temperature It therefore is connected to a temperature sensor on the North wall of the building If the...

Страница 139: ...e 10 4 4 Using weather dependent curves 4141 Availability The weather dependent curve is available for Main zone Heating Main zone Cooling Additional zone Heating Additional zone Cooling Tank only ava...

Страница 140: ...and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water for different ambient temperatures For e...

Страница 141: ...one heating Main zone or additional zone cooling Domestic hot water X1 X2 Examples of outdoor ambient temperature Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon...

Страница 142: ...nge the type for all zones main additional and for the tank go to 2 E Main zone WD curve type Viewing which type is selected is also possible via 3 C Additional zone WD curve type 5 E Tank WD curve ty...

Страница 143: ...ependent curve 2 points curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel Fine tune with setpoints At regular outdoor temperatures At cold out...

Страница 144: ...point screen Control the room temperature of the main zone via setpoint screen 1 Room See 10 3 5 Setpoint screen 4133 Schedule Indicate if the room temperature is controlled according to a schedule or...

Страница 145: ...ce heating cooling On Room thermostat control C 07 2 Allow for the dedicated Human Comfort Interface BRC1HHDA used as room thermostat to take care of room frost protection Set antifrost 1 4 1 Activati...

Страница 146: ...off However if 1 4 1 Antifrost is activated limited frost protection by the unit is possible In case of 1 leaving water temperature zone If Then Space heating cooling Off and Outdoor ambient temperatu...

Страница 147: ...nctionality is on 1 4 2 2 05 Room setpoint 4 C 16 C INFORMATION When the dedicated Human Comfort Interface BRC1HHDA used as room thermostat is disconnected because of incorrect wiring or damage of the...

Страница 148: ...thermostat Offset on the actual room temperature measured by the Human Comfort Interface 5 C 5 C step 0 5 C 1 7 2 09 Room sensor offset external room sensor option Only applicable if the external room...

Страница 149: ...n 2 Main zone See 10 3 5 Setpoint screen 4133 Schedule Indicate if the temperature of the leaving water is defined according to a schedule or not Influence of the LWT setpoint mode 2 4 is as follows I...

Страница 150: ...or heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Description 2...

Страница 151: ...zone Ta Outdoor temperature 1 00 Low outdoor ambient temperature 40 C 5 C 1 01 High outdoor ambient temperature 10 C 25 C 1 02 Desired leaving water temperature when the outdoor temperature equals or...

Страница 152: ...gher than 1 09 as for low outdoor temperatures less cold water is required 1 09 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 03 C...

Страница 153: ...n heating the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and...

Страница 154: ...sted to guarantee they are between the limits Always balance between the desired leaving water temperature with the desired room temperature and or the capacity according to the design and selection o...

Страница 155: ...t pump convector Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Code Description 2 9 C 07 0 Leavin...

Страница 156: ...eating for the main zone the target delta T temperature difference depends on the selected emitter type for the main zone Delta T is the absolute value of the temperature difference between the leavin...

Страница 157: ...ation of heat emitters in cooling mode 3 C 10 C Leaving water temperature Modulation Only applicable in case of room thermostat control When using the room thermostat functionality the customer needs...

Страница 158: ...o a higher position it cannot drop below the minimum setpoint See the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curve b Minimum leaving water temperature setpoint required to reach a...

Страница 159: ...alve closes when the unit is running in cooling operation mode Enable this setting to avoid cold leaving water through the heat emitter and the forming of condensation e g under floor heating loops or...

Страница 160: ...e for the additional zone via setpoint screen 3 Additional zone See 10 3 5 Setpoint screen 4133 Schedule Indicates if the desired leaving water temperature is according to a schedule See 10 5 3 Main z...

Страница 161: ...figure below 0 00 0 01 Ta Tt 0 03 0 02 Tt Target leaving water temperature additional zone Ta Outdoor temperature 0 03 Low outdoor ambient temperature 40 C 5 C 0 02 High outdoor ambient temperature 1...

Страница 162: ...erature 25 C 43 C 0 05 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 07 C 9 08 C Note This value should be higher than 0 04 as for...

Страница 163: ...ighest leaving water temperature in heating operation and the lowest leaving water temperature in cooling operation 3 8 1 9 05 Heating minimum 15 C 37 C 3 8 2 9 06 Heating maximum 2 0D 2 emitter type...

Страница 164: ...fixed to 10 C Else 3 C 10 C For E7 models If 2 0D 2 10 C 12 C Else 3 C 12 C 3 B 2 1 0E Delta T cooling A minimum temperature difference is required for the good operation of heat emitters in cooling m...

Страница 165: ...installed 1 Go to 4 Space heating cooling 2 Check if 4 1 Operation mode is listed and editable If so a heating cooling heat pump model is installed To tell the system which space operation to use you...

Страница 166: ...each month select an option Reversible Not restricted Heating only Restricted Cooling only Restricted 4 Confirm the changes Example Changeover restrictions When Restriction During cold season Example...

Страница 167: ...ting temperature Example A unit is configured as following Desired room temperature in heating mode 22 C Desired room temperature in cooling mode 24 C Hysteresis value 1 C Offset 4 C Changeover from h...

Страница 168: ...2 water temperature zones During configuration the number of water zones must be set Code Description 4 4 7 02 0 Single zone Only one leaving water temperature zone a b a Bypass b Main LWT zone 4 4 7...

Страница 169: ...e you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter Pump operation mode When the space heating cooling operation is OFF...

Страница 170: ...ONLY available in leaving water temperature control a b d e f c g b c a Space heating cooling control b Off c On d LWT temperature e Actual f Desired g Pump operation 4 5 F 0D 2 Request Pump operation...

Страница 171: ...s Value Description 0 No limitation 1 4 General limitation There is limitation in all conditions The required delta T control and comfort are NOT guaranteed 1 90 pump speed 2 80 pump speed 3 70 pump s...

Страница 172: ...abled the pump operation is possible at all outdoor temperatures Code Description 4 9 F 00 Pump operation 0 Disabled if outdoor temperature is higher than 4 02 or lower than F 01 depending on heating...

Страница 173: ...rops below the desired leaving water temperature Code Description 4 B 9 04 Overshoot 1 C 4 C Undershoot Restriction This function is only applicable in cooling mode during compressor startup It is NOT...

Страница 174: ...operation to immediately start heating up the water to the preset value Storage comfort However this consumes extra energy If powerful operation is active will be shown on the home screen To activate...

Страница 175: ...denotes the lower desired tank temperature It is the desired temperature when a storage economic action is scheduled preferably during day Code Description 5 3 6 0B Eco setpoint 30 C min 50 6 0E C Reh...

Страница 176: ...a schedule See the operation manual for more details Disinfection Applies only to installations with a domestic hot water tank The disinfection function disinfects the domestic hot water tank by perio...

Страница 177: ...by possible domestic hot water demand NOTICE Disinfection mode Even if you turn OFF tank heating operation C 3 Operation Tank disinfection mode will remain active However if you turn it OFF while disi...

Страница 178: ...rature drops below the reheat temperature minus the heat pump ON hysteresis temperature the tank heats up to the reheat temperature The minimum ON temperature is 20 C even if setpoint hysteresis is sm...

Страница 179: ...0B 0 0E 0 0D TDHW The desired tank temperature Ta The averaged outdoor ambient temperature 0 0E low outdoor ambient temperature 40 C 5 C 0 0D high outdoor ambient temperature 10 C 25 C 0 0C desired t...

Страница 180: ...eat pump temperature 6 01 THP MAX 6 01 t 6 00 HP 5 10 20 30 40 43 45 TU THP OFF THP MAX TDHW THP ON 50 HP Heat pump If heating up time by the heat pump takes too long auxiliary heating by the backup h...

Страница 181: ...nabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once the unit is initialised Holiday About holiday mode Du...

Страница 182: ...decrease the sound of the outdoor unit However this also decreases the heating cooling capacity of the system There are multiple quiet mode levels The installer can Completely deactivate quiet mode Ma...

Страница 183: ...ult The user or you can program the schedule in 7 4 2 Schedule For more information about scheduling see 10 3 7 Schedule screen Example 4134 You can configure restrictions in 7 4 4 Restrictions See be...

Страница 184: ...rice Only applicable in combination with the bivalent function See also Bivalent 4203 Code Description 7 5 1 N A Electricity price High 7 5 2 N A Electricity price Medium 7 5 3 N A Electricity price L...

Страница 185: ...n incentive per kWh renewable energy An incentive can be taken into account when setting the energy prices Although the running cost can increase the total operation cost taking into account the reimb...

Страница 186: ...ted in the submenu 8 Information Installer settings User settings Tank Commissioning 8 Information 8 1 Energy data 8 2 Malfunction history 8 3 Dealer information 8 4 Sensors 8 5 Actuators 8 6 Operatio...

Страница 187: ...Room tank or domestic hot water outside and leaving water temperature if applicable 8 5 Actuators Status mode of each actuator Example Domestic hot water pump ON OFF 8 6 Operation modes Current operat...

Страница 188: ...using the configuration wizard This way you can set the most important initial settings This way the unit will be able to run properly Afterwards more detailed settings can be done via the menu struc...

Страница 189: ...m a domestic hot water pump schedule to determine when to turn on and off the pump When turned on the pump runs and makes sure hot water is instantly available at the tap To save energy only turn on t...

Страница 190: ...if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0A 3 and emergency...

Страница 191: ...to your system when performing a space heating test run see 11 4 3 Operation test run 4221 depending on the actual water volume of the system Code Description 9 3 6 5 00 Equilibrium Deactivate backup...

Страница 192: ...n Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioning main menu scre...

Страница 193: ...led 1 enabled Glycol filled system Glycol Filled system This setting gives the installer the possibility to indicate whether the system is filled with glycol or water This is important in case glycol...

Страница 194: ...water temperature to be applied at low outdoor temperature when space heating priority is enabled The corrected higher setpoint will make sure that the total heat capacity of the water in the tank re...

Страница 195: ...here is a request for space heating or cooling If there is NO request for space heating cooling the tank is heated until the setpoint has been reached When Control Room thermostat This preset value is...

Страница 196: ...ich heaters are allowed to operate during preferential kWh rate power supply 0 No None 1 Only BSH Booster heater only 2 Only BUH Backup heater only 3 All All heaters See also below table Allowed heate...

Страница 197: ...unction 2 Closed The outdoor unit is connected to a preferential kWh rate power supply When the preferential kWh rate signal is sent by the electricity company the contact will close and the unit will...

Страница 198: ...nels The unit limits its power consumption during the Smart Grid s Recommended ON mode to only use the power provided by the photovoltaic panels However when the pulse meter is not available you can s...

Страница 199: ...oom only in case of room thermostat control or in the DHW tank instead of putting the photovoltaic panel energy on the grid In case of room buffering the room will heat up or cool down to the comfort...

Страница 200: ...ll be limited when the corresponding digital input asks 9 9 2 4 09 Type 0 Amp The limitation values are set in A 1 kW The limitation values are set in kW Limit when 9 9 1 Continuous and 9 9 2 Amp Code...

Страница 201: ...ce is set to Swedish NOTICE 2 weeks to change After you activated BBR16 you only have 2 weeks to change its settings BBR16 activation and BBR16 power limit After 2 weeks the unit freezes these setting...

Страница 202: ...sensor Code Description 9 B 1 C 08 External sensor When an optional external ambient sensor is connected the type of the sensor must be set 0 None NOT installed The thermistor in the dedicated Human...

Страница 203: ...selected time period Code Description 9 B 3 1 0A Averaging time 0 No averaging 1 12 hours 2 24 hours 3 48 hours 4 72 hours Bivalent Bivalent Only applicable in case of auxiliary boiler INFORMATION Bi...

Страница 204: ...tem calculates a value Tcalc which is variable between C 03 and C 03 C 04 TA Tcalc C 03 C 04 3 C C 03 a b TA Outdoor temperature Tcalc Bivalent ON temperature variable Below this temperature the auxil...

Страница 205: ...city price and gas price example both c kWh 2 Determine the value of C 03 using the graph For an example see the table legend 14 0 1 2 3 4 5 6 12 10 8 6 4 2 0 2 4 6 8 10 12 14 COP 10 5 b 2 5 a a C 03...

Страница 206: ...indoor unit error malfunctioning Low level errors caution warning will NOT be transmitted to alarm output 0 Abnormal The alarm output will be powered when an alarm occurs By setting this value a disti...

Страница 207: ...er demand The final decision to allow power interruption of the outdoor unit during standstill depends on the ambient temperature compressor conditions and minimum internal timers To enable the power...

Страница 208: ...be done using the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed in the field settings overview 9 I See To m...

Страница 209: ...A 2 Actuator test run A 3 Air purge A 4 UFH screed dryout About commissioning See 11 Commissioning 4215 10 5 11 User profile B User profile See To change the user permission level 4124 B User profile...

Страница 210: ...the submenu D Wireless gateway Malfunctioning Operation User profile Room D Wireless gateway D 1 Mode D 2 Reboot D 3 WPS D 4 Remove from cloud D 5 Home network connection D 6 Cloud connection About t...

Страница 211: ...www onlinecontroller daikineurope com Configuration To configure the ONECTA app follow the in app instructions While doing this the following actions and information are needed on the user interface M...

Страница 212: ...Home network connection Read out the status of the connection to the home network Code Description D 5 N A Home network connection Disconnected from WLAN_SSID Connected to WLAN_SSID Cloud connection...

Страница 213: ...setpoint 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4...

Страница 214: ...kWh power supply Benefit kWh power supply Smart grid operation mode Allow electrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard D...

Страница 215: ...software is equipped with protective functions such as room antifrost The unit automatically runs these functions when necessary During installation or service this behaviour is undesired Therefore t...

Страница 216: ...nstallation of the unit check the items listed below 2 Close the unit 3 Power up the unit You read the complete installation instructions as described in the installer reference guide The indoor unit...

Страница 217: ...me and flow rate in 8 1 Preparing water piping 473 To perform an air purge To perform a test run To perform an actuator test run Underfloor screed dryout function The underfloor screed dryout function...

Страница 218: ...talling the unit it is very important to remove all air in the water circuit When the air purge function is running the pump operates without actual operation of the unit and the removal of air in the...

Страница 219: ...e automatic air purge until you are sure that all air is removed from the system During air purge function pump speed limitation 9 0D is NOT applicable The air purge function automatically stops after...

Страница 220: ...elect Start air purge 5 Select OK to confirm Result The air purge starts It stops automatically when ready 6 During manual operation You can change the pump speed You must change the circuit To change...

Страница 221: ...in the logic to activate the backup heater see Equilibrium 4191 When part of the emitters are closed this might result in more frequent backup heater operation INFORMATION The test run only applies to...

Страница 222: ...ked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature infor...

Страница 223: ...rer for the maximum allowed water temperature to avoid cracking the screed programming the underfloor heating screed dryout schedule according to the initial heating instructions of the screed manufac...

Страница 224: ...e underfloor heating screed dryout function is active even if the user does NOT confirm emergency operation During underfloor heating screed dryout pump speed limitation 9 0D is NOT applicable NOTICE...

Страница 225: ...the total remaining time and the current desired leaving water temperature 2 Press the left dial to open the menu structure and to 1 View the status of sensors and actuators 2 Adjust the current prog...

Страница 226: ...03 2 You can read out the value here Stopped at the step where the underfloor screed dryout was stopped 3 Modify and restart the execution of the program a a If the UFH screed dryout program was stop...

Страница 227: ...g table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the comp...

Страница 228: ...is chapter 13 1 Maintenance safety precautions 228 13 2 Yearly maintenance 228 13 2 1 Yearly maintenance outdoor unit overview 228 13 2 2 Yearly maintenance outdoor unit instructions 229 13 2 3 Yearly...

Страница 229: ...ter NOTICE Handle the filter with care To prevent damage to the mesh of the filter do NOT use excessive force when you reinsert it 1 3 2 13 2 3 Yearly maintenance indoor unit overview Water pressure W...

Страница 230: ...t can be collected in a suitable container bottle sink 4 Open the drain valve for a couple of seconds c Result Water and dirt will come out 5 Close the drain valve 6 Screw the drain cap back on 7 Reat...

Страница 231: ...e hose Check whether the pressure relief valve hose is positioned appropriately to drain the water See 7 4 4 To connect the drain hose to the drain 472 Pressure relief valve of the domestic hot water...

Страница 232: ...chemical disinfection make sure water quality still complies with EU directive 2020 2184 13 3 To drain the domestic hot water tank DANGER RISK OF BURNING SCALDING The water in the tank can be very hot...

Страница 233: ...in a bottle sink using the installed drain hose 7 Remove the 2 clips that fix the water filter a b a a Clip b Magnetic filter dirt separator 8 Remove the water filter 9 Remove the drain hose from the...

Страница 234: ...ed up filter and strainer in the water filter housing INFORMATION Correctly install the strainer in the magnetic filter dirt separator housing using the protrusions a b c c a Rolled up filter b Strain...

Страница 235: ...ps to fix the water filter to the water circuit pipes 3 Make sure that the air purge valve of the water filter is in the open position 4 Open the valve if equipped of the water circuit towards the exp...

Страница 236: ...oise cavitation 240 14 3 7 Symptom The pressure relief valve opens 240 14 3 8 Symptom The water pressure relief valve leaks 241 14 3 9 Symptom The space is NOT sufficiently heated at low outdoor tempe...

Страница 237: ...ving problems based on symptoms 14 3 1 Symptom The unit is NOT heating or cooling as expected Possible causes Corrective action The temperature setting is NOT correct Check the temperature setting on...

Страница 238: ...can start If the backup heater doesn t start either check and make sure that The power supply to the backup heater is correctly wired The backup heater thermal protector is NOT activated The backup h...

Страница 239: ...t to be performed by the installer If you purge air from the heat emitters or collectors mind the following WARNING Air purging heat emitters or collectors Before you purge air from heat emitters or c...

Страница 240: ...s correct see 8 1 4 Changing the pre pressure of the expansion vessel 479 14 3 7 Symptom The pressure relief valve opens Possible causes Corrective action The expansion vessel is broken Replace the ex...

Страница 241: ...ctive action The backup heater operation is not activated Check the following The backup heater operation mode is enabled Go to 9 3 8 Installer settings Backup heater Operation 4 00 The backup heater...

Страница 242: ...Replace the pressure relief valve 14 3 11 Symptom Tank disinfection function is NOT completed correctly AH error Possible causes Corrective action The disinfection function was interrupted by domestic...

Страница 243: ...on the following will appear on the home screen depending on the severity Error Malfunction You can get a short and a long description of the malfunction as follows 1 Press the left dial to open the m...

Страница 244: ...at 8H 03 Overheating water circuit thermostat A1 00 Zero cross detection problem A5 00 OU High pressure peak cut freeze protection problem AA 01 Backup heater overheated or BUH power cable not connect...

Страница 245: ...H5 00 Malfunction of compressor overload protection H6 00 OU Malfunction of position detection sensor H8 00 OU Malfunction of compressor input CT system H9 00 OU Malfunction of outdoor air thermistor...

Страница 246: ...PJ 00 Capacity setting mismatch U0 00 OU Shortage of refrigerant U1 00 Malfunction by reverse phase open phase U2 00 OU Defect of power supply voltage U3 00 Underfloor heating screed dryout function...

Страница 247: ...rogram an Eco action 3 hours before the scheduled start up of the disinfection function to preheat the tank NOTICE When the minimum water flow is lower than described in the table below the unit will...

Страница 248: ...over refrigerant Make sure the valves Y1E Y3E Y2S Y3S Y4S are open If they are not open during refrigerant recovery refrigerant remains trapped in the unit a Y2S Y3S Y4S Y3E Y1E a Service port 5 16 fl...

Страница 249: ...pansion valves 4249 2 Recover refrigerant from the service port a 15 1 1 To manually open the electronic expansion valves Before recovering refrigerant make sure the electronic expansion valves are op...

Страница 250: ...3 EPRA14 18DAW1 H1P H7P 7 LEDs display BS1 BS4 Push buttons Operate the push buttons with an insulated stick such as a closed ballpoint pen to avoid touching of live parts To activate the recovery mod...

Страница 251: ...s To deactivate the recovery mode After recovering refrigerant deactivate the recovery mode as follows Procedure 7 LEDs display a H1P H2P H3P H4P H5P H6P H7P 1 Press and hold BS1 for 5 seconds 2 Press...

Страница 252: ...plicable A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authenti...

Страница 253: ...C D E HB HU HD 150 H U The symbols can be interpreted as follows A C Right side and left side obstacles walls baffle plates B Suction side obstacle wall baffle plate D Discharge side obstacle wall baf...

Страница 254: ...d Pinched pipe R5T Air heat exchanger middle e Refrigerant filter R6T Refrigerant liquid f One way valve R7T Compressor shell g Economiser heat exchanger R8T Compressor port h Service port 5 16 flare...

Страница 255: ...1 q Loose nut 1 b2 Space heating main mixed zone Water OUT screw connection 1 B1PW Space heating water pressure sensor c1 DHW Cold water IN screw connection 3 4 B2L Flow sensor c2 DHW Hot water OUT s...

Страница 256: ...tronic component assembly Electronic component assembly Front side view Front side view Indoor Indoor OFF OFF ON ON Outdoor Outdoor Position of compressor terminal Position of compressor terminal Posi...

Страница 257: ...g of the selector switch DS1 7 only for W1 models Ferrite core Z8C consists of 2 separate core parts Legend in case of V3 models A1P Printed circuit board main A2P Printed circuit board noise filter A...

Страница 258: ...ssor suction R4T Thermistor air heat exchanger distributor R5T Thermistor air heat exchanger middle R6T Thermistor refrigerant liquid R7T Thermistor compressor shell R8T Thermistor compressor port R9T...

Страница 259: ...E1HHEX Plate heat exchanger heater F1U Field fuse field supply F1U F7U A1P A2P Fuse H1P H7P A1P Light emitting diode service monitor is orange HAP A1P A2P Light emitting diode service monitor is gree...

Страница 260: ...11T Thermistor fin S1NPH High pressure sensor S1PH S2PH High pressure switch S1PL Low pressure switch T1A Current transfo V1R V2R A2P IGBT power module V3R A2P Diode module X1M X2M Terminal strip Y1E...

Страница 261: ...x Wiring depending on model PCB Note 1 Connection point of the power supply for the BUH should be foreseen outside the unit Note 1 Connection point of the power supply for the backup heater should be...

Страница 262: ...box Position in switch box Legend A1P Main PCB A2P ON OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A5P Bizone PCB A6P Current loop PCB A8P Demand PCB A11P Main PCB of t...

Страница 263: ...ackup heater power supply terminal strip X10M Smart Grid power supply terminal strip X X A J X H X Y Connector X M Terminal strip Optional Field supply Translation of text on wiring diagram English Tr...

Страница 264: ...upplied by PCB 230 V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgr...

Страница 265: ...etection voltage supplied by PCB Power limitation digital inputs 12 V DC 12 mA detection voltage supplied by PCB Space C H On OFF output Space cooling heating ON OFF output SWB Switch box 8 External O...

Страница 266: ...ion 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump convector main and or additional zone main X2...

Страница 267: ...40 45 50 55 60 65 10 C D A kPa E F1 F2 A External static pressure in the space heating cooling circuit B Water flow rate through the unit in the space heating cooling circuit C Operation range D Minim...

Страница 268: ...or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instruct...

Страница 269: ...Applicable indoor units ETVZ16S18E 6V ETVZ16S23E 6V ETVZ16S18E 9W ETVZ16S23E 9W Notes 1 6V 2 9W 3 Only applicable for models where cooling is possible 4 E model E 6V 9W 5 E7 model E 6V7 9W7 A B C Z 1...

Страница 270: ...step 1 C 55 C 2 8 3 9 03 R W 5 18 C step 1 C 7 C 3 2 8 4 9 02 R W 18 22 C step 1 C 22 C 3 Main zone 2 9 C 07 R W 0 LWT control 1 Ext RT control 2 RT control 2 A C 05 R W 0 1 1 contact 2 2 contacts Del...

Страница 271: ...C step 1 C 35 C 4 3 2 F 01 R W 10 35 C step 1 C 20 C 3 Space heating cooling 4 4 7 02 R W 0 1 LWT zone 1 2 LWT zones 4 5 F 0D R W 0 Continuous 1 Sample 2 Request 4 6 E 02 R W 3 R O 0 Reversible 3 1 He...

Страница 272: ...ep 1 C 2 C 5 E R O 0 2 points 1 Slope Offset User settings Quiet 7 4 1 R W 0 OFF 1 Manual 2 Automatic 7 4 3 R W 0 Quiet 1 More Quiet 2 Most Quiet Electricity price 7 5 1 R W 0 00 990 kWh 1 kWh 7 5 2 R...

Страница 273: ...1 C 20 C 3 Tank 9 1 B 1 6 0D R W 0 Reheat only 1 Reheat sched 2 Scheduled only 9 1 B 2 6 0A R W 30 6 0E C step 1 C 60 C 9 1 B 3 6 0B R W 30 min 50 6 0E C step 1 C 45 C 9 1 B 4 6 0C R W 30 min 50 6 0E...

Страница 274: ...aller settings 9 7 4 04 R W 0 Intermittent 1 Continuous 2 Off Benefit kWh power supply 9 8 2 D 00 R W 0 None 1 BSH only 2 BUH only 3 All heaters 9 8 3 D 05 R W 0 Forced off 1 As normal 9 8 4 D 01 R W...

Страница 275: ...1 C 22 C 3 9 I 0 06 R W 25 43 C step 1 C 35 C 3 9 I 0 07 R W 10 25 C step 1 C 20 C 3 9 I 0 0B R W 35 6 0E C step 1 C 55 C 9 I 0 0C R W 45 6 0E C step 1 C 4 Min 45 6 0E 6 0E C step 1 C 5 60 C 9 I 0 0D...

Страница 276: ...What is the maximum desired room temperature in heating What is the mimimum desired room temperature in heating What is the maximum desired room temperature in cooling What is the minimum desired room...

Страница 277: ...duled only 9 I 6 0E R W 40 65 C step 1 C 65 C 9 I 7 00 R W 0 4 C step 1 C 0 C 9 I 7 01 R W 2 40 C step 1 C 2 C Domestic hot water booster heater hysteresis What is the desired comfort storage temperat...

Страница 278: ...9 I C 00 R O 0 Solar priority 1 Heat pump priority 9 I C 01 0 9 I C 02 R W 0 No 1 Bivalent 9 I C 03 R W 25 25 C step 1 C 0 C Is an external backup heat source connected Bivalent activation temperature...

Страница 279: ...I E 05 R O 0 No 1 Yes 9 I E 06 1 9 I E 07 R O 1 Integrated 9 I E 08 R W 0 disabled 1 Enabled 9 I E 09 1 9 I E 0B R O 1 Yes 9 I E 0C 0 9 I E 0D R W 0 No 1 Yes 9 I E 0E 0 9 I F 00 R W 0 Disabled 1 Enab...

Страница 280: ...ith default value 9 I F 0A 0 9 I F 0B R W 0 No 1 Yes 9 I F 0C R W 0 No 1 Yes 9 I F 0D R W 0 Continuous 1 Sample 2 Request What is the pump operation mode Close shut off valve during thermo OFF Close s...

Страница 281: ......

Страница 282: ......

Страница 283: ......

Страница 284: ...4P644739 1A 2022 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...