5 Electrical installation
Installation manual
10
ETBH/9W
Daikin Altherma 3 H HT W
4P586453-1C – 2020.10
Item
Description
Heat pump convector
There are different controllers and
setups possible for the heat pump
convectors.
Depending on the setup, you also
need option EKRELAY1.
For more information, see:
▪ Installation manual of the heat
pump convectors
▪ Installation manual of the heat
pump convector options
▪ Addendum
book
for
optional
equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Remote outdoor
sensor
See:
▪ Installation manual of the remote
outdoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (
External sensor
=
Outdoor
)
[9.B.2]
Ext. amb. sensor offset
[9.B.3]
Averaging time
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset
Human Comfort
Interface
See:
▪ Installation and operation manual of
the Human Comfort Interface
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
Item
Description
(in case of DHW tank)
3‑way valve
See:
▪ Installation manual of the 3-way
valve
▪ Addendum
book
for
optional
equipment
Wires: 3×0.75 mm²
Maximum running current: 100 mA
[9.2]
Domestic hot water
(in case of DHW tank)
Domestic hot water
tank thermistor
See:
▪ Installation manual of the domestic
hot water tank
▪ Addendum
book
for
optional
equipment
Wires: 2
The thermistor and connection wire
(12 m) are delivered with the domestic
hot water tank.
[9.2]
Domestic hot water
(in case of DHW tank)
Power supply for
booster heater and
thermal protection
(from indoor unit)
See:
▪ Installation manual of the DHW
tank
▪ Addendum
book
for
optional
equipment
Wires: (4+GND)×2.5 mm²
[9.4]
Booster heater
(in case of DHW tank)
Power supply for
booster heater (to
indoor unit)
See:
▪ Installation manual of the domestic
hot water tank
▪ Addendum
book
for
optional
equipment
Wires: 2+GND
Maximum running current: 13 A
[9.4]
Booster heater
WLAN adapter
See:
▪ Installation manual of the WLAN
adapter
▪ Addendum
book
for
optional
equipment
Use the cable delivered with the
WLAN adapter.
[D]
Wireless gateway
LAN adapter
See:
▪ Installation manual of the LAN
adapter
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²). Must be
sheathed.
Maximum length: 200 m
See below ("LAN adapter – System
requirements").
Содержание ETBH16DF6V
Страница 34: ......
Страница 35: ......
Страница 36: ...4P586453 1C 2020 10 Copyright 2019 Daikin 4P586453 1 C 00000003 Verantwortung f r Energie und Umwelt...