background image

10 Technical data

Installation manual

34

ETVH/23E

Daikin Altherma 3 H HT F

4P644728-1D – 2022.08

Notes to go through before starting the unit

English

Translation

Notes to go through before
starting the unit

Notes to go through before
starting the unit

X1M

Main terminal

X2M

Field wiring terminal for AC

X5M

Field wiring terminal for DC

X6M

Backup heater power supply
terminal

X10M

Smart Grid terminal

Earth wiring

Field supply

1

Several wiring possibilities

Option

Not mounted in switch box

Wiring depending on model

PCB

Note 1: Connection point of the
power supply for the BUH
should be foreseen outside the
unit.

Note 1: Connection point of the
power supply for the backup
heater should be foreseen outside
the unit.

Backup heater power supply

Backup heater power supply

 6T1 (3~, 230 V, 6 kW)

 6T1 (3~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6V3 (1N~, 230 V, 6 kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

 6WN/9WN (3N~, 400 V, 6/9

kW)

User installed options

User installed options

 Remote user interface

 Dedicated Human Comfort

Interface (BRC1HHDA used as
room thermostat)

 Ext. indoor thermistor

 External indoor thermistor

 Ext outdoor thermistor

 External outdoor thermistor

 Digital I/O PCB

 Digital I/O PCB

 Demand PCB

 Demand PCB

 Safety thermostat

 Safety thermostat

 Smart Grid

 Smart Grid

 WLAN module

 WLAN module

 WLAN cartridge

 WLAN cartridge

 Bizone mixing kit

 Bizone mixing kit

Main LWT

Main leaving water temperature

 On/OFF thermostat (wired)

 ON/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 ON/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Add LWT

Additional leaving water
temperature

 On/OFF thermostat (wired)

 ON/OFF thermostat (wired)

 On/OFF thermostat (wireless)

 ON/OFF thermostat (wireless)

 Ext. thermistor

 External thermistor

 Heat pump convector

 Heat pump convector

Position in switch box

English

Translation

Position in switch box

Position in switch box

Legend

A1P

Main PCB

A2P

* ON/OFF thermostat (PC=power circuit)

A3P

* Heat pump convector

A4P

* Digital I/O PCB

A8P

* Demand PCB

A11P

Main PCB of the MMI (= user interface of the
indoor unit)

A14P

* PCB of the dedicated Human Comfort

Interface (BRC1HHDA used as room
thermostat)

A15P

* Receiver PCB (wireless ON/OFF

thermostat)

A20P

* WLAN module

A30P

* Bizone mixing kit PCB

CN* (A4P)

* Connector

DS1 (A8P)

* DIP switch

F1B

# Overcurrent fuse backup heater

F1U, F2U (A4P)

* Fuse 5 A 250 V for digital I/O PCB

K1A, K2A

* High voltage Smart Grid relay

K1M, K2M

Contactor backup heater

K5M

Safety contactor backup heater

K*R (A1P-A4P)

Relay on PCB

M2P

# Domestic hot water pump

M2S

# 2-way valve for cooling mode

PC (A15P)

* Power circuit

PHC1 (A4P)

* Optocoupler input circuit

Q1L

Thermal protector backup heater

Q4L

# Safety thermostat

Q*DI

# Earth leakage circuit breaker

R1H (A2P)

* Humidity sensor

R1T (A2P)

* Ambient sensor ON/OFF thermostat

R2T (A2P)

* External sensor (floor or ambient)

R6T

* External indoor or outdoor ambient

thermistor

S1S

# Preferential kWh rate power supply contact

S2S

# Electrical meter pulse input 1

S3S

# Electrical meter pulse input 2

S4S

# Smart Grid feed-in

S6S~S9S

* Digital power limitation inputs

S10S-S11S

# Low voltage Smart Grid contact

SS1 (A4P)

* Selector switch

TR1

Power supply transformer

X6M

# Backup heater power supply terminal strip

X10M

* Smart Grid power supply terminal strip

X*, X*A, J*, X*H*,
X*Y

Connector

X*M

Terminal strip

*

Optional

#

Field supply

Translation of text on wiring diagram

English

Translation

(1) Main power connection

(1) Main power connection

For HP tariff

For heat pump tariff

Indoor unit supplied from outdoor Indoor unit supplied from outdoor

Normal kWh rate power supply

Normal kWh rate power supply

Only for normal power supply
(standard)

Only for normal power supply
(standard)

Only for preferential kWh rate
power supply (outdoor)

Only for preferential kWh rate
power supply (outdoor)

Содержание ETVX16E6V7

Страница 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Страница 2: ...e 21 7 2 3 Configuration wizard System 21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 23 7 2 6 Configuration wizard Additional zone 24 7 2 7 Configuration wizard T...

Страница 3: ...the instructions from this manual See 5 Piping installation 47 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Страница 4: ...omestic hot water circuit j Sealing tape for low voltage wiring intake 3 1 2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit b a a b a Handles at the back of...

Страница 5: ...he cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Страница 6: ...pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into pos...

Страница 7: ...piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the o...

Страница 8: ...lve between the pressure relief valve field supply and the DHW tank NOTICE A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domestic cold...

Страница 9: ...system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks m...

Страница 10: ...r tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 2 6 To insu...

Страница 11: ...ent Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional...

Страница 12: ...see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable mai...

Страница 13: ...ackup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 6 kW 1N 230 V a 26 A b c 0 22 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d...

Страница 14: ...all a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 2 D Shut off va...

Страница 15: ...door unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below A 1 M M2P B A...

Страница 16: ...illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y2 7 B A B 7 9 X2M A4P...

Страница 17: ...puts cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ti...

Страница 18: ...acts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Forced on The use of a Smart Grid pulse meter i...

Страница 19: ...2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factory...

Страница 20: ...izard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to In...

Страница 21: ...rview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applie...

Страница 22: ...periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION The auto emergency setting can be set in the menu stru...

Страница 23: ...change one check if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0...

Страница 24: ...endent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT se...

Страница 25: ...ing reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage co...

Страница 26: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Страница 27: ...the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curv...

Страница 28: ...644728 1D 2022 08 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Страница 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Страница 30: ...ring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply pa...

Страница 31: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe t...

Страница 32: ...fter the first 12 hours of power on manually disable room frost protection by setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking o...

Страница 33: ...d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 m Shut off valve recommended n Non ret...

Страница 34: ...eat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P ON OFF thermostat PC power circuit A3P Heat pump convector A4P Digit...

Страница 35: ...Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat conta...

Страница 36: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P644728 1D 2022 08 Copyright 2021 Daikin 4P644728 1 D 00000004 Verantwortung f r Energie und Umwelt...

Отзывы: