Installation manual

6

ERQ125~250A7W1B

Inverter condensing unit

4PW51323-1D – 2022.10

3

Piping connections

(See figure 10)

Front connection:
Remove the stop valve cover to connect.

Bottom connection:
Remove the knock holes on the bottom frame and route the
piping under the bottom frame.

Processing the gas side accessory pipe (2)
Only in case of connecting at lateral side, cut the gas side
accessory pipe (2) as shown in 

figure 11

.

4

Piping length restrictions

4.1

Installation limitations

4.2

How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
R=(Total length (m) of liquid piping size at Ø9.5)x0.059
Determine the weight of refrigerant to be charged additionally
referring to the item 

"Additional refrigerant charge" on page 13

and fill in the amount on the fluorinated greenhouse gas label.

4.3

Diameters

6.5.

Protection against contamination when installing 
pipes

- Take measures to prevent foreign materials like moisture and 

contamination from mixing into the system.

- Great caution is needed when passing copper tubes through 

walls.

- Block all gaps in the holes for passing out piping and wiring 

using sealing material (field supply). (The capacity of the unit 
will drop and small animals may enter the machine.)
Example: passing piping out through the front

Precautions when connecting field piping.

Perform brazing at the gas stop valve before
brazing at the liquid stop valve.

Add brazing material as shown in the figure.

Be sure to use the supplied accessory pipes
when carrying out piping work in the field.

Be sure that the field installed piping does not
touch other pipes, the bottom panel or side panel.
Especially for the bottom and side connection, be
sure to protect the piping with suitable insulation,
to prevent it from coming into contact with the
casing.

A

Front connection
Remove the stop valve cover to connect.

B

Bottom connection:
Remove the knock holes on the bottom frame and route the piping 
under the bottom frame

1

Gas pipe stop valve

2

Liquid pipe stop valve

3

Service port for adding refrigerant

4

Gas side accessory pipe (1)

5

Gas side accessory pipe (2)

6

Liquid side accessory pipe (1)

7

Liquid side accessory pipe (2)

8

Brazing

9

Gas side piping (field supply)

10

Liquid side piping (field supply)

11

Punch the knockout holes (use a hammer)

1

Gas side accessory pipe

2

Cutting location

3

Gas side piping (field supply)

4

Base

Model

A

B

C

D

ERQ125

(mm)

166

16

199

246

ERQ200

(mm)

156

17

188

247

ERQ250

(mm)

156

23

192

247

NOTE

When connecting the piping on site, be sure to
use the accessory piping.

Make sure the onsite piping does not come into
contact with other piping, the bottom frame or side
panels of the unit.

1

Outdoor unit

2

Expansion valve kit

3

Air handling unit

Max (m)

Min (m)

L1

50

5

L2

5

A

–5 / +5

(a)

(a) Below or above the outdoor unit.

B

–30 / +30

(a)

Outdoor unit type

Piping size (mm)

Gas

Liquid

125

Ø15.9

Ø9.5

200

Ø19.1

Ø9.5

250

Ø22.2

Ø9.5

Installation period

Protection method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the period

After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak check.

L1

L2

A

B

1

2

3

1

2

3

1

Plug the areas marked with "

".

(When the piping is routed from the 
front panel.)

2

Gas side piping

3

Liquid side piping

Содержание ERQ200A7W1B

Страница 1: ...INSTALLATION MANUAL ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit...

Страница 2: ...e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a...

Страница 3: ...ne of the actions to achieve this is the reuse of reclaimed refrigerant in units produced and sold in Europe For more information about the countries that are in scope visit http www daikin eu loop by...

Страница 4: ...of sides A C have no impact on service space dimensions Refer to figure 2 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B h...

Страница 5: ...equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 3 In places with weak reception keep distances of 3 m or more to avoid electromagnet...

Страница 6: ...within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the...

Страница 7: ...nched piping 1 Remove the valve lid and make sure that the stop valves are fully closed 2 Connect a charge hose to service ports of all stop valves 3 Recover gas and oil from the pinched piping by usi...

Страница 8: ...ying out piping work in the field Be sure that the field installed piping does not touch other pipes the bottom panel or side panel Especially for the bottom and side connection be sure to protect the...

Страница 9: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Страница 10: ...rmistor discharge M1C M3C R50 R59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high SD1 Safety devices input T1A Current sensor...

Страница 11: ...und wires and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have t...

Страница 12: ...s plug the holes with packing materials to be prepared on site 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the weak low voltage electric wiring i e for the remote contr...

Страница 13: ...V 3N 50 Hz 2 Fuse 3 Earth leakage breaker 4 Grounding wire 5 Power supply terminal block 6 Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N 7 Ground wire GRN YLW 8 Clamp the power wi...

Страница 14: ...FRIGERANT The outdoor unit is factory charged but depending on the length of the piping when installed the outdoor unit may require additional charging For charging the additional refrigerant follow t...

Страница 15: ...it and installation conditions on page 12 are completed If the stop valve is left open without turning on the power it may cause refrigerant to build up in the compressor leading to insulation degrada...

Страница 16: ...Micro computer operation monitor Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c...

Страница 17: ...an insulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Cau...

Страница 18: ...d adjust the LED indication to either one of the possible settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip swit...

Страница 19: ...ons A additional refrigerant charging operation not applicable B refrigerant recovery operation vacuuming operation C setting of high static pressure D automatic low noise operation setting at nightti...

Страница 20: ...recting the abnormality Correcting after abnormal completion of the test operation The test operation is only completed if there is no malfunction code displayed on the remote controller In case of a...

Страница 21: ...ier than air Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the am...

Страница 22: ......

Страница 23: ...F2 1 6 5 4 C H SELECTOR TO IN D UNIT A1P 3 2 F1 F2 13 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 14 1 9 2 3 8 L1 L2 TO IN D F1 F2 A1P F1 F2 L N P1 P2 2 3 6 7 4 5 15 1 2 5 6 4 3 7 8 21 12 13 14 15 16 5 1 7 10...

Страница 24: ...4PW51323 1D 2022 10 Copyright 2009 Daikin 3...

Отзывы: