6 Configuration

Installation manual

22

ETVH/9W(G)

Daikin Altherma 3 H HT F

4P586454-1B – 2020.01

Comfort setpoint

Only  applicable  when  domestic  hot  water  preparation  is 

Schedule

only

 or 

Sc reheat

. When programming the schedule, you

can make use of the comfort setpoint as a preset value. When you
later  want  to  change  the  storage  setpoint,  you  only  have  to  do  it  in
one place.

The  tank  will  heat  up  until  the 

storage  comfort  temperature

  has

been  reached.  It  is  the  higher  desired  temperature  when  a  storage
comfort action is scheduled.

Additionally, a storage stop can be programmed. This feature puts a
stop  to  tank  heating  even  if  the  setpoint  has  NOT  been  reached.
Only  program  a  storage  stop  when  tank  heating  is  absolutely
undesirable.

#

Code

Description

[5.2]

[6-0A]

Comfort setpoint

:

▪ 30°C~[6‑0E]°C

Eco setpoint

The 

storage  economic  temperature

  denotes  the  lower  desired

tank  temperature.  It  is  the  desired  temperature  when  a  storage
economic action is scheduled (preferably during day).

#

Code

Description

[5.3]

[6-0B]

Eco setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Reheat setpoint

Desired reheat tank temperature

, used:

▪ in 

Schedule 

reheat

  mode,  during  reheat  mode:  the

guaranteed  minimum  tank  temperature  is  set  by  the 

Reheat

setpoint

  minus  the  reheat  hysteresis.  If  the  tank  temperature

drops below this value, the tank is heated up.

▪ during  storage  comfort,  to  prioritize  the  domestic  hot  water

preparation.  When  the  tank  temperature  rises  above  this  value,
domestic  hot  water  preparation  and  space  heating/cooling  are
executed sequentially.

#

Code

Description

[5.4]

[6-0C]

Reheat setpoint

:

▪ 30°C~min(50,[6‑0E])°C

6.3

Weather-dependent curve

6.3.1

What is a weather-dependent curve?

Weather-dependent operation

The unit operates 'weather dependent' if the desired leaving water or
tank  temperature  is  determined  automatically  by  the  outdoor
temperature.  It  therefore  is  connected  to  a  temperature  sensor  on
the  North  wall  of  the  building.  If  the  outdoor  temperature  drops  or
rises, the unit compensates instantly. Thus, the unit does not have to
wait  for  feedback  by  the  thermostat  to  increase  or  decrease  the
temperature  of  the  leaving  water  or  tank.  Because  it  reacts  more
quickly,  it  prevents  high  rises  and  drops  of  the  indoor  temperature
and water temperature at tap points.

Advantage

Weather-dependent operation reduces energy consumption.

Weather-dependent curve

To  be  able  to  compensate  for  differences  in  temperature,  the  unit
relies on its weather-dependent curve. This curve defines how much
the  temperature  of  the  tank  or  leaving  water  must  be  at  different
outdoor  temperatures.  Because  the  slope  of  the  curve  depends  on
local circumstances such as climate and the insulation of the house,
the curve can be adjusted by an installer or user.

Types of weather-dependent curve

There are 2 types of weather-dependent curves:

▪ 2-points curve

▪ Slope-offset curve

Which type of curve you use to make adjustments, depends on your
personal  preference.  See 

"6.3.4  Using  weather-dependent

curves" 

[

4

 23].

Availability

The weather-dependent curve is available for:

▪ Main zone - Heating

▪ Main zone - Cooling

▪ Additional zone - Heating

▪ Additional zone - Cooling

▪ Tank

INFORMATION

To  operate  weather  dependent,  correctly  configure  the
setpoint  of  the  main  zone,  additional  zone  or  tank.  See

"6.3.4 Using weather-dependent curves" 

[

4

 23].

6.3.2

2-points curve

Define the weather-dependent curve with these two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Example

Y1

Y2

X1

X2

a

Item

Description

a

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Domestic hot water tank

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

Содержание ETVH-D9WG

Страница 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETVX16S18DA9W G ETVX16S23DA9W G htt...

Страница 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Страница 3: ...ckup heater 20 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 21 6 2 7 Configuration wizard Tank 21 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent...

Страница 4: ...ddendum book for optional equipment e Indoor unit installation manual f Operation manual g Sealing rings for shut off valves space heating water circuit h Sealing rings for field supplied shut off val...

Страница 5: ...e hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 3 Remov...

Страница 6: ...the pallet and place it on the floor Also see 2 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 3 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into...

Страница 7: ...does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if al...

Страница 8: ...guide that include the activation of pump in case of low temperatures However in case of a power failure these functions cannot guarantee protection Do one of the following to protect the water circu...

Страница 9: ...lycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to the water you can use...

Страница 10: ...option EKRELAY1 Addendum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat type 3 9 rea...

Страница 11: ...erface make sure to set 2 9 2 Control Room thermostat Domestic hot water settings To allow for energy buffering in the domestic hot water tank on the user interface make sure to set 9 2 1 4 Domestic h...

Страница 12: ...rthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the...

Страница 13: ...h box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 5 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone an...

Страница 14: ...he cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open th...

Страница 15: ...h box cover 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wi...

Страница 16: ...nsumption digital inputs cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the...

Страница 17: ...6 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more detaile...

Страница 18: ...ost settings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the u...

Страница 19: ...pe antifreeze function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configurat...

Страница 20: ...higher than 50 C Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the domestic hot water tank Capacity ste...

Страница 21: ...reset or custom Code Description 2 1 N A 0 No 1 Yes 6 2 6 Configuration wizard Additional zone The most important settings for the additional leaving water zone can be set here Emitter type For more i...

Страница 22: ...re sensor on the North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or d...

Страница 23: ...cooling Domestic hot water X1 X2 Examples of outdoor ambient temperature Item Description Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat...

Страница 24: ...OK Hot Cold Hot Hot a See 6 3 2 2 points curve 422 6 4 Settings menu You can set additional settings using the main menu screen and its submenus The most important settings are presented here 6 4 1 Ma...

Страница 25: ...g 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Lim...

Страница 26: ...local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor...

Страница 27: ...fferent actuators For example when you select Pump a test run of the pump will start 1 Set the user permission level to Installer See To change the user permission level 418 2 Go to A 2 Commissioning...

Страница 28: ...sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to...

Страница 29: ...A Indoor unit B Field installed a1 Space heating water IN a2 Space heating water OUT b1 Domestic hot water cold water IN loose nut 3 4 b2 Domestic hot water hot water OUT loose nut 3 4 c1 Water IN co...

Страница 30: ...ired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation...

Страница 31: ...rmostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PC...

Страница 32: ...core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Co...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...4P586454 1B 2020 01 Copyright 2019 Daikin 4P586454 1 B 00000003 Verantwortung f r Energie und Umwelt...

Отзывы: