6 Configuration

Installation manual

17

ETBH/9W
Daikin Altherma 3 H HT W
4P586453-1C – 2020.10

B

C

A

A

10

Q4L

9

C

B

9

10

X5M

X5M

3

Fix the cable with cable ties to the cable tie mountings.

NOTICE

Make  sure  to  select  and  install  the  safety  thermostat
according to the applicable legislation.

In  any  case,  to  prevent  unnecessary  tripping  of  the  safety
thermostat, we recommend the following:

▪ The safety thermostat is automatically resettable.

▪ The  safety  thermostat  has  a  maximum  temperature

variation rate of 2°C/min.

▪ There is a minimum distance of 2 m between the safety

thermostat  and  the  motorized  3‑way  valve  delivered
with the domestic hot water tank.

INFORMATION

ALWAYS  configure  the  safety  thermostat  after  it  is
installed.  Without  configuration,  the  unit  will  ignore  the
safety thermostat contact.

INFORMATION

The  preferential  kWh  rate  power  supply  contact  is
connected to the same terminals (X5M/9+10) as the safety
thermostat.  Thus,  the  system  can  have  EITHER
preferential  kWh  rate  power  supply  OR  a  safety
thermostat.

6

Configuration

INFORMATION

Cooling is only applicable in case of:

▪ Reversible models

▪ Heating only conversion kit (EKHBCONV)

6.1

Overview: Configuration

This  chapter  describes  what  you  have  to  do  and  know  to  configure
the system after it is installed.

NOTICE

This  chapter  explains  only  the  basic  configuration.  For
more  detailed  explanation  and  background  information,
see the installer reference guide.

Why

If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:

▪ The calculations of the software

▪ What you can see on and do with the user interface

How

You can configure the system via the user interface.

First  time  –  Configuration  wizard.

  When  you  turn  ON  the  user

interface  for  the  first  time  (via  the  unit),  the  configuration  wizard
starts to help you configure the system.

Restart  the  configuration  wizard.

  If  the  system  is  already

configured, you can restart the configuration wizard. To restart the
configuration 

wizard, 

go 

to 

Installer 

settings

 

>

Configuration  wizard

.  To  access 

Installer  settings

,  see

"6.1.1 To access the most used commands"

 [

4

 17].

Afterwards.

  If  necessary,  you  can  make  changes  to  the

configuration in the menu structure or the overview settings.

INFORMATION

When  the  configuration  wizard  is  finished,  the  user
interface  will  show  an  overview  screen  and  request  to
confirm.  When  confirmed,  the  system  will  restart  and  the
home screen will be displayed.

Accessing settings – Legend for tables

You  can  access  the  installer  settings  using  two  different  methods.
However,  NOT  all  settings  are  accessible  via  both  methods.  If  so,
the  corresponding  table  columns  in  this  chapter  are  set  to  N/A  (not
applicable).

Method

Column in tables

Accessing settings via the breadcrumb in the

home menu screen

 or the 

menu structure

.

To enable breadcrumbs, press the   button
in the home screen.

#

For example: [2.9]

Accessing settings via the code in the

overview field settings

.

Code

For example: [C-07]

See also:

"To access the installer settings"

 [

4

 18]

"6.5 Menu structure: Overview installer settings"

 [

4

 26]

6.1.1

To access the most used commands

To change the user permission level

You can change the user permission level as follows:

Содержание ETBH16DF6V

Страница 1: ...Installation manual Daikin Altherma 3 H HT W English https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W ETBH16DF6V ETBH16DF9W ETBX16DF6V ETBX16DF9W...

Страница 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Страница 3: ...Additional zone 21 6 2 7 Configuration wizard Tank 22 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent curve 22 6 3 2 2 points curve 23 6 3 3 Slope offset curve 23 6 3 4 Using weather...

Страница 4: ...g 1 h a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut off valve f Shut off valve g Overpressure bypass...

Страница 5: ...box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user i...

Страница 6: ...en the switch box See 3 2 1 To open the indoor unit 45 Fix the unit to the wall with an 8 mm screw 3 3 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected...

Страница 7: ...anger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be guaranteed NOTICE Con...

Страница 8: ...he glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to air Leaving the cap off the glycol container causes the concentrat...

Страница 9: ...ccess to other components during service CAUTION Do NOT push or place redundant cable length in the unit NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm 5...

Страница 10: ...nt Wires 2 0 75 1 25 mm Maximum length 500 m 2 9 Control 1 6 Room sensor offset Item Description in case of DHW tank 3 way valve See Installation manual of the 3 way valve Addendum book for optional e...

Страница 11: ...EKHWP HYC Tank with optional booster heater installed at the top of the tank Power consumption control settings On the user interface make sure to set 9 9 1 1 Power consumption control Continuous 9 9...

Страница 12: ...able legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit...

Страница 13: ...alve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent...

Страница 14: ...o the cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open...

Страница 15: ...nnect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF outp...

Страница 16: ...r consumption digital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3...

Страница 17: ...ork as expected The configuration influences the following The calculations of the software What you can see on and do with the user interface How You can configure the system via the user interface F...

Страница 18: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Страница 19: ...lly or by manual interaction When Emergency is set to Automatic and a heat pump failure occurs the backup heater automatically takes over the heat load and the booster heater in the optional tank take...

Страница 20: ...you can set the exact heater capacity and this will lead to more accurate energy data Code Description 9 4 1 6 02 Booster heater capacity kW Only applies to domestic hot water tank with an internal bo...

Страница 21: ...ase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled...

Страница 22: ...ng Tank Heat up mode Reheat only Comfort setpoint Only applicable when domestic hot water preparation is Schedule only or Schedule reheat When programming the schedule you can make use of the comfort...

Страница 23: ...mperature Y1 Y2 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water ta...

Страница 24: ...n zone WD curve type Viewing which type is selected is also possible via 3 C Additional zone WD curve type 5 E Tank WD curve type Restriction Only available to installers To change the weather depende...

Страница 25: ...an only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF conditi...

Страница 26: ...meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumpt...

Страница 27: ...unted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Страница 28: ...tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To mon...

Страница 29: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 8 Hand over to the user O...

Страница 30: ...ng diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Sh...

Страница 31: ...mostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermosta...

Страница 32: ...V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety...

Страница 33: ...tion signal 2 core signal 2 core signal 2 core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A1...

Страница 34: ......

Страница 35: ......

Страница 36: ...4P586453 1C 2020 10 Copyright 2019 Daikin 4P586453 1 C 00000003 Verantwortung f r Energie und Umwelt...

Отзывы: