3/19
Breadcrumb
Setting name
Range, step
Default value
Field settings table
2.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
2.8.1
[9-01]
R/W
15~37°C, step: 1°C
25°C
2.8.2
[9-00]
R/W ([2-
0C]
≠
2)
R/O ([2-
0C] = 2)
[2-0C]=2:
37~70, step: 1°C
70°C
[2-0C]
≠
2:
37~55, step: 1°C
55°C
2.8.3
[9-03]
R/W
5~18°C, step: 1°C
7°C
2.8.4
[9-02]
R/W
18~22°C, step: 1°C
22°C
Main zone
2.9
[C-07]
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
2.A
[C-05]
R/W
1: 1 contact
2: 2 contacts
└─
Delta T
2.B.1
[1-0B]
R/W(*10)
[2-0D]=2
R/O (*9)
3~10°C, step: 1°C (*9)
[2-0C]
≠
2 (Radiator)
3~12°C, step: 1°C (*10)
5°C
[2-0C] = 2 (Radiator)
10~12°C, step: 1°C (*10)
10°C
2.B.2
[1-0D]
R/W
3~10°C, step: 1°C
5°C
└─
Modulation
2.C.1
[8-05]
R/W
0: No
1: Yes
2.C.2
[8-06]
R/W
0~10°C, step: 1°C
5°C
└─
Shut off valve
2.D.1
[F-0B]
R/W
0: No
1: Yes
2.D.2
[F-0C]
R/W
0: No (*10)
1: Yes (*9)
Main zone
2.E
R/W
0: 2-points
1: Slope-Offset
Additional zone
3.4
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
└─
Heating WD curve
3.5
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
3.5
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
During cooling
WD curve type
Setpoint mode
Leaving water value for high ambient temp. for LWT add zone
heating WD curve.
Leaving water value for low ambient temp. for LWT add zone
heating WD curve.
Ext Thermostat type
Delta T heating
Delta T cooling
Modulation
Max modulation
During thermo
Cooling minimum
Cooling maximum
Control
Heating minimum
Emitter type
Heating maximum
(*1) *X*_(*2) *H*_(*3) *B*_(*4) *EKECBUA*3V_
(*5) *EKECBUA*6V_(*6) *EKECBUA*9W_(*7) BUH less_
(*8) 300L tank_(*9) E_(*10) E7