7 Configuration

Installation manual

29

ETBH/X16E
Daikin Altherma 3 H HT W
4P644727-1B – 2022.03

Item

Description

Y1, Y2,

Y3, Y4

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Domestic hot water tank

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

7.3.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Main zone – Heating

[2.4] 

Main zone

 > 

Setpoint

mode

WD heating, fixed cooling

OR 

Weather dependent

Main zone – Cooling

[2.4] 

Main zone

 > 

Setpoint

mode

Weather dependent

Additional zone – Heating

[3.4] 

Additional zone

 >

Setpoint mode

WD heating, fixed cooling

OR 

Weather dependent

Additional zone – Cooling

[3.4] 

Additional zone

 >

Setpoint mode

Weather dependent

Tank

[5.B] 

Tank

 > 

Setpoint mode

Restriction: 

Only available to

installers.

Weather dependent

To change the type of weather-dependent curve

To change the type for all zones (main + additional) and for the tank,
go to [2.E] 

Main zone

 > 

WD curve type

.

Viewing which type is selected is also possible via:

▪ [3.C] 

Additional zone

 > 

WD curve type

▪ [5.E] 

Tank

 > 

WD curve type

Restriction: 

Only available to installers.

To change the weather-dependent curve

Zone

Go to …

Main zone – Heating

[2.5] 

Main zone

 > 

Heating WD

curve

Main zone – Cooling

[2.6] 

Main zone

 > 

Cooling WD

curve

Additional zone – Heating

[3.5] 

Additional zone

 >

Heating WD curve

Additional zone – Cooling

[3.6] 

Additional zone

 >

Cooling WD curve

Zone

Go to …

Tank

Restriction: 

Only available to

installers.

[5.C] 

Tank

 > 

WD curve

INFORMATION

Maximum and minimum setpoints

You cannot configure the curve with temperatures that are
higher  or  lower  than  the  set  maximum  and  minimum
setpoints for that zone or for the tank. When the maximum
or minimum setpoint is reached, the curve flattens out.

To fine-tune the weather-dependent curve: slope-offset curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

To fine-tune the weather-dependent curve: 2-points curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with

setpoints:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Y2

(a)

Y1

(a)

X1

(a)

X2

(a)

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

(a)

See 

"7.3.2 2-points curve"

 [

4

 28].

7.4

Settings menu

You can set additional settings using the main menu screen and its
submenus. The most important settings are presented here.

7.4.1

Main zone

Ext thermostat type

Only applicable in external room thermostat control.

NOTICE

If  an  external  room  thermostat  is  used,  the  external  room
thermostat will control the room frost protection. However,
the  room  frost  protection  is  only  possible  if  [C.2] 

Space

heating/cooling

=

On

.

Содержание ETBH16E 6V Series

Страница 1: ...Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16E 6V ETBH16E 9W ETBX16E 6V ETBX16E 9W A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Страница 2: ...e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama megfelelnek az al bbi ir nyelv ek nek...

Страница 3: ...regulation s provided that the products are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility...

Страница 4: ...er 25 7 2 5 Configuration wizard Main zone 25 7 2 6 Configuration wizard Additional zone 26 7 2 7 Configuration wizard Tank 27 7 3 Weather dependent curve 27 7 3 1 What is a weather dependent curve 27...

Страница 5: ...WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING D...

Страница 6: ...anual e WLAN cartridge f Sealing ring for shut off valve g Shut off valve h Overpressure bypass valve i Wall bracket 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site req...

Страница 7: ...the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interface...

Страница 8: ...in hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Connect...

Страница 9: ...er interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guarante...

Страница 10: ...ct the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system be...

Страница 11: ...e set to 1 If the glycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to th...

Страница 12: ...y 421 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Ext thermostat type For the additional zone 3 A Ext thermostat ty...

Страница 13: ...nstaller reference guide Use the cable delivered with the WLAN module D Wireless gateway Bizone kit See Installation manual of the bizone kit Addendum book for optional equipment Use the cable deliver...

Страница 14: ...y of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rat...

Страница 15: ...terface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if nec...

Страница 16: ...open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per me...

Страница 17: ...tion below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required B C A A 7 Y1 C B X2M X2M A4P A4P a 7 9 Y1 YC X1M a Insta...

Страница 18: ...open the indoor unit 47 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below B C...

Страница 19: ...5M X5M 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessar...

Страница 20: ...Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high...

Страница 21: ...Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid conta...

Страница 22: ...staller settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column...

Страница 23: ...INFORMATION By default daylight savings time is enabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once the...

Страница 24: ...reduced DHW off if the house is unattended for longer periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION T...

Страница 25: ...h Code Description 9 3 2 5 0D 0 230V 1ph 1 230V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup heat...

Страница 26: ...outdoor ambient temperature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient te...

Страница 27: ...stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoi...

Страница 28: ...o the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decr...

Страница 29: ...er dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional...

Страница 30: ...acts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Ext thermostat type Only applicable in external room thermostat control For mor...

Страница 31: ...perature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext...

Страница 32: ...door unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indo...

Страница 33: ...or leaving water and tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic h...

Страница 34: ...6 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sur...

Страница 35: ...diagram Indoor unit 3D120613B R2T R1T B1PW B2L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Страница 36: ...rmostat wired On OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF therm...

Страница 37: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Страница 38: ...luded A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR1 wireless room thermostat Only for KRTRB wireless room thermostat Only for KRTW wired room thermostat 5 core for C H oper...

Страница 39: ......

Страница 40: ...4P644727 1B 2022 03 Copyright 2021 Daikin 4P644727 1 B 00000001 Verantwortung f r Energie und Umwelt...

Отзывы: