6 Configuration

Installation manual

21

ETVH/9W(G)
Daikin Altherma 3 H HT F
4P586454-1B – 2020.01

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

6.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"6.2.5  Configuration

wizard: Main zone" 

[

4

 20].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"6.2.5 Configuration wizard: Main zone" 

[

4

 20].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"6.2.5  Configuration

wizard: Main zone" 

[

4

 20].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent curves. Also see 

"6.3 Weather-dependent curve" 

[

4

 22].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"6.2.5 Configuration wizard: Main zone" 

[

4

 20].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

6.2.7

Configuration wizard: Tank

INFORMATION

To make tank defrost possible, we recommend a minimum
tank temperature of 35°C.

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

#

Code

Description

[5.6]

[6-0D]

Heat up mode

:

▪ 0: 

Reheat 

only

:  Only  reheat

operation is allowed.

▪ 1: 

Sc reheat

: The domestic

hot water tank is heated according to a
schedule  and  between  the  scheduled
heat  up  cycles,  reheat  operation  is
allowed.

▪ 2: 

Schedule  only

:  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

See the operation manual for more details.

Содержание ETVH-D9WG

Страница 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETVX16S18DA9W G ETVX16S23DA9W G htt...

Страница 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Страница 3: ...ckup heater 20 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 21 6 2 7 Configuration wizard Tank 21 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent...

Страница 4: ...ddendum book for optional equipment e Indoor unit installation manual f Operation manual g Sealing rings for shut off valves space heating water circuit h Sealing rings for field supplied shut off val...

Страница 5: ...e hinges at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 3 Remov...

Страница 6: ...the pallet and place it on the floor Also see 2 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 3 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into...

Страница 7: ...does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if al...

Страница 8: ...guide that include the activation of pump in case of low temperatures However in case of a power failure these functions cannot guarantee protection Do one of the following to protect the water circu...

Страница 9: ...lycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to the water you can use...

Страница 10: ...option EKRELAY1 Addendum book for optional equipment Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat type 3 9 rea...

Страница 11: ...erface make sure to set 2 9 2 Control Room thermostat Domestic hot water settings To allow for energy buffering in the domestic hot water tank on the user interface make sure to set 9 2 1 4 Domestic h...

Страница 12: ...rthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the...

Страница 13: ...h box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 5 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zone an...

Страница 14: ...he cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open th...

Страница 15: ...h box cover 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wi...

Страница 16: ...nsumption digital inputs cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the...

Страница 17: ...6 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed NOTICE This chapter explains only the basic configuration For more detaile...

Страница 18: ...ost settings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the u...

Страница 19: ...pe antifreeze function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configurat...

Страница 20: ...higher than 50 C Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the domestic hot water tank Capacity ste...

Страница 21: ...reset or custom Code Description 2 1 N A 0 No 1 Yes 6 2 6 Configuration wizard Additional zone The most important settings for the additional leaving water zone can be set here Emitter type For more i...

Страница 22: ...re sensor on the North wall of the building If the outdoor temperature drops or rises the unit compensates instantly Thus the unit does not have to wait for feedback by the thermostat to increase or d...

Страница 23: ...cooling Domestic hot water X1 X2 Examples of outdoor ambient temperature Item Description Y1 Y2 Y3 Y4 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat...

Страница 24: ...OK Hot Cold Hot Hot a See 6 3 2 2 points curve 422 6 4 Settings menu You can set additional settings using the main menu screen and its submenus The most important settings are presented here 6 4 1 Ma...

Страница 25: ...g 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Lim...

Страница 26: ...local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor...

Страница 27: ...fferent actuators For example when you select Pump a test run of the pump will start 1 Set the user permission level to Installer See To change the user permission level 418 2 Go to A 2 Commissioning...

Страница 28: ...sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to...

Страница 29: ...A Indoor unit B Field installed a1 Space heating water IN a2 Space heating water OUT b1 Domestic hot water cold water IN loose nut 3 4 b2 Domestic hot water hot water OUT loose nut 3 4 c1 Water IN co...

Страница 30: ...ired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation...

Страница 31: ...rmostat For safety thermostat Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PC...

Страница 32: ...core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Co...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...4P586454 1B 2020 01 Copyright 2019 Daikin 4P586454 1 B 00000003 Verantwortung f r Energie und Umwelt...

Отзывы: